Regin RCFM-230D Instruction Download Page 2

RCFM-230D

2

Fan control

The fan can be controlled via RCFM-230D with the following modes: 
Low speed, Medium speed, High speed, Auto, Off. The current fan 
speed in the Auto mode depends on the deviation between the room 

 

temperature and the controlling setpoint. 
When using automatic control, ”AUTO” is shown in the display.
The number of fan speed steps can be selected via parameter 30. If 
the parameter is set to 1, the first fan speed step will be used for fan 
control. 
Via parameter 31, it is possible to set the fan to the lowest speed 
level when Auto mode is selected. If this parameter is set to 1, the fan 
will run in all operating modes except Off and Window (unless mould 
protection is active, in which case the fan will run in these modes as 
well). Fan kickstart can be utilised. The fan will then run at 100 % for 
a set time when starting up (0...10 seconds).

Manual control of the fan speed

By pressing the fan button, you change the fan speed according to 
the sequence I

à

II

à

III

à

AUTO

à

OFF. When using manual control, 

”MAN” is shown in the display. 
If the fan has been configured not to be affected by the heating or 
cooling demand, ”AUTO” will not be shown when pressing the fan 
button.

Blocking of manual fan control

When the fan has been configured not to run via parameter 25, it is 
possible to also prevent it from being controlled manually. Activation 
takes place via parameter 66.
Example: If the fan is configured to run only during cooling demand 
and this function has been activated, it will not be controllable during 
heating demand.

Indications

The display has the following indications:
HEAT   Heating control
COOL   Cooling control

 

The open window symbol is shown if this function has 

 

 

been configured and a window is open. 

OFF   The thermostat does not heat or cool

Blocking of buttons

The buttons of the thermostat can be blocked in order to prevent the 
settings from being changed by unauthorized individuals. It is possible 
to either block only some buttons or, if desired, all of them. Activation 
takes place via parameter 65. 
The INCREASE and DECREASE button combination will always 
remain active in order for the configuration menu to be reachable.

Shutting off the thermostat

By pressing the fan button, you switch between the different fan speeds. 
In the Off mode, the thermostat’s other functions are shut off.

Parameter list

When the thermostat is in Comfort mode or Window mode, different
parameter values can be set in a parameter list.
Hold the INCREASE and DECREASE buttons depressed simultaneously 
for about 5 seconds until the Service symbol is displayed and then press 
the INCREASE button twice.
First the display will show parameter 1. Use the INCREASE and DE

-

CREASE buttons to scroll between the parameters and press the fan 
button to select the desired parameter. The parameter number will then 
be replaced by the parameter value. The value can be changed using the 
INCREASE and DECREASE buttons. If a button is held depressed the 
value will start scrolling, first slowly and then with increasing speed.
To exit the parameter list and go back to the basic display, press the 
INCREASE button until “EXIT” is shown (one step before parameter 1) 
and press the fan button. You can also exit the parameter list by pressing 
down the INCREASE and DECREASE buttons simultaneously.

Parameters

The following parameters can be changed in the parameter list.

Nº = parameter number
FS = factory setting
NO = normally open
NC = normally closed

Description

FS

1

Control mode:
2=2-pipe system

 

3=4-pipe system 

(not used for this model)

4=Electric heater 

(not used for this model)

2

2

Not used for this model

3

Operating mode when activating digital input 1:
0=Economy mode (occupancy 

d

etector)

1=Off mode (window contact)

0

4

Mould protection:
0=Not active
1=Active (fan never stops)

0

5

Deadband at Comfort mode. If the deadband is 
2 K, the heating setpoint is equal to the setpoint 
minus 1 and the cooling setpoint is equal to the 
setpoint plus 1.

2 K

6

Heating setpoint when unoccupied.

15°C

Description

FS

7

Cooling setpoint when unoccupied.

30°C

8-9

Not used for this model

10

Hysteresis (ΔT).

1 K

11

Switch off timer for Comfort mode.

0 min

12

Switch on delay for Comfort mode.

