Carbon monoxide (CO) transmitter

COF is a detector intended for demand-controlled ventilation in park-

ing garages and road tunnels etc. The detector measures the CO 

concentration using an electrochemical method of measurement char-

acterised by high selectivity and accuracy even in low concentrations. 

The output signal is a linear representation of the gas concentration. 

Technical data

Supply voltage 

 

12...28 V DC 

Power consumption 

20 mA 

Method of measurement 

Electrochemical 

Outputs 

 

4...20 mA, two-wire 

 

 

0...10 V DC, three-wire 

Calibration 

 

Automatic zero adjustment, the unit must  

 

 

be manually calibrated once a year 

Ambient temperature 

-10...+40°C 

Ambient humidity    

0...90 % RH 

Protection class   

IP56 

Dimensions (WxHxD) 

80 x 82 x 86 mm 

Weight 

 

0.190 kg 

Material, casing   

Polycarbonate 

Type of gas 

 

Carbon monoxide (CO) 

Measuring range   

0...300 ppm

Accuracy 

 

±3 % 

Lifetime sensor 

 

~ 6 years

Installation

COF is recommended to be mounted in breathing height, about 150-180 

cm above the floor. One detector is to be placed per 200-500 square 

metres garage surface, provided that the surface is open (without any 

”pockets”) and that there is continuous air flow. If there are any ”service 

pits”, a COF should be installed in each pit. Install the detector at least 
50 cm from ventilation ducts and room corners. The transmitter must be 
mounted with the cable connection pointing up.

Wiring

The output signal is set via a jumper according to the figures below.

(+) 12...28 V DC

0...10 V DC

!

(+)

(-)

(+)

(-)

CONTROLLER

0...10 V DC

(+)

(-)

(+) 12...28 V DC

(-)

R = Max. 300 Ohm

CONTROLLER

4...20 mA

Control and alarm levels

We recommend using two alarm levels, pre-alarm and full alarm. In 
case of a pre-alarm, the fans are to be set to full speed and strategi-

cally placed flashing lights are to be activated. In case of a full alarm, 

strategically placed sirens are to be started, advising people to leave 
the garage immediately. Recommended levels for these alarms:

Pre-alarm 

50 ppm

Full alarm 

100 ppm

This product carries the CE mark. For more information, see  
www.regincontrols.com.
This product is TÜV-approved in accordance with VDI 2053.

Contact

AB Regin, Box 116, SE-428 22 Kållered, Sweden 
Tel: +46 31 720 02 00, Fax: +46 31 720 02 50 
www.regincontrols.com, [email protected]