55
Manual C
ORRIGO
C-
SERIES
2000.09
CONFIGURATION- Corrigo C40
M N O P . Q R S
Configuration code 2
0 . 0
M Function DI6/DO6
0. External alarm & frost protection
0
1. Auto position & frost protection
1
2. Fire damper exercising
N Fire alarm
0. Alarm only
0
1. Alarm + supply air and exhaust air fans stop
1
2. Alarm + supply air fan stops
2
3. Alarm + exhaust air fan stops
3
O Function DI7/DI8
0. Not active
0
1. Pushbutton
1
2. Timer
2
P Function not available for Corrigo C40
This code must always be set to 0
0
Q Function not available for Corrigo C40
This code must always be set to 0
0
R Daylight saving time
0. No
0
1. Yes
1
S Humidity control
0. Humidification / Dehumidification
0
1. Humidification
1
2. Dehumidification
2