Corrigo ventilation user guide, revision F
Fel! Använd fliken Start om du vill tillämpa heading 1 för texten som ska
visas här.
17
Air control
This menu is only shown if frequency controlled fans have been configured.
Depending on the choice of fan control, different combinations of the menus below will be
shown.
Pressure control SAF (there are also corresponding menus for EAF)
Here, Actual and Setpoint values are displayed. This is a
read-only menu. No settings can be made here.
Submenu Setpoint values for normal speed (1/1)
and reduced speed (1/2).
Submenu outdoor compensation. An outdoor
temperature dependent compensation of the
pressure setpoint value can be added. The
compensation can be set for either the supply air
fan alone or for both fans.
Submenu extra compensation. A temperature
dependent compensation similar to the one
above but with selectable temperature source.
Flow control SAF (there are also corresponding menus for EAF)
Setpoint Flow control. Here, Actual and Setpoint values
are displayed. This is a read-only menu. No settings can
be made here.
Submenu Setpoint values for normal speed (1/1)
and reduced speed (1/2).
Submenu Outdoor compensation. An outdoor
temperature dependent compensation of the
pressure setpoint value can be added. The
compensation can be set for either the supply air
fan alone or for both fans.
Pressure control SAF
Actual: 480 Pa
Setp: 490 Pa
Pressure control SAF
Setp 1/1: 490 Pa
Setp 1/2: 300 Pa
Outdoor comp setp
-20 °C = -50 Pa
10 °C = 0 Pa
Act comp: -5 Pa
Comp sens:Room temp1
15 °C = 0 Pa
20 °C = 0 Pa
25 °C = 0 Pa
Flow control SAF
Actual: 1800 m3/h
Setp: 2000 m3/h
Flow control SAF
Setp 1/1: 2000 m3/h
Setp 1/2: 1000 m3/h
Outdoor comp setp
-15 °C =-200.0 m3/h
10 °C = 0.0 m3/h
Act comp: 0.0 m3/h