Regin CORRIGO L10 Manual Download Page 2

3071-A  JAN 01

CORRIGO L10

INSTRUCTION

2

INSTRUCTION

Other control outputs
Digital outputs DO1...DO5  - Terminal 8...14

These outputs are divided into two types:

DO1 and DO2 are of triac type and can handle 24V AC /
0.5A  (1A short pulse load).

DO3, DO4 and DO5 are potential free relay outputs and
can handle 230V AC / 5A.

DO1

 DX cooling stage 1

DO2

 DX cooling stage 2 

or

 frost protection interlock

DO3

 Fan control

DO4

 Pump control 

or

 electric heating interlock.

DO5

 Alarm output

Language selection

C

ORRIGO

 L10 has the ability to show display in different

languages. To select another language, simply press
and hold down the   

!

  key while applying power to the

unit, it now enters language selection mode. Release
the button. To change, press the

 !

   button once

again. The display now shows current selected
language. Press  

é

 or  

ê

   buttons until desired

language appears. Then press  

OK

 to confirm and

store your selection. Press  

OK

  once again to leave the

language selection mode and revert to the normal
menu system.

All the information which can be shown on the display
are organised as menu frames in a ’tree’-shaped
layout. This tree can be navigated up/down and left/right
using the keypad on the front. You can look at control
parameters, change parameter values and handle
alarms.
Authorization levels when logging in controls the
amount of access given to a user when accessing
parameters.

The ”trunk” of the menusystem consists of the following
menu frame items:

Login
Configuration

Only shown in level 3

Inputs
Outputs
Scheduler
Settings

Only shown in level 2 and 3

During normal operation when keys are not used a
series of information frames are scrolled in the display.
The first one consists of a frame showing product
identity, current time and running mode. The second
one shows setpoint/actual value for the controller and
the third shows the output levels for Y1, Y2 and Y3.

To enter the menutree press the  

OK

 key. The menu

frame will change to display 

Inputs

.

Use the 

é

 

and 

ê

  keys to move up and down the

menutree trunk. Arrows in the right margin show
whether there are more frames to be displayed above
or below current menu frame. To enter one of the
”branches” press  

OK. 

When on a branch you can use

the arrow keys in a similar manner as the trunk to see
choices or subframes. Use the  

Esc

  key to jump back

in towards the trunk.

When in a menu frame with adjustable parameter(s)
you can enter ”edit mode” by pressing the  

!

  key.

Edit mode is confirmed by a flashing cursor in the first
editable field. Use the arrow keys to change the value.
Then press the  

OK

 key to confirm and store the

changed value and the cursor will jump to the next
editable field. Repeat this procedure for the next field.
After pressing  

OK

  at the last editable field the menu-

system will leave the edit mode and resume browse
mode.
To discard a change without saving it press  

Esc. 

The

cursor jumps back to the previous field. The edit mode
is automatically abandoned after a minute of inactivity.

The         key opens access to the alarm queue. It
shows active and unconfirmed alarms in the display.
The LED indicator for alarm out lights when there is at
least one alarm in the queue. It is located above the
key. If there are more than one alarm pending, use the

éê

 keys to browse them. Confirm with the 

OK 

key.

 

To

abandon without any action, press the 

Esc 

key.

Setpoint/Actual

  20.0°/20.0°

*CORRIGO L10-1*

O 12:09 AUT/ON

 Y1 / Y2 / Y3
  0%/ 45%/  0%

%

%

Login

C

ORRIGO

 L10 has 4 different user levels to prevent

changes being made to important settings by mistake.

0

Not logged in. Allows user to see the most important
values and manage alarms but not to make any
changes.

1

Main setpoint value, date and time can be set.
Outputs can be overridden by manual setting and
main operating mode can also be set manually to on
or off.

2

Gives user access to other setpoint values and run
time settings.

3

Access granted to all settable parameters. Used by
system manager when configuring the system. User
can also alter system login codes at this level.

Login procedure: If the scrolling information display is
showing press the  

OK

  key at which the display shows

Inputs

.

Press the 

é

 key until the menu frame arrow points to

Login

.

Select this branch by pressing the 

OK 

key.

Login menu is now shown.
To log in, press the  

!

  key and a cursor appears at the

first code digit. Press the 

éê

  keys to increase or

decrease the value.

Press the 

OK

 key to confirm and advance to next code

digit.
If you enter the wrong value by mistake, simply press
the 

Esc 

key to revert to previous entry.

After pressing the  

OK

 key at the last code digit the login

passcode is evaluated.
Invalid passcode will render an error message. Correct
passcode results in a message stating the user level
entered.
The menusystem reverts to main menu after ca: 2 sec.

Factory settings

Corrigo L10 is delivered with following default
usercodes:
Level 1

1111

Level 2

2222

Level 3

3333

Login at level 3 to be able to change these codes.

>Inputs          

á

 Outputs         

â

Control funct.   

á

0 Suppl. air cn  

â

Reviews: