CONFIGURATION-
Corrigo C10-LON
M
N
O
P
.
Q
R
S
Configuration code 2
.
0
M Function DI6/DO6
0. External alarm & frost protection
0
1. Auto position & frost protection
1
2. Fire damper exercising
N Fire alarm
0. Alarm only
0
1. Alarm + supply air and exhaust air fans stop
1
2. Alarm + supply air fan stops
2
3. Alarm + exhaust air fan stops
3
O Function DI7/DI8
0. Not active
0
1. Pushbutton
1
2. Timer
2
P 2-speed fans (Can not be combined with DX-cooling)
0. No
0
1. Yes
1
Q External setpoint
0. No
0
1. Yes
1
R Daylight saving time
0. No
0
1. Yes
1
S This function is not available for Corrigo C10
The code must always be set to 0
0