Duct mounted humidity/temperature 

transmitter

HTDT2500(-420) are duct mounted humidity and temperature 
transmitters for relative humidity and temperature measurement in air 
handling systems. Available with 0...10 V DC (HTDT2500) or 4...20 
mA (HTDT2500-420) output signal, and passive PT1000 signal.

Installation

Mount the transmitter in the duct using either the screw pockets in 

the enclosure or the mounting flange provided. Open the cover by 

carefully depressing the two plastic latchhooks and at the same time 
pulling the lower edge of the cover outwards. When mounted in con-

taminated environments the transmitter’s membrane filter should be 
exchanged for a sintered brass filter.

Wiring

Connect supply voltage and output signals according to the diagram for 
the unit being installed.

Connect passive PT1000 signal either between terminals 6-7 or 5-8.

Technical data

Supply voltage:

HTDT2500: 24 V AC ±20 % or 15...35 V DC
HTDT2500-420: 20...35 V DC (R

L

 < 500 Ω), 11...35 V DC (R

< 50 Ω)

Output signals:

Humidity: 0...10 V DC (4...20 mA), corresponding to 0...100 % RH 
Measuring range: 10...95 % RH
Accuracy at 20°C: ±2.5 %
Temperature range: 0...10 V DC (4...20 mA), corresponding to 0...50°C.
Accuracy at 20°C: ±0,3 K.
PT1000 (

DIN class A, according to IEC751

)

External load impedance:

HTDT2500: Min. 10 kΩ.
HTDT2500-420: Max. 500 Ω.

Contact

AB Regin, Box 116, 428 22 Kållered, Sweden 
Tel: +46 31 720 02 00, Fax: +46 31 720 02 50 
www.regin.se, [email protected]

10532E  JUL

 18

EN

V+

GND

RH 0...10 V DC

2

3

Temp. 0...10 V DC

HTDT2500

V+

Temp. 4...20 mA

HTDT2500-420

RH 4...20 mA

1

1

2

3

4

7

6

8

5

85

90

35

235

20-200

Ø12

100

CE