52
Manual C
ORRIGO
C-
SERIES
2000.09
CONFIGURATION- Corrigo C30
A B C D . E F G H . I J K L
Configuration code 1
.
. 0
A Control function
0. Supply air control
0
1. Supply air control with outdoor temperature compensation
1
2. Room control with cascaded supply air temperature control
2
3. Room control with min/max limiting of supply air temp.
3
4. Room control, single sensor
4
5. Supply air control/Room control. Outdoor temp dependent
5
6. Not available for Corrigo C30
-
B Heater type
0. Water heater
0
1. Electric heater
1
C Output Y1
0. Not active
0
1. Heating
1
2. Damper
2
3. Cooling
3
D Output Y2
0. Not active
0
1. Plate heat exchanger
1
2. Rotating heat exchanger
2
3. Not available for Corrigo C30
-
4. Damper
4
5. Heating
5
6. Cooling
6
E Output Y3
0. Not active
0
1. Cooling
1
2. Heating
2
F Frost protection (Water heating only)
0. Not active
0
1. Active on Y1
1
2. Active on Y2
2
3. Active on Y1 with automatic alarm reset
3
4. Active on Y2 with automatic alarm reset
4
G Shutdown mode (Water heating only. Requires outdoor sensor)
0. No
0
1. Yes
1
H Pump stop (Water heating only. Requires outdoor sensor)
0. No
0
1. Yes
1
I Function not available for Corrigo C30
This code must always be set to 0
0
J DX-cooling
0. No
0
1. 1-step
1
2. 2-step
2
3. 3-step binary
3
K Cooling recovery
0. No
0
1. Yes
1
L Free cooling
0. No
0
1. Yes
1