Regin CORRIGO L10 Manual Download Page 5

3071-A  JAN 01

CORRIGO L10

INSTRUCTION

5

INSTRUCTION

Terminal connections overview

Technical support

Consult your local Regin dealer.

EMC emissions and immunity standard

This product meets or exceeds requirements for
european EMC standards CENELEC EN50081-1 and
EN50082-1 and carries the CE mark.

LVD

This product conforms with the LVD directives IEC730-1
and IEC730-2-9.

Fig. 2

Light emitting diode (LED)

Corrigo L10 has an LED to indicate one or more
alarms in the alarm queue. When not lit it means there
are no alarms in the alarm queue. If it flashes, new
unconfirmed alarms are pending. If it is constantly lit it
means that there are confirmed but non-reset alarms in
the queue.

16. Setpoint frost protection

17. Setpoint shutdown mode

18. Pump stop temperature and delay

19. Extended run time with pushbutton on DI3

20. Cool-down time (when using electric heater)

21. DX minimum On/Off times

22. Lowered min limit on DX-cooling

23. Outdoor temp. for blocking DX-cooling

24. Show min/max for analogue inputs (Yes/no)

25. Damping of AI1...AI4

26. Parameters for deviation alarm (max diff. and delay).

27. Outdoor temperature span

28. Alarm delay - fans

29. Alarm output blocking

The alarm output can be blocked so that some
pending alarms only activate the alarm output
during certain times. In the blocked state all alarms
are blocked except frost alarm, over-temperature
alarm and smoke alarm that will always trigger the
alarm output. Although an alarm has been blocked it
will be registered and indicated by the alarm
indicator on the front panel. Texts in the alarm
queue will appear as normal.

Settings...(continued)

Factory settings

Configuration

Default setting

Config. code

0501.0000.010

A. CONTROL FUNCT.

0 Supply air control

B. OUTPUT SEQUENCE

5 Heat/Plate exchg./Cool

C. HEATER TYPE

0 Water heater

D. FROST PROTECTION

1 Y1

E. SHUTDOWN MODE

0 No

F. PUMP STOP

0 No

G. FUNCTION AI1

0 Outdoor temperature

H. FUNCTION DI1

0 Fan alarm

I.

FUNCTION DI3

0 Input not used

J. FUNCTION DI4

1 Frost detection

K. FUNCTION DO1,DO2

0 Outputs not used

Storage of parameters and settings

All settings and paramters are stored in non-volatile
memory. this means that C

ORRIGO

 L10 does not have to

be reprogrammed even when subjected to very long
periods of power loss.
The real time clock in C

ORRIGO

 L10 has a powerfail

backup that lasts for about 24 hours. If subjected to
longer periods of power loss, the clock has to be set
again but the run periods in the scheduler are not
affected. Any alarms in the alarm queue will be lost
pending power failure.

1
2

3
4
5
6
7

8
9
10

11
12
13
14

15
16
17
18
19

20
21
22
23

24
25
26

Net A (L10-LON only)
Net B (L10-LON only)

DI4

Alarms cooler/Exchg./Smoke/Ext.

DI3

Ext.runtime/Smokealarm/Ext. alarm

DI2

Pump indicator

DI1

Fan malfuct.alarm/Fan indicator

DI+

Common DI1..DI4

C1/2 24V AC input
DO2 DX cooler stage 2
DO1 DX cooler stage 1

DO3..5 Common relay pole
DO5

Alarm output

DO4

Control pump

DO4

Control fans

AI1

Outdoor temp./External setpoint

AI2

Room temperature

AI3

Supply air temperature

AI4

Frost prot./High temperature limit

M

Signal neutral

AO1

Y1  0..10V DC

AO2

Y2  0..10V DC

AO3

Y3  0..10V DC

M

Signal neutral

24V AC
N System neutral
Protective earth

24V AC / 0.5A

230V AC

5A

24V AC

Supply voltage

Reviews: