5
Manual C
ORRIGO
C-
SERIES
2000.09
Technical data
Supply voltage
24V AC +/- 15%
Power consumption
3VA
Ambient temperature
0...50 deg.C.
Storage temperature
-40...+50 deg.C.
Ambient humidity
Maximum 90% RH
Dimensions (w x h x d)
105 x 112 (incl.terminals) x 58 mm.
Protection class
IP20. Front mounting IP40
Mounting
On DIN-rail in a cabinet or standard housing.
On cabinet front using mounting kit FMC
Connections
Disconnectable terminal strips
Temp.sensor inputs
PT1000
Analogue inputs
0....10V DC
Digital inputs
Potential free closure.
Digital outputs
0.5 A, 24 V AC triac outputs
Analogue outputs
0...10 V DC, 5 mA. Short-circuit protected
Memory
Flash. All settings are stored in the event of power failure.
Real-time clock with 48 hour reserve running time.
Display
Background illumination. LCD, 2 rows of 16 characters
Running indication
7 in number steady shining yellow LEDs
Alarm indication
7 in number steady shining/flashing red LEDs
Alarms
Steady shining/flashing LED and relay output,
1A 24V DC/AC.
The alarm output can be blocked to prevent unprioritised
alarms activating the alarm relay during the night or
during holidays.
This product conforms with the requirements of
European EMC standards CENELEC EN50081-1 and
EN50082-1 and carries the CE mark.
Front mounting kit
When mounting C
ORRIGO
in a cabinet front use the FMk1 kit for easier mounting.
The kit contains a front frame with see-through lid and an integrated mounting-rail.
Protection class IP65.
When mounting 2 C
ORRIGO
s or one C
ORRIGO
plus a relay unit next to each other in
the cabinet front use the FMk2 mounting kit. It contains the same items as FMK1
above but in different dimensions.
Summary of Contents for Corrigo C Series