Regin CORRIGO C40-LON Instruction Manual Download Page 2

2623A OKT 99  1.2.4

CORRIGO C40-LON

INSTRUCTION

Analogue 0...10 V DC control outputs, AO1...AO6

Output signal 0...10 V DC, 5 mA. Short circuit proof.

AO1

Control output Y1

AO2

Control output Y2

AO3

Control output Y3

The function of the different outputs depends on the
configuration settings but the sequence order will always
be Y3 

à

 Y2 

à

 Y1 on increasing heat demand.

AO4

Control output, supply air fan

AO5

Control output, exhaust air fan

AO6

Humidity control

These outputs must refer to terminal 41, Signal neutral.
Since signal neutral in the Corrigo is electrically
separated from system neutral the signal neutral from
the actuator must be connected to terminal 41 even if
the actuator and the Corrigo share a common trans-
former.

Other control outputs, DO1...DO7

The digital outputs DO1...DO6 are triac controlled.
0,5A, 24 V AC. Short term peak load 1A.
Output DO7 is a potential free relay contact.
The outputs are paired to 24 V AC supply inputs. (See
terminal schematics, page 6).
For higher voltages and currents use relay modules
RM6-24/D or RM6H-24/D that are specially designed for
use with Corrigo.

Some of the outputs have alternative functions
depending on the system configuration.

DO1

Activate supply air fan.

DO2

Activate exhaust air fan.

DO3

Control circulation pump.

DO4

Control DX-chiller 1

DO5

Control DX-chiller 2

DO6

External frost protection or fire damper exercising.
(See text section DO6/DI6 page 6).

DO7

Potential free relay contact for alarm output.
1 A, 24 V AC/DC. Closes on alarm.

Buttons and display

Language

The menu text language can be changed.
Hold the 

!

 button depressed during power up to enter the

setup mode. Then press 

!

 again and a blinking marker

will appear next to the current language. Select the desired
language by using the arrow buttons. When the marker is
next to the desired language, press 

OK

. Press 

OK

 again

to return to the normal menu system.
All information that can be shown on the display is organi-
sed in menues in a ”menu-tree”.
Using the buttons on the front you can move between the
different menues in the tree, look at parameters, change
settings, display and reset alarms.
What you can see and do is governed by your log-on level.
The ”Trunk” of the menu-tree contains the following
menues:

Logon
Configuration

Only shown in level 3

Control temp

ï

 Starting point

Control humidity
Control pressure
Running mode
AI Analogue in
DI Digital in
AO Analogue out
DO Digital out
Scheduler
Alarm settings

Not shown in level 0

Settings

Only shown in level 2 and 3

During normal running when the buttons are not in use a
series of menu pages is shown.
The display alternates between, a general display with
product description and clock, setpoint/actual temperature,
and output status for  the control outputs Y1, Y2, Y3.

To gain access to the menu-tree press 

OK

 and the display

will change to 

Control temp

.

By pressing 

é

 and 

ê

 you can move up and down the tree.

The arrows to the right in the display indicate whether
there are menu pages above or below the one shown.

>Control Temp

á

AI Analogue in

â

To move out onto any of the ”branches” press 

OK

. Out on

the branch you can then move about in the same way
using the arrowbuttons. By pressing 

Esc

 you can jump

back towards the trunk.
In menu pages with settable parameters you shift to
”Setting mode” by pressing 

!

.

A dark blinking marker will then appear in the first settable
position. By using the arrow buttons the value can be
changed. When the correct value is shown press 

OK

 and

the marker will move to the next position. After 

OK

 on the

last position the new value is stored and the ”Setting
mode” is ended.
To abort without change press 

Esc

 and the marker will

move back to the previous position. Setting mode is
aborted automatically after a few minutes button-inactivity.

   Shows the alarm queue. Displays active and non-
acknowleged alarms. The alarm-LED above the button is
lit when there are alarms in the queue.If there are multiple
alarms use the arrow buttons to move between pages.
Alarms are acknowleged by pressing 

OK

.

To abort press 

Esc.

Login

Corrigo has 4 different login levels to prevent the user
from inadvertently changing any settings.

0

Without logging in most of the important parameters
can be viewed, alarms can be acknowleged but no
parameters can be changed.

1

Main setpoint, time and date can be set.
Outputs can be manually set and the running mode
can be set to manually on or off.