0 min

13

Sensor connected to AI1:
0=Internal sensor, 1=External room sensor, 
11=Supply air limitation sensor

0

14-
21

Not used for this model

22

Time in hours between exercise of heating actua

-

tor.

23

23

Time in hours between exercise of cooling actua

-

tor.

23

24

Setpoint or actual value shown in the display: 
0=Actual, setpoint when changing the setpoint, 
1=Actual value, setpoint adjustment when setpoint 
adjustment is altered, 2=Setpoint, 3=Only the 
setpoint adjustment

2

25

Configuration of fan control:
0=No control, 1=The fan is controlled by the heat

-

ing requirement, 2=The fan is controlled by the 
cooling requirement, 3=The fan is controlled by 
the heating and cooling requirement
When using an electric heater, this parameter 
should only be set to 1 or 3, or the heater may be 
overheated.

3

26-
29

Not used for this model

30

Number of fan speeds.

3

31

Fan speed in the Auto mode:

 

0=The fan speed follows the cooling/heating 
output, 1=The fan speed is minimum limited to 

the lowest speed

1

32

Temperature compensation on AI1.

0 K

33

Temperature compensation for the internal room 
sensor.

0 K

34

Highest permitted setpoint offset upwards. Set

-

table value=0...13 K. Starting point=22°C.

13 K

35

Highest permitted setpoint offset downwards. Set

-

table value=0...17 K. Starting point=22°C.

17 K

Summary of Contents for RCFM-230D

Page 1: ...ction box so that the arrows on the bottom plate point upwards Do not tighten the screws too hard Disconnection RCFM 230D should be connected to a switch or circuit breaker in the building installation This switch should be in close proximity to the ther mostat and within easy reach of the operator and should be marked as the disconnecting device for the equipment Always use the circuit breaker to...

Page 2: ...play will show parameter 1 Use the INCREASE and DE CREASE buttons to scroll between the parameters and press the fan button to select the desired parameter The parameter number will then be replaced by the parameter value The value can be changed using the INCREASE and DECREASE buttons If a button is held depressed the value will start scrolling first slowly and then with increasing speed To exit ...

Page 3: ...up 0 10 seconds 0 s 70 Supply air temperature max limitation for cascade control and heating control 35 C 71 Supply air temperature min limitation for cascade control and heating control 24 C 72 Supply air temperature max limitation for cascade control and cooling control 24 C 73 Supply air temperature min limitation for cascade control and cooling control 12 C 74 Cascade factor between room contr...

Page 4: ... arbetsbrytare för att termostaten ska kunna göras spänningslös Denna brytare ska mon teras i termostatens närhet och lätt kunna nås av operatören Den ska tydligt märkas som brytare för termostaten RCFM 230D måste alltid göras spänningslös vid underhåll på fan coil enheten och ställdonen Inställningar Reglerfall RCFM 230D har via en knapp på termostaten säsongsvis omställn ing mellan värme och kyl...

Page 5: ... via parameter 65 Kombinationen ÖKA MINSKA knapp kommer alltid att vara aktiv för att man ska kunna nå konfigureringsmenyn Avstängning av termostaten Genom att trycka på fläktknappen växlar man mellan de olika fläkt hastigheterna Frånläget innebär att termostatens övriga funktioner är avstängda Parameterlista När termostaten befinner sig i Komfort eller Fönsterläge går det att ställa in olika para...

Page 6: ...nställning aktiva knappar 0 Inga aktiva knappar 1 Bara fläktknapp aktiv 2 Bara ÖKA MINSKA knappar aktiva 3 ÖKA MINSKA och fläktknapp aktiva 4 Bara M knapp aktiv 5 Fläkt och M knappar aktiva 6 ÖKA MINSKA och M knappar aktiva 7 Alla knappar aktiva 7 66 Funktion för att förhindra användare från att ställa in manuell fläkthastighet om fläkten inte ska gå p g a kyl värmeutstyrning enligt parameter 25 0...

