Mount the controller on a DIN-rail in a panel or in a
seperate casing.
If installed in a panel front, use assembly kit FMC.
Protection class

IP20

Ambient temperature

0...50ºC

Installation

Wiring

Supply voltage - Terminal 24...26

Terminals for supply 24V AC, system neutral och
protective earth.

Analogue inputs AI1...AI4 - Plint 15...19

Use Pt1000 type sensors. The usage for each sensor
is determined by the selected controller options. Use
the table on the left (Fig. 1) for quick reference to
determine sensor usage. Connect selected sensors
according to the list.

N.B. 

All AI inputs must refer to the common terminal for

these inputs (terminal 19). This terminal may not be
connected to any other terminals in the system.

AI1

 is used, depending on configuration, either for:

1. Outdoor temperature.
2. External setpoint - input for setpoint signal.

These function are mutually exclusive. Only one of them
can be selected at a time.

C

ORRIGO

 L10 is a less complex digital controller

compared to the C10 model. This controller is
intended for use with air-handling systems and has a
simple easy-to-learn user interface. It also comes
with many system options to ensure flexibility.

C

ORRIGO

 L10 controls temperature in up to three

sequences which are configurables as either heat,
cool, damper, plate heat-exchanger or rotating heat-
exchanger. Different types of controlling functions can
be selected including  supply air control with or without
compensation or zone/room control with or without
cascade function.  In addition to the basic control
features it  has a number of abilities such as DX-
cooling in one or two stages, controlling and monitoring
fans and pumps, alarm handling, etc.
C

ORRIGO

 L10 has a real-time clock with battery backup,

weekly timing period and automatic setting/resetting  of
daylight saving time periods.

L10 is also available with a LON communication option
(model L10-LON).

Sensors...

AI2

 is used for zone/room temperature in some control-

ler configurations.

AI3

 is used for supply air temperature in some control-

ler configurations.

AI4

 is used, depending on configuration, either for:

1. Frost protection in systems with water heater. If
shutdown mode is selected, L10 uses this input as
control value when the fans are stopped.
2. Overheat protection in systems with electric heater. In
this case it should be connected to a potential free
closing switch.

Digital inputs DI1...DI4 - Plint 3..7

The digital inputs are activated by closing switch
against terminal 7 (DI+).

N.B. 

This terminal must not be wired together with other

signal and/or system neutrals in the system but only as
reference point to DI1...DI4.
Reference voltage 24V AC.
DI1 Pressure switch / fan run indicator 

or

Fan overload protector.

DI2 Pump run indicator
DI3 Extended run (timer/pushbutton/presence) 

or

smoke alarm 

or

 external alarm.

DI4 Alarm for: chiller, heat exchanger, smoke detector

or

 external alarm.

Analogue outputs
0...10V DC outputs AO1...AO3 - Terminal 20...23

Signal 0...10V DC, 5mA.

AO1

Control output Y1

AO2

Control output Y2

AO3

Control output Y3

These outputs must refer to terminal 23, which is
signal neutral. 

N.B.

 In C

ORRIGO

 L10 this terminal is

internally connected to system neutral.

The functions of the outputs depend on the current
control configuration but the sequence order is always
Y3 

ð

 Y2 

ð

 Y1 on increasing heat demand.