Regin RCFM-230D Instruction Download Page 1

INSTRUCTION

 

RCFM-230D

1

i

Consult documentation in all cases where this symbol 

is used, in order to find out the nature of the potential 

hazards and any actions to be taken.

Instruction for products with software version 

1.4. 

Read this instruction before installation and 

wiring of the product.

RCFM-230D

Room thermostat for controlling fan-coil units

RCFM-230D is a room thermostat intended for controlling fan-coil 

heaters/coolers with on/off, thermostat function. Installation is directly 
on the wall or on an electrical connection box. The thermostat does 
not have a communication connection. The fan can be set to one of 
three speeds.
RCFM-230D has change-over function and should be used for 2-pipe 
systems.

Technical data

Supply voltage 

 

230 V AC ±10 %, 50/60 Hz

Power consumption 

< 3 W

Ambient temperature 

0...50°C

Ambient humidity   

Max 90 % RH

Storage temperature  

-20...+70°C

Built-in temperature sensor  NTC type, range 0...50°C

Inputs   

 

Refer to connection illustrations and    

 

 

 

table below 

Outputs  

 

Relays for fan control, 230 V AC, 3 A

 

 

 

 

DO4 for actuators, Triac, 230 V AC, 

 

 

 

 

max. 300 mA (3 A initially)

Terminal blocks    

Lift type (maximum cable area 2.1 mm

2

)

Protection class    

IP20

 

Pollution degree   

2

 

Overvoltage category 

3

Material casing    

Polycarbonate, PC

Dimensions  

 

102 x 120 x 29 mm

Installation

Place the thermostat in a location that has a temperature representative 
for the room. A suitable location is approx. 1.6 m above floor level in a 
place with unobstructed air circulation. 
Depress the locking tab in the upper edge of the thermostat with a 

screwdriver

. Carefully turn the screwdriver until the bottom plate and the 

electronics unit are slightly separated (see figure 1). Then use the cutout 
that becomes visible in the edge of the bottom plate to open the upper 
edge completely (see figure 2). Do the same thing in the lower edge of the 
thermostat.

 

Figure 1

Figure 2

Lift the electronics unit up from the bottom plate. The bottom plate with 
terminals has a number of hole combinations. Select suitable holes and 
fasten the bottom plate on the wall or connection box, so that the arrows 
on the bottom plate point upwards. Do not tighten the screws too hard!

 Disconnection

RCFM-230D should be connected to a switch or circuit breaker in the 
building installation. This switch should be in close proximity to the ther

-

mostat and within easy reach of the operator, and should be marked as 
the disconnecting device for the equipment.

Always use the circuit breaker to disconnect the thermostat from the 
mains supply during maintenance of the fan-coil and actuators.

Settings

Control modes

RCFM-230D has, via a button on the thermostat, seasonal switch

-

ing between heating and cooling (change-over, see below). Cascade 
control and min/max limitation of the supply air is also possible.

Change-over function

RCFM-230D has a function for change-over via the M button on the 
thermostat. By pressing the M button, you choose whether output 
DO4 should operate with heating or cooling function.

Operating mode

There are four different operating modes. Switching between these 

modes is performed 

locally.

Comfort: 

 is shown in the display. Heating and cooling have a 

smaller 

neutral zone NZC. Switching between Comfort/Economy and 

Off is done via the fan button. Comfort/Economy is selected via the 
parameter list and can be controlled by input DI.

Economy (Standby):

 “Standby” is shown in the display. The heat

-

ing and cooling setpoints are freely adjustable. Factory settings: 
heating=15°C, cooling=30°C.

Off:

 The thermostat does not heat or cool and the fan stops (unless 

mould protection has been selected, in which case the fan will still 
run).

Window: 

 

  is shown in the display, the thermostat is off and the fan 

stops (unless mould protection is active, in which case the fan will run 
in this mode as well). The window contact is connected to the DI and 
must be configured.

Occupancy detection/window contact

Parameter 3 determines if the DI is window contact input or 

 

occupancy detection input. An occupancy detector can be connected 
to the DI in order to switch between Comfort and Economy mode.

Setpoint

The setpoint displacement is set using the INCREASE and DE

-

CREASE buttons. Parameter 24 determines what is shown in the 
display. Refer to the parameter list for details. The basic setpoint is 
set via parameter 64.

7434N

 

APR 16

EN

Summary of Contents for RCFM-230D

Page 1: ...ction box so that the arrows on the bottom plate point upwards Do not tighten the screws too hard Disconnection RCFM 230D should be connected to a switch or circuit breaker in the building installation This switch should be in close proximity to the ther mostat and within easy reach of the operator and should be marked as the disconnecting device for the equipment Always use the circuit breaker to...

Page 2: ...play will show parameter 1 Use the INCREASE and DE CREASE buttons to scroll between the parameters and press the fan button to select the desired parameter The parameter number will then be replaced by the parameter value The value can be changed using the INCREASE and DECREASE buttons If a button is held depressed the value will start scrolling first slowly and then with increasing speed To exit ...

Page 3: ...up 0 10 seconds 0 s 70 Supply air temperature max limitation for cascade control and heating control 35 C 71 Supply air temperature min limitation for cascade control and heating control 24 C 72 Supply air temperature max limitation for cascade control and cooling control 24 C 73 Supply air temperature min limitation for cascade control and cooling control 12 C 74 Cascade factor between room contr...