2

Gives access to most setpoints and running para-
meters.

3

Gives total access.
Used by the commissioning engineer for system
configuration.
Enables changing of login codes.

To login when the display shows the normal series of
information menues, first press 

OK

 and the display will

show 

Control temp

.

Control Funct.

á

>0 Suppl Air cnt

â

INSTRUCTION

2

ð

ð

*CORRIGO C40*

Setpoint/Actual

Y1 / Y2 / Y3

Mo 980907 10:10

20.0ºC / 20.0ºC

0% / 45% / 0%

DI7 and DI8 should, depending on settings, either be
wired to a momentarily closing pushbutton or to, for
example, a timer.
If DI7 and DI8 are both closed at the same time the unit
is shut down.
If a separate handswitch for setting the running mode is
installed it should be wired according to figure 1.

%

EF/Setp/Act/Out

275Pa/275Pa/70%

Setpoint/Actual

50%RH / 48%RH

SF/Setp/Act/Out

275Pa/275Pa/70%

Summary of Contents for CORRIGO C40-LON

Page 1: ... inputs terminals 24 27 30 33 Humidity sensors AI3 AI4 AI3 and AI4 are to be connected to humidity transmitters with output 0 10 V DC corresponding to 0 100 RH AI3 room humidity sensor main sensor AI4 duct humidity sensor limiting sensor placed in the incoming air duct after the air handling unit Sensors AI3 AI8 Use PT1000 sensors See data sheet 4 150 The choice of which sensors to connect is dete...

Page 2: ... normal running when the buttons are not in use a series of menu pages is shown The display alternates between a general display with product description and clock setpoint actual temperature and output status for the control outputs Y1 Y2 Y3 To gain access to the menu tree press OK and the display will change to Control temp By pressing é and ê you can move up and down the tree The arrows to the ...

Page 3: ... control of the supply air temperature 3 Room temperature control with minimum maximum limiting of the supply air temperature 4 Room temperature control without supply air tempera ture sensor 5 Outdoor temperature controlled change over between constant supply air temperature control with outdoor temperature compensation or room temperature control 6 Can not be used with Corrigo C40 since an exhau...

Page 4: ...s blocked at outdoor temperatures lower than a preset value to prevent condensation problems Needs room sensor on AI7 and outdoor sensor on AI5 M Function input DI6 and output DO6 0 External alarm Frost protection 1 Auto Frost protection 2 Fire damper exercise See text block about the function DO6 DI6 page 6 N Fire alarm 0 Alarm only Both fans continue to run 1 Alarm and both fans are stopped 2 Al...

Page 5: ...on holidays 5 Holiday periods Level 2 and up 2 periods comprising any number of days may be programmed Running time during a holiday is set by programming the day H into one of the three scheduler periods If none of the periods contains the day H the system will be shut down on holidays Alarm settings Here all settings for the alarm system are set 1 Sensor alarm Should the actual temperature diffe...

Page 6: ...tput DO6 is deactivated and the dampers begin to return to the start position To avoid an alarm output DI6 must once again be deactivated within 3 minutes and then activated again within 3 minutes indicating that the dampers are back in their original position Factory settings Configuration Factory settings Config code 1 0011 1110 0000 Config code 2 0100 010 A CONTROL FUNCTION 0 Supply air temp co...

Page 7: ...Cooling 3 D Output Y2 0 Not active 0 1 Plate heat exchanger 1 2 Rotating heat exchanger 2 3 Not available for Corrigo C40 4 Damper 4 5 Heating 5 6 Cooling 6 E Output Y3 0 Not active 0 1 Cooling 1 2 Heating 2 F Frost protection Water heating only 0 Not active 0 1 Active on Y1 1 2 Active on Y2 2 3 Active on Y1 with automatic alarm reset 3 4 Active on Y2 with automatic alarm reset 4 G Shutdown mode W...

Page 8: ...d exhaust air fans stop 1 2 Alarm supply air fan stops 2 3 Alarm exhaust air fan stops 3 O Function DI7 DI8 0 Not active 0 1 Pushbutton 1 2 Timer 2 P Function not available for Corrigo C40 This code must always be set to 0 0 Q Function not available for Corrigo C40 This code must always be set to 0 0 R Daylight saving time 0 No 0 1 Yes 1 S Humidity control 0 Humidification Dehumidification 0 1 Hum...

Reviews: