20
Manual C
ORRIGO
C-
SERIES
2000.09
Information series - rolling display
During normal running when the buttons are not in use a series of menu pages is
shown.
The display alternates between a general display with product description and
clock, setpoint/actual temperature, output status for the control outputs Y1,Y2 and
Y3 and setpoint, actual value and output status for supply air fan and exhaust air
fan and sepoint and actual value for the humidity control.
The initial display shows the product name, date and time.
Program version number
By pressing
Esc
when the gerneral display is active the
product version number is displayed. For LON-models the 12 digit neuron
ID-number is also displayed
The information menu is started by leaving the main menu by means of
Esc
or by
leaving the keyboard unused for a ten-minute period. First, the start window will be
shown for 10 seconds and then the three displays shown above will alternate at
three-second intervals.
Main menu
Press the
OK
button.The information menu will stop and the main menu will open
immediately.
The main menu consists of a number of menu headings and what can be seen and
done is governed by the log-in level of the user, as described below.
When the main menu is opened TEMP CONTROL is always displayed at the top of
the display.
The arrow marker to the left of TEMP CONTROL means that this heading is mar-
ked and pressing the
OK
button opens this menu and shows its submenus.
Arrows at the right of the display indicate that there are headings above and below
the text that is currently being displayed. Move by using the arrow buttons.
The main menu has the following headings:
Login
Configuration
Only shown at user level 3
Temp Control
Pressure control
Models C20 and C40 only
Humidity control
Models C30 and C40 only
Running mode
AI Analogue in
DI Digital in
AO Analogue out
DO Digital out
Scheduler
Alarm settings
Only shown at user level 1 or higher
Settings
Only shown at user level 2 or higher
* CORRIGO C40 *
Mo 990208 1012
Setpoint/Actual
20,0°C / 20,0°C
Y1 / Y2 / Y3
0% / 45% / 0%
SF/Setp/Act/Out
275Pa/275Pa/70%
EF/Setp/Act/Out
250Pa/250Pa/60%
Setpoint/Actual
50% RH / 48% RH
>Temp control
á
AI Analogue in
â