Page 4: ... arbetsbrytare för att termostaten ska kunna göras spänningslös Denna brytare ska mon teras i termostatens närhet och lätt kunna nås av operatören Den ska tydligt märkas som brytare för termostaten RCFM 230D måste alltid göras spänningslös vid underhåll på fan coil enheten och ställdonen Inställningar Reglerfall RCFM 230D har via en knapp på termostaten säsongsvis omställn ing mellan värme och kyl...

Page 5: ... via parameter 65 Kombinationen ÖKA MINSKA knapp kommer alltid att vara aktiv för att man ska kunna nå konfigureringsmenyn Avstängning av termostaten Genom att trycka på fläktknappen växlar man mellan de olika fläkt hastigheterna Frånläget innebär att termostatens övriga funktioner är avstängda Parameterlista När termostaten befinner sig i Komfort eller Fönsterläge går det att ställa in olika para...

Page 6: ...nställning aktiva knappar 0 Inga aktiva knappar 1 Bara fläktknapp aktiv 2 Bara ÖKA MINSKA knappar aktiva 3 ÖKA MINSKA och fläktknapp aktiva 4 Bara M knapp aktiv 5 Fläkt och M knappar aktiva 6 ÖKA MINSKA och M knappar aktiva 7 Alla knappar aktiva 7 66 Funktion för att förhindra användare från att ställa in manuell fläkthastighet om fläkten inte ska gå p g a kyl värmeutstyrning enligt parameter 25 0...

Page 7: ... www regincontrols com info regin se ANLEITUNG i Anleitung für Produkte mit Softwarestand 1 4 und neuer Diese Montageanleitung vor Installation und Anschluss des Produktes bitte durchlesen Dieses Symbol macht auf eventuelle Gefahren bei der Handhabung des Produkts und in der Dokumentation nachzulesende Maßnahmen aufmerksam DE RCFM 230D Raumthermostat für Fan Coil Anlagen RCFM 230D ist ein Raumther...

Page 8: ...CREASE eingestellt Mit Parameter 24 wird festgelegt was im Basisdisplay angezeigt wird Für genauere Informa tionen siehe Parameterliste Der Basissollwert wird über Parameter 64 eingestellt Ventilatorregelung Für die Ventilatoransteuerung hat RCFM 230D folgende Alternativen Stufe I niedrig Stufe II mittel Stufe III hoch Auto Aus Die aktuelle Ventilatorstufe Auto ist abhängig von der Abweichung zwis...

Page 9: ...fs 3 Ansteuerung in Abhängigkeit des Heiz Kühlbedarfs Bei Verwendung eines elektrischen Erhitzers sollte der Parameter nur auf 1 oder 3 eingestellt werden Ansonsten kann es zu einer Überhitzung kommen 3 26 29 Nicht für dieses Modell gültig 30 Anzahl Ventilatorstufen 3 31 Ventilatorstufe in Auto 0 Folgt dem Heiz Kühlstellsignal 1 Ventilator betrieb mit Grundstufe 1 32 Temperaturkorrektur an AI1 0 K...

Page 10: ... für Ventilatoran steuerung Relais 230 V AC 3 A 30 Nicht verbunden 31 DO4 Digitalausgang 4 Heizen Kühlen Digitalausgang 230 V AC max 300 mA Max 2 A für 20 ms 32 CDO45 Referenzpunkt für DO4 5 Gemeinsamer Anschluss für Digitalausgänge 4 5 33 Nicht verbunden 40 DI Digitaleingang Potenzialfreier Fenster oder Präsenzkontakt Einstellbar als NO NG 41 0 V Analoge Masse 42 AI Analogeingang Externer PT1000 ...

Page 11: ...auffage et d un mode Refroidisse ment qui fonctionnent en fonction d un changement saisonnier fonction change over Le changement se fait l aide d un bouton La régulation en cascade et la limitation minimale maximale du soufflage est également possible Fonction change over Sur RCFM 230D la fonction change over est commandée par le bouton M situé à côté de l écran Ce bouton vous permet de choisir si...

Page 12: ...appuyé les chiffres se mettent à défiler d abord lentement puis plus vite Pour quitter la liste des paramètres et revenir l écran d accueil appuyer sur la touche AUGMENTER jusqu à ce que EXIT s affiche à l écran juste avant le paramètre 1 puis appuyer sur le bouton Ventilateur Vous pouvez aussi appuyer simultanément sur les touches AUGMENTER DIMINUER Paramètres Les paramètres suivants peuvent être...

Page 13: ...t bou ton M actifs 7 Tous les boulons sont actifs 7 Nº Description RU 66 Fonction destinée à empêcher l utilisateur de régler la vitesse du ventilateur manuellement si celui ci ne doit pas fonctionner en raison de la sortie refroidissement chauffage comme indiqué au paramètre 25 0 Inactive 1 Active 0 67 Sans objet pour ce modèle 68 Sans objet pour ce modèle 69 Relance du ventilateur Le ventilateur...

Page 14: ... dant 20 ms 32 CDO45 Neutre DO4 5 Neutre pour les sorties digi tales 4 et 5 33 Non utilisé 40 DI Entrée digitale Contact libre de potentiel pour un contact de fenêtre ou un détecteur de présence Configurable sur NO NF 41 0 V Commun analo gique 42 AI Entrée analogique Sonde d ambiance PT1000 externe à la place de la sonde NTC interne ou de la sonde de soufflage pour la limitation minimale maximale ...