PULSER-ADD

Triac controller for proportional control 

of electric heating, add-on unit

PULSER-ADD is a complete proportional controller for electric 
heating. It has automatic voltage adjustment. It has no sensor input 
but is intended to be controlled by another PULSER unit.
PULSER-ADD is only intended for electric heating control. The con-
trol principle makes it unsuitable for motor- or lighting control.
PULSER-ADD cannot  control 3-phase loads.

Installation

Remove the front. The locking screw is behind the set-point knob. 

Mount PULSER‑ADD vertically with the cooling flange at the top. Use 

screws with a maximum head diameter of 5.5mm.

 PULSER-ADD emits approx. 20W of heat which must be dis-

sipated. Ambient temp.: 0 - 30°C, non-condensing.
Protection class: IP20.

Wiring

Supply voltage

Terminals 1 and 2. Not polarity sensitive.
Supply voltage: 200 - 415V AC, 50 - 60 Hz with automatic voltage 
adjustment. Maximum current 16A.

Control principle

PULSER‑ADD pulses the full load On ‑ Off parallel to the master unit 

it is connected to.

PULSER‑ADD has zero phase‑angle firing to eliminate RFI.

Start-up and fault finding

 Be careful when working in the PULSER-ADD. All internal 

components including the cooling flange are at line voltage potential. 

Never leave the unit under power without the front cover on.

1.  Check that all wiring is correct.
2.  Measure the resistance between terminals 3 - 4: At 230V: 

14.4

<R<230

.  At 400V:25

<R<400

.

3.  Connect supply voltage and twist the setpoint knob of the master 

unit between end stops. Check that the LED which can be seen 

through the underside of PULSER‑ADD goes on and off at the 

same time as the LED of the master unit. Check with a clamp-on 

ammeter that current is flowing to the heater.

Anything wrong?

1.  Disconnect supply power. Remove the control signal wiring from 

terminals I and I. Reconnect power. The LED should be continu-

ously off and no current should flow to the heater. Disconnect 

power and connect the terminals I and I to the terminals 1 and 2. 
Reconnect power. The LED should be continuously on and full 

current should flow to the heater.

2.  If everything is OK this far the PULSER-ADD is OK and the fault 

must be found elsewhere.

This product carries the CE mark.  

For more information, see www.regincontrols.com.

Contact

AB Regin, Box 116, 428 22 Kållered, Sweden 

Tel: +46 31 720 02 00, Fax: +46 31 

www.regin.se, [email protected]

1882H

 

MA

Y 19

EN

    

I I

1 2 U 3 4 U

Figure 1: Wiring of supply voltage and load

 The supply voltage to PULSER-ADD should be wired via an all-pole 

switch with a minimum contact gap > 3mm. The cooling flange is live.

Load

Terminals 3 and 4.
Resistive single- or two-phase heater
Maximum load: 

3680W at 230V  (16A) 

 

 

6400W at 400V  (16A)

Minimum load: 

230W at 230V  (1A) 

 

 

400W at 400V  (1A)

Control signal

Terminals I and I. Not polarity sensitive.
Wire to terminals U and U in the main unit.

    

PULSER...

PULSER-ADD

1 2 U 3 4 U

I I

K 1 2 U 3 4 U K G G

Figure 2: Wiring of control signal

 PULSER-ADD is galvanically separate from the main unit.  

They may therefore be supplied from different phases. The PULSER‑ADD 

control signal has high potential compared to neutral and earth (>200V). 
Thus, wiring of the control signal must comply with local codes for line 
voltage installations. The control signal must be wired so that the signal is 
cut when the supply voltage is cut.

Summary of Contents for PULSER-ADD

Page 1: ...ect supply voltage and twist the setpoint knob of the master unit between end stops Check that the LED which can be seen through the underside of PULSER ADD goes on and off at the same time as the LED of the master unit Check with a clamp on ammeter that current is flowing to the heater Anything wrong 1 Disconnect supply power Remove the control signal wiring from terminals I and I Reconnect power...

Page 2: ...igur 2 Inkoppling av styrsignal PULSER ADD är galvaniskt skild från sin huvudapparat Det är där för möjligt att mata enheterna från olika faser Enheterna måste däremot ha skilda belastningar Styrsignalen har hög potential mot noll och jord 200V Kablering och installation av styrsignalen ska alltså följa gällande föreskrifter för nätspänningsinstallationer Styrsignalen ska förreglas så att den bryt...

Page 3: ...Fühlereingang ist aber zur Steuerung von einem anderen Regler geeignet Der PULSER ADD ist nur zur Heizung sregelung geeignet Das Regelprinzip schließt eine Lichtsteuerung aus Nicht geeignet zur 3 Phasensteuerung Einbau Entfernen Sie die Front Die Fixirschraube befindet sich hinter dem Sollwertgeber Montieren Sie den PULSER ADD vertikal mit dem Kühlkörper oben Verwenden Sie Schrauben mit maximal 5 ...

Page 4: ...haut potentiel par rapport au neutre et à la terre 200V De ce cette façon le raccordement électrique et l installation des sondes doivent se conformer avec les normes locales en vigueur Il est nécessaire de couper le signal entre les appareils quand l alimentation générale est coupée Princip de regulation Le PULSER ADD module les temps de fonctionnement et les temps d arrêt en parallèle avec le PU...

Reviews: