Regin RCF-230AD Instructions Manual Download Page 1

INSTRUCTION

 

RCF-230AD

i

Instruction for products manufactured from 

May 2010. Read this instruction before  

installation and wiring of the product.

Consult documentation in all cases where this symbol 

is used, in order to find out the nature of the potential 

hazards and any actions to be taken

1

RCF-230AD

Room controller for controlling fan-coil units

RCF-230AD is a room controller intended for controlling fan-coil heat-

ers/coolers and actuators with 0...10 V control signal. Installation is 

directly on the wall or on an electrical connection box. The controller 

does not have a communication connection. The fan can be set to 

one of three speeds.

RCF-230AD has change-over function and can be used for 2-pipe or 

4-pipe systems.

Technical data

Supply voltage 

 

230 V AC ±10 %, 50/60 Hz

Power consumption 

3 W

Ambient temperature 

0...50°C

Ambient humidity   

Max 90 % RH

Storage temperature  

-20...+70°C

Built-in temperature sensor  NTC type, range 0...50°C

Inputs   

 

Refer to connection illustrations and    

  

 

 

table  below 

Outputs  

 

Relays for fan control, 230 V AC, 3 A 

 

 

 

AO1, AO2, 0...10 V DC

Terminal blocks    

Lift type for a maximum cable area 2.1 mm

2

Protection class    

IP20 

Pollution degree   

Overvoltage category 

3

Material casing    

Polycarbonate, PC

Dimensions  

 

102 x 120 x 29 mm

Installation

Place the controller in a location that has a temperature representative for 

the room. A suitable location is approx. 1.6 m above floor level in a place 

with unobstructed air circulation. 
Depress the locking tab in the upper edge of the controller with a 
screwdriver. Carefully turn the screwdriver until the bottom plate and the 

electronics unit are slightly separated. See figure 1. Then 

use the cutout 

that becomes visible in the edge of the bottom plate to open the upper 

edge completely. See figure 2. Do the same thing in the lower edge of the 

controller. 

Figure 1

Figure 2

Lift the electronics unit up from the bottom plate. The bottom plate with 
terminals has a number of hole combinations. Select suitable holes and 
fasten the bottom plate on the wall or connection box, so that the arrows 
on the bottom plate point upwards. Do not tighten the screws too hard!

 Disconnection

RCF-230AD should be connected to a switch or circuit breaker in the 
building installation. This switch should be in close proximity to the con-
troller and within easy reach of the operator, and should be marked as the 
disconnecting device for the equipment.
Always use the circuit breaker to disconnect the controller from the mains 
supply during maintenance of the fan-coil and actuators.

Settings

Control modes

RCF-230AD has control modes Heating and Cooling in sequence or  
seasonal switching between heating and cooling (change-over, see 
below).

Change-over function

RCF-230AD has an input for change-over that automatically sets the 
output AO1 to operate with heating or cooling function. A sensor of 
type PT1000 can be connected to the input and must be mounted so 
that it senses the temperature on the supply pipe to the coil.
When the temperature exceeds 28°C, the output function is set to 
heating and when the temperature drops below 16°C, the output is 
set to cooling. As an alternative, a potential-free contact can be used. 
The input function can be set to NO/NC.
To ensure satisfactory functioning using sensor, the system must 
have continuous primary circuit circulation. When the change-over 
function is not used, the input must be left disconnected.

Operating mode

There are four different operating modes. Switching between these 
modes is performed locally.

Comfort: 

 is shown in the display, heating and cooling have a 

smaller neutral zone NZC. An occupancy detector can be connected 
to the DI in order to select between Comfort and Economy. Switching 
between Comfort/Economy and Off can also be done via the On/Off 
button. Comfort/Economy is selected via the parameter list.

Economy (Standby):

 “Standby” is shown in the display. The heat-

ing and cooling setpoints are freely adjustable. Factory settings: 
heating=15°C, cooling=30°C.

Off:

 The controller does not heat or cool and the fan is inactive, un-

less mould protection has been selected, in which case the fan will 
still run.

Window: 

   is shown in the display, the controller is in Off mode but 

the display is still lit. The window contact is connected to the DI and 

must be configured.

Occupancy detection

Parameter 3 determines if the DI is window contact input or 
occupancy detection input. An occupancy detector can be connected 
to the DI in order to switch between Comfort and Economy mode.

Setpoint

The setpoint is set using the INCREASE and DECREASE buttons. 
Parameter 24 determines what is shown in the display. Refer to the 
parameter list for details. When the setpoint adjustment is shown, the 
basic setpoint is 22°C. 

7436J

 

NOV 12

EN

Summary of Contents for RCF-230AD

Page 1: ...oximity to the con troller and within easy reach of the operator and should be marked as the disconnecting device for the equipment Always use the circuit breaker to disconnect the controller from the mains supply during maintenance of the fan coil and actuators Settings Control modes RCF 230AD has control modes Heating and Cooling in sequence or seasonal switching between heating and cooling chan...

Page 2: ... press the IN CREASE button until EXIT is shown one step before parameter 1 and press the On Off button You can also exit the parameter list by pressing down the INCREASE and DECREASE buttons simultaneously Parameters The following parameters can be changed in the parameter list Para meter number Description FS factory setting 1 Control mode 2 2 pipe system 3 4 pipe system 4 Electric heater not va...

