Regin ED-T43L-V Instructions Download Page 1

EN

INSTRUCTION

ED-T43L-V

IN20031 REV. A, 2020-10-28

C

Caauuttiioonn!! Read and understand the instruction before using the product.

C

Caauuttiioonn!! Ensure that the installation complies with local safety

regulations.

C

Caauuttiioonn!! Before installation or maintenance, the power supply should first

be disconnected. Installation or maintenance of this unit should only be
carried out by qualified personnel. The manufacturer is not responsible
for any eventual damage or injury caused by inadequate skills during instal-
lation, or through removal of or deactivation of any security devices.

Function

ED-T43L-V is a user-friendly touch display suitable for all types of
indoor environments. The users have access to different settings
depending on the assigned access rights.

Technical Data

General data

Supply voltage

24 V DC (22…26 V DC)

Power consumption

1.2 VA

Protection class

IP20

Storage temperature

-20…70 °C

Ambient temperature

0…45 °C

Ambient humidity

5…95 % rH

Dimensions, external (WxHxD)

144 x 96 x 14 mm

Display type

Resistive touch

Touch panel

4.3" TFT-display

Communication data

Communication ports

1

Port type

RS485

Default protocol

Modbus

Supported protocols

Modbus

Communication speed

19200 bps

Parity

N

Stop bits

1

Installation

The display is starting up after connecting the power. Wait a few seconds
for the home screen to be shown.

Log in as described under

Handling

.

Wiring

The display cable is connected to the display port on the Corrigo
controller via a 4P4C modular contact. The cable is ordered separately
and is available in two versions (3 and 10 m). A user made cable can be
made according to the wiring diagram in

Figure 1

The maximum cable

length is 100 m.

Figure 1 User made cable

Settings

The display reflects the controller configuration. The configuration can
be changed with the free software

Application tool

(see www.

regincontrols.com). Values such as setpoints, time channels, times etc
are changed via the display as described under

Handling

.

Handling

Getting started

1. Press

2. Log in with

3. Go to

Account settings

and use the navigation buttons to go to page 3

4. Select the functions that should be shown in the display

5. If a different language is required, navigate to page 2 and change it

under

Language

Log in access code

The display uses the same access code that is used in the controller.

Navigation

Navigation is done using four main menu buttons.

Menu button

Description

This is the home screen. Here the user gets an overview of
the actual values and setpoints.

In this menu fan settings are made:

– Boost fan

– Extended run

– Stop

Time channels can be set and modified in this menu (if they
are configured in the controller).

Different settings can be viewed or modified under this menu,
e.g.:

– Account settings, such as language settings and pin codes

– Home screen content

– Setpoints

– Date and time

– Status

– Configurations related to CLOUDigo, TCP/IP and address

G0

+C

B

A

1

2

3

4

ED-T43L-V

4P4C contact

ED-T43L-V

1

Reviews: