Regin CORRIGO L10 Manual Download Page 6

CONFIGUR

ATION -

Corrigo L10

A

B

C

D

.

E

F

G

H

.

I

J

K

Configuration code

.

.

A Control function

0. Supply air control

0

1. Supply air control with outdoor temperature compensation

1

2. Room control with cascaded supply air temperature control

2

3. Room control with min/max limiting of supply air temp.

3

4. Room control, single sensor

4

5. Supply air control/Room control. Outdoor temp dependent

5

B

Outpus sequences Y1, Y2, Y3

0. Heating / - / -

0

1. Heating / Cooling / -

1

2. Heating / Dampers / -

2

3. Heating / Dampers / Cooling

3

4. Heating / Plate exchanger / -

4

5. Heating / Plate exchanger / Cooling

5

6. Heating / Rotating exchanger / -

6

7. Heating / Rotating exchanger / Cooling

7

8. Cooling

8

C Heater type

0. Water heater

0

1. Electric heater

1

D Frost protection

0. Not active

0

1. Active

 on Y1

1

2. Active on Y1 with automatic alarm reset

2

EShutdown mode

0. No

0

1. 

Yes

1

F Pump stop

0. No

0

1. 

Yes

1

G Function AI1

0. Outdoor temperature sensor

0

1. External setpoint device

1

H Function DI1

0. Fan alarm

0

1. Fan indication

1

I Function DI3

0.Not active

0

1. Timer

1

2. Pushbutton

2

3. Alarm,

 smoke detector

3

4. External alarm

4

J Function DI4

0. Not active

0

1. Freeze-up protection plate-exchanger

1

2. Alarm,

 rotating exchanger

2

3. Alarm,

 chiller

3

4. Alarm,

 smoke detector

4

5. External alarm

5

K Function DO1, DO2

0. -- / --

0

1. DX1 / --

1

2. -- / Frost interlock

2

3. DX1 / Frost interlock

3

4. DX1 / DX2 in sequence

4

5. DX1 / DX2 binary

5

Numbers in bold indicate factory settings