Regin Corrigo C10-LON Quick Start Manual Download Page 3

2418C JAN 00  1.5.5

CORRIGO C10-LON

INSTRUCTION

Press 

é

until the cursor arrow points at 

Login

. Press

OK

.

The login menu will be displayed.

To log in press 

!

 and a marker will be shown at the first

digit. Press 

éê

 to change the value. Press 

OK

 to

acknowlege the correct value and the marker will move
to the next digit.
If you make an error you can return to the previous digit
by pressing 

Esc

.

After 

OK

 on the last digit the code is evaluated.

An incorrect code is rejected and an errormessage is
displayed.A correct code will display an acknowledging
message showing the login level.
After 2 seconds the system returns to the main menu.

Factory codes

On delivery the following codes are installed
Level 0 0000 Level 0 is default without having to log on
Level 1 1111
Level 2 2222
Level 3 3333
These codes can be changed when logged in at level 3.
Enter the login menu again.
Press the 

ê

 until the menu for the level you wish to

change is shown.
Press 

!

 to enter Setting mode. A marker will be shown

at the first digit.  Press 

éê

 to change the value.

Press 

OK

 to acknowlege the correct value and the

marker will move to the next digit.
If you make an error you can return to the previous digit
by pressing 

Esc

.

After 

OK

 on the last digit the new code is acknowleged.

Save the codes in a safe place. Especially the code for
level 3.
Should the code for level 3 be lost, a one-day code can
be obtained from Regin.

Set your cod
0000   Level:0

Configuration

Configuration implies the commissioning setting of all the
parameters in Corrigo.
The configuration menues are only accessible at level 3.
Choose the menu 

Configuration

 in the main menu.

Normal method

(A quick method is described at the end
of the configuration section).

The configuration section comprises a number of menu
pages (A...S). Go through the pages one at a time.
In each page, choose the alternative valid for the
application on hand.
Each menu page is here described in short, showing the
available alternatives.
For detailed information, see the manual for Corrigo C10.

A. Control function

0. Constant supply air temperature
1. Constant supply air temperature with outdoor tempera-

ture  compensation

2. Room temperature control with cascade control of the

supply air temperature.

3. Room temperature control with minimum/maximum

limiting of the supply air temperature.

4. Room temperature control without supply air tempera-

ture sensor.

5. Outdoor temperature controlled change-over between

constant supply air temperature control with outdoor
temperature  compensation or room temperarature
control.

6. Exhaust air temperature control with minimum/

maximum limiting of the supply air temperature.

B. Heater type

0. Water heated.

(AI8 Frost protection sensor)

1

Electric heater.

(AI8 High temperature limit)

C. Output sequence Y1

0

-

Output not active

1

AO1 Heater

2

AO1 Damper

3

AO1 Cooler

D. Output sequence Y2

0

-

Output not active

1

AO2 Plate exchanger

(DI4 ice-up sensor)

2

AO2 Rotating exchanger

(DI4 rotation sentinel)

3

AO2 Liquid connected exch.

(AI4 Limit sensor in
the exchanger circuit)

Exhaust
temp

Outdoor temp

Control Funct.

á

>0 Suppl Air cnt

â

4

AO2 Damper

5

AO2 Heater

6

AO2 Cooler

E. Output sequence Y3

0

-

Output not active

1

AO3 Cooler

2

AO3 Heater

F. Frost protection 

(Only if water heating is chosen).

0

Not active

.

Y1

Y1 forced open on frost risk.

2

Y2

Y2 forced open on frost risk.

3

Y1 Aut Reset. Y1 forcedopen, automatic reset.

4

Y2 Aut Reset. Y2 forced open, automatic reset.

G. Shutdown mode 

(Only if water heating is chosen).

0

No

1

Yes

When the system is shut down Corrigo will contol the
valve actuator to maintain a preset temperature at the
frost protection sensor. Only activated if the circulation
pump is running.
Needs frost protection sensor on AI8.

H. Pump stop

 (Only if water heating is chosen).

0

No

1

Yes

The water circulation pump is stopped when there is no
heating demand and the outdoor temperature is above a
preset temperature. Activation delayed 15 minutes
Stopped pump is exercised 5 minutes/day at 12:00.
Needs outdoor temperature sensor on AI5.

