47
Manual C
ORRIGO
C-
SERIES
2000.09
Commissioning protocol
Scheduler
Factory setting Commissioning setting
Period 1
MTWTF 08:00-17:00
_______________
Period 2
_______________
Period 3
_______________
Reduced speed 1
_______________
Reduced speed 2
_______________
Reduced speed 3
_______________
Holidays
980101
_______________
Alarm settings
1. Temp deviation alarm
5K och 2 minutes
______________
2. Outdoor temp interval within which
temp deviation alarm is active 20...-20°C
_______________
3. Pressure deviation alarm
50Pa / 2 minutes
_______________
4. Alarm delay, supply air fan
30 seconds
_______________
5. Alarm delay, exhaust air fan
30 seconds
_______________
6. Alarm output active
Mo-Su 00:00 - 24:00
_______________
7. Stop on exchanger alarm
No
_______________
Settings
1. Setpoint frost protection
7°C
_______________
2. Setpoint shut-down mode
25°C
_______________
3. Pump stop. Min outdoor temp, 6°C
_______________
start- stop delay
15 minutes
_______________
4. Cool-down (electric heating)
120 seconds
_______________
5. Delay supply air fan
60 seconds
_______________
time with 100% Exch. at start
90 seconds
_______________
6. Extended running.Pushbutton 0 minutes
_______________
7. P-band Y2,Y3. Factor
0,5 / 0,5
_______________
8. Min outdoor air, mix. damper Y2 0 %
_______________
9. Free cooling. Min outdoor temp 10°C
_______________
difference outdoor/indoor
3 K
_______________
10.Free cooling. Setpoint room
21°C
_______________
11.Cooling recovery.
Diff outdoor-/exhaust air temp 2 K
_______________
12.DX-cooling. Min. on-/off-times 5 min. and 5 min.
_______________
13.DX-cooling. Lowered min.lim. 5 K
_______________
14.DX-cooling. Min. outdoor temp. 12°C
_______________
15.Starttime damper exercising.
00:00
_______________
16.Min-temp and P-band,
liquid conn. exch.
2°C and 5K
_______________
17.Force fan low speed
on low outdoor temp
Yes / -10 °C
_______________
18.SF/EF pressure range
500/500 Pa
_______________
19.Damping factor AI1...AI8
1
_/ _/ _/ _/ _/ _/ _/_
20.Function DI1...DI8
+
_/ _/ _/ _/ _/ _/ _/_
20.Show Min/Max-temp AI3...AI8 No
_______________
Installation
System
Commiss. date
Commiss. by