Page 7: ... www regincontrols com info regin se ANLEITUNG i Anleitung für Produkte mit Softwarestand 1 4 und neuer Diese Montageanleitung vor Installation und Anschluss des Produktes bitte durchlesen Dieses Symbol macht auf eventuelle Gefahren bei der Handhabung des Produkts und in der Dokumentation nachzulesende Maßnahmen aufmerksam DE RCFM 230D Raumthermostat für Fan Coil Anlagen RCFM 230D ist ein Raumther...

Page 8: ...CREASE eingestellt Mit Parameter 24 wird festgelegt was im Basisdisplay angezeigt wird Für genauere Informa tionen siehe Parameterliste Der Basissollwert wird über Parameter 64 eingestellt Ventilatorregelung Für die Ventilatoransteuerung hat RCFM 230D folgende Alternativen Stufe I niedrig Stufe II mittel Stufe III hoch Auto Aus Die aktuelle Ventilatorstufe Auto ist abhängig von der Abweichung zwis...

Page 9: ...fs 3 Ansteuerung in Abhängigkeit des Heiz Kühlbedarfs Bei Verwendung eines elektrischen Erhitzers sollte der Parameter nur auf 1 oder 3 eingestellt werden Ansonsten kann es zu einer Überhitzung kommen 3 26 29 Nicht für dieses Modell gültig 30 Anzahl Ventilatorstufen 3 31 Ventilatorstufe in Auto 0 Folgt dem Heiz Kühlstellsignal 1 Ventilator betrieb mit Grundstufe 1 32 Temperaturkorrektur an AI1 0 K...

Page 10: ... für Ventilatoran steuerung Relais 230 V AC 3 A 30 Nicht verbunden 31 DO4 Digitalausgang 4 Heizen Kühlen Digitalausgang 230 V AC max 300 mA Max 2 A für 20 ms 32 CDO45 Referenzpunkt für DO4 5 Gemeinsamer Anschluss für Digitalausgänge 4 5 33 Nicht verbunden 40 DI Digitaleingang Potenzialfreier Fenster oder Präsenzkontakt Einstellbar als NO NG 41 0 V Analoge Masse 42 AI Analogeingang Externer PT1000 ...

Page 11: ...auffage et d un mode Refroidisse ment qui fonctionnent en fonction d un changement saisonnier fonction change over Le changement se fait l aide d un bouton La régulation en cascade et la limitation minimale maximale du soufflage est également possible Fonction change over Sur RCFM 230D la fonction change over est commandée par le bouton M situé à côté de l écran Ce bouton vous permet de choisir si...

Page 12: ...appuyé les chiffres se mettent à défiler d abord lentement puis plus vite Pour quitter la liste des paramètres et revenir l écran d accueil appuyer sur la touche AUGMENTER jusqu à ce que EXIT s affiche à l écran juste avant le paramètre 1 puis appuyer sur le bouton Ventilateur Vous pouvez aussi appuyer simultanément sur les touches AUGMENTER DIMINUER Paramètres Les paramètres suivants peuvent être...

Page 13: ...t bou ton M actifs 7 Tous les boulons sont actifs 7 Nº Description RU 66 Fonction destinée à empêcher l utilisateur de régler la vitesse du ventilateur manuellement si celui ci ne doit pas fonctionner en raison de la sortie refroidissement chauffage comme indiqué au paramètre 25 0 Inactive 1 Active 0 67 Sans objet pour ce modèle 68 Sans objet pour ce modèle 69 Relance du ventilateur Le ventilateur...

Page 14: ... dant 20 ms 32 CDO45 Neutre DO4 5 Neutre pour les sorties digi tales 4 et 5 33 Non utilisé 40 DI Entrée digitale Contact libre de potentiel pour un contact de fenêtre ou un détecteur de présence Configurable sur NO NF 41 0 V Commun analo gique 42 AI Entrée analogique Sonde d ambiance PT1000 externe à la place de la sonde NTC interne ou de la sonde de soufflage pour la limitation minimale maximale ...