I. Efficiency calculation

0

No

1

Yes

Heat exchanger efficiency is calculated usin exhaust air
temperature, extract air temperature and outdoor
temperature.
At efficiency values <50% and full output on Y2 the
alarm ”Low efficiency” is activated.
Cannot be combined with liquid connected exchanger.
Needs exhaust air
sensor on AI3,
extract air sensor
on AI4 and
outdoor sensor
on AI5.

Extract air temp

INSTRUCTION

3

ð

ð

Summary of Contents for Corrigo C10-LON

Page 1: ...osen AI8 is depending on setting used for 1 Frost protection sensor for applications with water heated heater 2 High temperature limiting switch for applications with electrical heater When used for high temperature limiting switch it must be connected to a free contact closing on alarm Fan supervision supply air fan exhaust air fan AI1 AI2 Connect AI1 and AI2 to free contacts that open when the f...

Page 2: ...he Trunk of the menu tree contains the following menues Logon Configuration Only shown in level 3 Control temp ï Starting point Running mode AI Analogue in DI Digital in AO Analogue out DO Digital out Scheduler Alarm settings Not shown in level 0 Settings Only shown in level 2 and 3 During normal running when the buttons are not in use a series of menu pages is shown The display alternates between...

Page 3: ...with outdoor tempera ture compensation 2 Room temperature control with cascade control of the supply air temperature 3 Room temperature control with minimum maximum limiting of the supply air temperature 4 Room temperature control without supply air tempera ture sensor 5 Outdoor temperature controlled change over between constant supply air temperature control with outdoor temperature compensation...

Page 4: ...ng engineer When the configuration is terminated by leaving the configuration branch by pressin Esc an automatic restart with the new parameters will take place The login level will be reset to 0 Configuration quick method The top two menu pages on the configuration branch show two configuration codes Configuration code 1 and Configuration code 2 Each position in the code represents in order the v...

Page 5: ... none of the periods contains the day H the system will be shut down on holidays 5 Holiday periods Level 2 and up 2 periods comprising any number of days may be programmed Running time during a holiday is set by programming the day H into one of the three scheduler periods If none of the periods contains the day H the system will be shut down on holidays Alarm settings Here all settings for the al...

Page 6: ...cating that the dampers have reached the other end point When DI6 is activated the output DO6 is deactivated and the dampers begin to return to the start position To avoid an alarm output DI6 must once again be deactivated within 5 minutes and then activated again within 5 minutes indicating that the dampers are back in their original position Factory settings Configuration Factory settins Config ...

Page 7: ...Y1 0 Not active 0 1 Heating 1 2 Damper 2 3 Cooling 3 D Output Y2 0 Not active 0 1 Plate heat exchanger 1 2 Rotating heat exchanger 2 3 Liquid connected heat exchanger 3 4 Damper 4 5 Heating 5 6 Cooling 6 E Output Y3 0 Not active 0 1 Cooling 1 2 Heating 2 F Frost protection Water heating only 0 Not active 0 1 Active on Y1 1 2 Active on Y2 2 3 Active on Y1 with automatic alarm reset 3 4 Active on Y2...

Page 8: ...rm only 0 1 Alarm supply air and exhaust air fans stop 1 2 Alarm supply air fan stops 2 3 Alarm exhaust air fan stops 3 O Function DI7 DI8 0 Not active 0 1 Pushbutton 1 2 Timer 2 P 2 speed fans Can not be combined with DX cooling 0 No 0 1 Yes 1 Q External setpoint 0 No 0 1 Yes 1 R Daylight saving time 0 No 0 1 Yes 1 S This function is not available for Corrigo C10 The code must always be set to 0 ...

Page 9: ...egrenzungsfühler im Wärmetauscherkreis 3 Externer Sollwert Eingang für Sollwertsignal verwendet Fühler Diese Funktion sind deshalb gegenseitig auszu schließen Nur eine der Funktionen kann gewählt werden AI8 wird in Abhängigkeit von der Einstellung entweder für Frostschutz in Applikationen mit Wasserbatterie Überhitzungsschutz in Applikationen mit Elektroheizung Wenn er als Eingang für den Überhitz...

Page 10: ...nd Corrigo an die Spannung angeschlossen wird ermöglicht Um die Sprache zu ändern nochmals auf die Taste drücken Ein Anzeige wird neben der aktuellen Sprache angezeigt Zum Ändern é oder ê drücken Wenn die gewünschte Sprache gewählt ist OK drücken Nochmals OK drücken um wieder in das normale System zu gelangen Jede Information die im Fenster angezeigt werden kann ist in Abschnitten in einen Eingabe...

Reviews: