CONFIGURATION-

Corrigo C40-LON

M

N

O

P

.

Q

R

S

Configuration code 2

0

.

0

M Function DI6/DO6

0. External alarm & frost protection

0

1. Auto position & frost protection

1

2. Fire damper exercising

N Fire alarm

0. Alarm only

0

1. Alarm + supply air and exhaust air fans stop

1

2. Alarm + supply air fan stops

2

3. Alarm + exhaust air fan stops

3

O Function DI7/DI8

0. Not active

0

1. Pushbutton

1

2. Timer

2

P Function not available for Corrigo C40

This code must always be set to 0

0

Q Function not available for Corrigo C40

This code must always be set to 0

0

R Daylight saving time

0. No

0

1. Yes

1

S Humidity control

0. Humidification / Dehumidification

0

1. Humidification

1

2. Dehumidification

2

Summary of Contents for CORRIGO C40-LON

Page 1: ... inputs terminals 24 27 30 33 Humidity sensors AI3 AI4 AI3 and AI4 are to be connected to humidity transmitters with output 0 10 V DC corresponding to 0 100 RH AI3 room humidity sensor main sensor AI4 duct humidity sensor limiting sensor placed in the incoming air duct after the air handling unit Sensors AI3 AI8 Use PT1000 sensors See data sheet 4 150 The choice of which sensors to connect is dete...

Page 2: ... normal running when the buttons are not in use a series of menu pages is shown The display alternates between a general display with product description and clock setpoint actual temperature and output status for the control outputs Y1 Y2 Y3 To gain access to the menu tree press OK and the display will change to Control temp By pressing é and ê you can move up and down the tree The arrows to the ...

Page 3: ... control of the supply air temperature 3 Room temperature control with minimum maximum limiting of the supply air temperature 4 Room temperature control without supply air tempera ture sensor 5 Outdoor temperature controlled change over between constant supply air temperature control with outdoor temperature compensation or room temperature control 6 Can not be used with Corrigo C40 since an exhau...

Page 4: ...s blocked at outdoor temperatures lower than a preset value to prevent condensation problems Needs room sensor on AI7 and outdoor sensor on AI5 M Function input DI6 and output DO6 0 External alarm Frost protection 1 Auto Frost protection 2 Fire damper exercise See text block about the function DO6 DI6 page 6 N Fire alarm 0 Alarm only Both fans continue to run 1 Alarm and both fans are stopped 2 Al...

Page 5: ...on holidays 5 Holiday periods Level 2 and up 2 periods comprising any number of days may be programmed Running time during a holiday is set by programming the day H into one of the three scheduler periods If none of the periods contains the day H the system will be shut down on holidays Alarm settings Here all settings for the alarm system are set 1 Sensor alarm Should the actual temperature diffe...

Page 6: ...tput DO6 is deactivated and the dampers begin to return to the start position To avoid an alarm output DI6 must once again be deactivated within 3 minutes and then activated again within 3 minutes indicating that the dampers are back in their original position Factory settings Configuration Factory settings Config code 1 0011 1110 0000 Config code 2 0100 010 A CONTROL FUNCTION 0 Supply air temp co...

Page 7: ...Cooling 3 D Output Y2 0 Not active 0 1 Plate heat exchanger 1 2 Rotating heat exchanger 2 3 Not available for Corrigo C40 4 Damper 4 5 Heating 5 6 Cooling 6 E Output Y3 0 Not active 0 1 Cooling 1 2 Heating 2 F Frost protection Water heating only 0 Not active 0 1 Active on Y1 1 2 Active on Y2 2 3 Active on Y1 with automatic alarm reset 3 4 Active on Y2 with automatic alarm reset 4 G Shutdown mode W...

Page 8: ...d exhaust air fans stop 1 2 Alarm supply air fan stops 2 3 Alarm exhaust air fan stops 3 O Function DI7 DI8 0 Not active 0 1 Pushbutton 1 2 Timer 2 P Function not available for Corrigo C40 This code must always be set to 0 0 Q Function not available for Corrigo C40 This code must always be set to 0 0 R Daylight saving time 0 No 0 1 Yes 1 S Humidity control 0 Humidification Dehumidification 0 1 Hum...

Reviews: