
3137F SEPT
15
PULSER HC-LON
Box 116 428 22 KÅLLERED SWEDEN
Tel +46 (0)31 720 02 00 Fax +46 (0)31 720 02 50
INSTRUCTIONS
INSTRUCTIONS
Triac Controller for Proportional Control of
Electric Heating and Cooling
Pulser HC-LON
controls the temperature in a room control-
ling heating and cooling in sequence. The controller can
work either with internal sensor, external values taken from
sensors in the room or values taken from a Local Operating
Network (LON). There is a built-in potentiometer for setpoint
displacement. The controller works proportionally - the ratio
between on-time and off-time is varied to suit the prevailing
heat demand.
Mounting
Remove the front, the screw is located behind the set-point
knob. Mount the device vertically with the cooling flange
at the top. Use screws with a maximum head diameter of
5.5mm.
If
Pulser HC-LON
is to be used with the internal sensor, it
should be mounted about 1.5m above the floor at a location
with representative temperature for the room. It is essential
that air can flow around the device without hinderance from
furniture or doors.
Pulser HC-LON
emits about 10W which must be dissipa-
ted. Maximum ambient temperature at full load is +30°C.
Ambient temperature: 0 to +30°C non-condensing.
Protection class: IP20.
Electrical Installation
The installation has to be carried out by a qualified profes
-
sional and in accordance with applicable directives.
The supply voltage must be wired via a fully isolating
switch with a contact gap of at least 3 mm,
Supply voltage: 200...250 V AC, 50...60 Hz connects to
terminal block J3, terminals 13 and 14 (fig 1).
The load is connected between terminals 15 and 16 in
terminal block J3 according to fig 1.
Maximum load:
2300 W at 230 V AC, 10 A.
Minimum load:
230 W at 230 V AC, 1 A.
The cooling flange is live!
Terminal block J1 which is for voltages of 24 V AC and
sensors is presented later in this document.
Control Principle
Pulser HC-LON
pulses the full load. It adjusts the mean
power output to the prevailing power demand by propor-
tionally adjusting the ratio between on-time and off-time.
The pulse period (sum of on- and off-time) is constant
60s.
To eliminate radio frequency interference the device has
zero phase-angle firing.
There are four ways of configuring the output from
Pulser
HC-LON.
1:
230 V AC heating (fig 1).
Heating by triac control but no cooling
2:
230 V AC heating (fig 1).
24 V AC 3-point (increase/decrease) cooling (fig 5).
Heating by triac control and cooling by a valve with
3-point control.
3:
230 V AC heating (fig 1).
24 V AC thermo cooling (fig 6).
Heating by triac control and cooling by a valve with
thermal actuator 24 V AC.
4:
24 V AC thermo heating (fig 7).
24 V AC thermo cooling (fig 7).
Both heating and cooling by one 24 V AC thermal
actuator output each.
150
94
43
Read this instruction before installation
and wiring of the product
Consult documentation in all cases where this
symbol is used, in order to find out the nature of
the potential hazards and any actions to be taken
i
Fig 2
Fig 1
Fig 3
a
b
c
d
16
15
14
13
J1
CN1
J3