background image

INSTRUCTION

i

Read this instruction before installation 

and wiring of the product

NO2F

1

NO2F

Nitrogen dioxide (NO

2

) transmitter

NO2F is a detector intended for demand-controlled ventilation in 

parking garages and road tunnels etc. The detector measures the 

NO

2

 concentration using an electrochemical method of measurement 

characterised by high selectivity and accuracy even in low concentra-

tions. The output signal is a linear representation of the gas concen-

tration.

Technical data

Supply voltage 

 

12...28 V DC 

Power consumption 

20 mAh 

Method of measurement 

Electrochemical 

Outputs  

 

4...20 mA, two-wire 

 

 

 

0...10 V DC, three-wire 

Calibration 

 

Automatic zero adjustment 

Ambient temperature 

-10...+40°C 

Ambient humidity    

0...90 % RH 

Protection class   

IP56 

Dimensions (WxHxD) 

80 x 82 x 86 mm 

Weight   

 

0.190 kg 

Material, casing   

Polycarbonate 

Type of gas 

 

Nitrogen dioxide (NO

2

Measuring range   

0...20 ppm

Accuracy 

 

±3 % 

Lifetime sensor 

 

~ 2 years

Installation

NO2F is recommended to be mounted about 20-30 cm above the floor. 

One detector is to be placed per 200-500 square metres garage surface, 
provided that the surface is open (without any ”pockets”) and that there 

is continuous air flow. Install the detector at least 50 cm from ventilation 

ducts and room corners. The transmitter must be mounted with the cable 
connection pointing up.

Wiring

The output signal is set via a jumper according to the figures below.

(+) 12...28 V DC

0...10 V DC

!

(+)

(-)

(+)

(-)

CONTROLLER

0...10 V DC

(+)

(-)

(+) 12...28 V DC

(-)

R = Max. 300 Ohm

CONTROLLER

4...20 mA

Control and alarm levels

We recommend using two alarm levels, pre-alarm and full alarm. In 
case of a pre-alarm, the fans are to be set to full speed and strategi-

cally placed flashing lights are to be activated. In case of a full alarm, 

strategically placed sirens are to be started, advising people to leave 
the garage immediately. Recommended levels for these alarms:

Pre-alarm 

2 ppm

Full alarm 

5 ppm

Service life and length of warranty

Regin recommends that the product be replaced by a new unit every 
two years (24 months) due to the service life of the measuring ele-
ment. Therefore, the length of warranty for this particular product is  
12 months. Because of the calibration required, the measuring ele-
ment is non-replaceable.

This product carries the CE mark. For more information, see  
www.regincontrols.com.
This product is TÜV-approved in accordance with VDI 2053.

Contact

AB Regin, Box 116, SE-428 22 Kållered, Sweden 
Tel: +46 31 720 02 00, Fax: +46 31 720 02 50 
www.regincontrols.com, [email protected]

8259F

 

DEC 18

EN