Page 3: ...lly open NC normally closed Wiring 10 20 30 LOGIC 40 50 POWER Bottom plate connections Connection diagrams for RCF 230AD 10 L 230 V AC Line Power supply 11 NC Not connected 12 N 230 V AC Neutral Power supply internally con nected to terminal 13 13 N Fan coil common 230 V AC Neutral Common fan coil connec tor internally connected to terminal 12 20 DO1 Fan coil output 1 for fan control Relay 230 V A...

Page 4: ... och SÄNKA knapparna Parameter 24 bestämmer vad som visas i displayen Se parameterlistan för detaljer Då man väljer att börvärdesförskjutningen ska visas är grundbörvär det 22 C Börvärdesbegränsning I parameter 34 och 35 går det att ställa in den maximalt tillåtna höjnin gen respektive minskningen av börvärdet Exempel Om P35 5 och P34 3 kan börvärdet ändras mellan 17 C och 25 C se nedanstående bil...

Page 5: ...är värmebörvärdet lika med börvärdet minus 1 och kylbörvärdet lika med börvärdet plus 1 2 K 6 Värmebörvärde vid frånvaro 15 C 7 Kylbörvärde vid frånvaro 30 C 8 P band för rumsregulatorn 10 K 9 I tid för rumsregulatorn 300 s 10 Gäller ej denna modell 11 Frånslagstimer för Komfortläge 0 min 12 Tillslagsfördröjning för Komfortläge 0 min 13 Givare ansluten till AI1 0 Intern givare 1 Extern rumsgivare ...

Page 6: ...Relä 230 V AC 3 A 21 DO2 Fan coil utgång 2 för fläktstyrning Relä 230 V AC 3 A 22 DO3 Fan coil utgång 3 för fläktstyrning Relä 230 V AC 3 A 30 33 NC Ej ansluten 40 DI Digital ingång Potentialfri fönsterkontakt el ler närvarokontakt Konfigur erbar för NO NC 41 0 V Analog jord 42 AI Analog ingång Extern PT1000 istället för intern NTC 43 UI Universell ingång Change over ingång Poten tialfri omkopplar...

Page 7: ...RCF 230AD verfügt über die Regelmodi Heizen und Kühlen in Sequenz oder jahreszeitliches Umschalten zwischen Heizen und Kühlen Change Over siehe unten Change Over Funktion RCF 230AD hat einen Change Over Eingang der den Ausgang AO1 je nach Bedarf automatisch auf Heizen oder Kühlen umstellt An den Eingang kann ein Pt1000 Fühler angeschlossen werden der so montiert werden muss dass die Vorlauftempera...

Page 8: ...iste geändert werden Para meter nummer Beschreibung Werks einstellung WE 1 Regelmodus 2 2 Rohr System 3 4 Rohr System 4 Elektr Erhitzer nicht gültig für dieses Modell 3 2 Change Over 0 Regelung Heizen 1 Regelung Kühlen 2 Automatischer Change Over über analo gen Temperaturfühler oder Digitaleingang 2 3 Betriebsmodus bei aktiviertem DI 1 0 Eco Präsenz 1 Abschaltbetrieb Fenster 0 4 Schimmelschutzfunk...

Page 9: ...ter Fan Coil 230 V AC Gemeinsamer Fan Coil Anschluss intern mit Klemme 12 verbunden 20 DO1 Fan Coil Ausgang 1 für Ventilator ansteuerung Relais 230 V AC 3 A 21 DO2 Fan Coil Ausgang 2 für Ventilator ansteuerung Relais 230 V AC 3 A 22 DO3 Fan Coil Ausgang 3 für Ventilator ansteuerung Relais 230 V AC 3 A 30 33 Nicht verbunden 40 DI Digitaleingang Potenzialfreier Fenster oder Präsenzkontakt Einstellba...

Page 10: ...pose d un mode Chauffage et d un mode Refroidisse ment qui fonctionnent soit en séquence soit en fonction d un changement saisonnier fonction change over Fonction change over RCF 230AD est doté d une entrée pour la fonction change over Cette dernière permet d utiliser la sortie AO1 pour commander soit le chauffage soit le refroidissement en fonction du besoin Cette entrée peut aussi être raccordée...

Page 11: ...nez le bouton appuyé les chiffres se mettent à défi ler d abord lentement puis plus vite Pour quitter la liste des paramètres et revenir l écran d accueil appuyez sur la touche AUGMENTER jusqu à ce que EXIT s affiche à l écran juste avant le paramètre 1 puis appuyez sur le bouton de marche arrêt Vous pouvez aussi appuyer simultanément sur les touches AUGMEN TER DIMINUER Paramètres Les paramètres s...

Page 12: ...ante interne 0 K 34 Ajustement maximum autorisé de la valeur de consigne vers le haut augmenter Réglable 0 13 K Valeur de la consigne par défaut 22 C 13 K 35 Ajustement maximum autorisé de la valeur de consigne vers le bas diminuer Réglable 0 17 K Valeur de la consigne par défaut 22 C 17 K 36 État de l entrée digitale 1 DI1 NO NF 0 NO 1 NC 0 37 État de l entrée universelle 1 UI1 NO NF 0 NO 1 NC 0 ...

Page 13: ... tiel configurable NO NF ou PT1000 44 0 V Terre analogique 50 0 V Terre analogique 51 AO1 Sortie analogique 1 52 AO2 Sortie analogique 2 53 NC Réservé pour une utilisation future 54 NC Réservé pour une utilisation future Protection par fusible équivalent à la somme des courants entre DO1 DO3 Sécurité électrique et EMC Ce produit est conforme aux exigences du standard européen EN60730 1 2 9 et port...

Reviews: