Alarms
When alarms are activated they are displayed in the alarm queue and also as a
blinking red light on the display panel on the front of the controller. Certain alarms
cannot be traced to one of the 7 LEDs on the panel and therefore have no separate
alarm on the front. The alarm lamp above the alarm button always blinks red,
however, in the event of an alarm.
Alarm queue
To check the alarm queue press the alarm button
. The display will then show
active alarms, the date and time when the alarm became active and the alarm
status.
Alarm status
Blinking ”AL” indicates that the alarm is active and has not been
acknowledged.
Steady ”AL” indicates that the alarm is active but has been acknowledged.
Blinking ”OK” indicates that the alarm has aborted but has not been
acknowledged.
Acknowledging an alarm
Alarms are acknowledged by means of the
OK
button which will remove the alarm
from the alarm list. If the alarms are still active they will remain in the alarm list but
the blinking will be replaced by a steady ”AL” and a steady red light on the alarm
signals.
Arrows on the right-hand side show when there are more alarms in the queue.
Login
CORRIGO has four different login levels to prevent the user from inadvertently
changing any settings.
0
Without logging in all of the most important parameters can be viewed such
as input and output status, alarms in the alarm queue, setpoints etc. Alarms
can also be acknowledged.
1
Main setpoint, time and date can be set. Outputs can be manually set and
the running mode can be set to manually on or off. Other parameters can be
read off but not changed.
2
Gives access to most setpoints and running parameters such as outdoor
compensation, control alarm deviations, time delays etc.
3
The highest user level giving total access. Used by the commissioning
engineer for system configuration.
Menu information
If the user attempts to make changes that cannot be made or which lie outside his
user level the controller will display the following information:
Unauthorised
Make new logon
No changes in
this menu
Alarm chiller
AL 980925 14:20
Menu help text
There are extra help-text to most of the menu pages. By pressing the
OK
button
(except when in
”Change mode”)
the extra text will be displayed.