CORRIGO C40-LON

INSTRUCTION

Corrigo C40-LON is a controller primarily intended
for controlling air handling units. It can easily be
adapted to suit different types of units.
Corrigo C40-LON has built-in capability for LON
communication. See separate LON interface manual.

Corrigo C40-LON has six 0...10 V DC control outputs,
three in sequence for controlling for example heating /
heat exchanger / cooling and two for speed control of
supply air fan and exhaust air fan and one for humidity
control. It has a number of functions and possibilities,
such as DX-cooling in one or two steps, outdoor
temperature compensation, fire damper exercise, control
and monitoring of fans and circulation pump, free
cooling, heat-exhanger efficiency calculation etc.
Corrigo C40-LON can also receive and handle a number
of alarms such as fan and filter alarm, smoke alarm,
chiller alarm, heat-exchanger alarm and has a free relay
output for total alarm. Corrigo C40-LON has a year-base
real-time clock, week-scheduler , holiday calendar,
holiday periods and automatic normal time/daylight
saving time change-over.

Installation

Mount the unit on a DIN rail in a cabinet or separate
enclosure.
For mounting in the cabinet front, use mounting kit FMC.
Degree of protection

IP20

Ambient temperature

0...50°C

Wiring

Supply voltage

Terminals 42 and 43: 24 V AC, ±15%, 50/60 Hz.

Fan speed control, supply/exhaust air fans AI1, AI2

Connect AI1 and AI2 to pressure transmitters measuring
the pressure over each fan. Use transmitters  with a
0...10V DC output signal. The pressure range is
adjustable.

N.B. 

Since these signals control vital functions they must

be connected for the unit to work as intended.

Analogue inputs AI1...AI8
N.B.

 All AI-inputs must refer to the signal neutral terminals

for AI-inputs (terminals 24, 27, 30, 33).

Humidity sensors AI3, AI4

AI3 and AI4 are to be connected to humidity transmitters
with output 0...10 V DC corresponding to 0...100% RH.
AI3, room humidity sensor, main sensor.
AI4, duct humidity sensor, limiting sensor placed in the
incoming air duct after the air handling unit.

Sensors AI3...AI8

Use PT1000 sensors. (See data sheet 4-150).
The choice of which sensors to connect is determined by
the choice of functions. The table, fig 3 can be used as an
aid in determining which sensors to install.
Connect the sensors according to the terminal schematics
on page 6.

AI8 

is, depending on setting, used for:

1. Frost protection sensor for applications with water

heated heater.

2. High temperature limiting switch for applications with

electrical heater.

When used for high temperature limiting switch it must be
connected to a free contact closing on alarm.

!

IMPORTANT: Read these
instructions before installation
and wiring of the product.

Fig 1

Normal
Reduced
0
Auto

DI7

DI8

Fig 2

INSTRUCTION

1

ð

DMD

DTL

Corrigo

Corrigo

Digital inputs DI1...DI8

The digital inputs DI1...DI8 must refer to terminal 22.

N.B. 

Terminal 22 must 

not 

be connected to any other

terminals but should only be used as reference for units
connected to DI1...DI8.
The inputs may only be connected to potential free
contacts.
Closed contact activates alarm or function.
Unused inputs are to be left open.

DI1

Input for filter guards

DI2

Input for circulation pump indication.
Must be connected for systems with water heating.

DI3

Input for chiller alarm

DI4

Input for rotation sentinel or ice build-up sentinel for
heat exchanger.

DI5

Input for smoke alarm.

DI6

Input for fire damper end-position indication,
external alarm or external switches ”not in Auto
position”.
(See textblock on DO6/DI6 on page 6).

DI7

Input for start of extended running time, normal flow.

DI8

Input for start of extended running time, reduced
flow.

Tel:+46 (0)31 795 44 60    Fax:+46 (0)31 795 38 50

Box 116   428 22  KÅLLERED, SWEDEN

Summary of Contents for CORRIGO C40-LON

Page 1: ... inputs terminals 24 27 30 33 Humidity sensors AI3 AI4 AI3 and AI4 are to be connected to humidity transmitters with output 0 10 V DC corresponding to 0 100 RH AI3 room humidity sensor main sensor AI4 duct humidity sensor limiting sensor placed in the incoming air duct after the air handling unit Sensors AI3 AI8 Use PT1000 sensors See data sheet 4 150 The choice of which sensors to connect is dete...

Page 2: ... normal running when the buttons are not in use a series of menu pages is shown The display alternates between a general display with product description and clock setpoint actual temperature and output status for the control outputs Y1 Y2 Y3 To gain access to the menu tree press OK and the display will change to Control temp By pressing é and ê you can move up and down the tree The arrows to the ...

Page 3: ... control of the supply air temperature 3 Room temperature control with minimum maximum limiting of the supply air temperature 4 Room temperature control without supply air tempera ture sensor 5 Outdoor temperature controlled change over between constant supply air temperature control with outdoor temperature compensation or room temperature control 6 Can not be used with Corrigo C40 since an exhau...

Page 4: ...s blocked at outdoor temperatures lower than a preset value to prevent condensation problems Needs room sensor on AI7 and outdoor sensor on AI5 M Function input DI6 and output DO6 0 External alarm Frost protection 1 Auto Frost protection 2 Fire damper exercise See text block about the function DO6 DI6 page 6 N Fire alarm 0 Alarm only Both fans continue to run 1 Alarm and both fans are stopped 2 Al...

Page 5: ...on holidays 5 Holiday periods Level 2 and up 2 periods comprising any number of days may be programmed Running time during a holiday is set by programming the day H into one of the three scheduler periods If none of the periods contains the day H the system will be shut down on holidays Alarm settings Here all settings for the alarm system are set 1 Sensor alarm Should the actual temperature diffe...

Page 6: ...tput DO6 is deactivated and the dampers begin to return to the start position To avoid an alarm output DI6 must once again be deactivated within 3 minutes and then activated again within 3 minutes indicating that the dampers are back in their original position Factory settings Configuration Factory settings Config code 1 0011 1110 0000 Config code 2 0100 010 A CONTROL FUNCTION 0 Supply air temp co...

Page 7: ...Cooling 3 D Output Y2 0 Not active 0 1 Plate heat exchanger 1 2 Rotating heat exchanger 2 3 Not available for Corrigo C40 4 Damper 4 5 Heating 5 6 Cooling 6 E Output Y3 0 Not active 0 1 Cooling 1 2 Heating 2 F Frost protection Water heating only 0 Not active 0 1 Active on Y1 1 2 Active on Y2 2 3 Active on Y1 with automatic alarm reset 3 4 Active on Y2 with automatic alarm reset 4 G Shutdown mode W...

Page 8: ...d exhaust air fans stop 1 2 Alarm supply air fan stops 2 3 Alarm exhaust air fan stops 3 O Function DI7 DI8 0 Not active 0 1 Pushbutton 1 2 Timer 2 P Function not available for Corrigo C40 This code must always be set to 0 0 Q Function not available for Corrigo C40 This code must always be set to 0 0 R Daylight saving time 0 No 0 1 Yes 1 S Humidity control 0 Humidification Dehumidification 0 1 Hum...

Reviews: