Configuration

All settings, apart from choosing internal or external sensor, are
made using the four buttons on the front. To access the con-
figuration menu, simultaneously depress and hold the two arrow-
buttons. After a few seconds the display will show 00

0

. Now

release the arrow-buttons and klick the minus-button three times
in rapid succession. The display will show the first menu-page.
Move through the menu pages using the arrow-buttons. Change
parameter values using the + and - buttons.
To exit the configuration menu, simultaneously click the two arrow-
buttons. The ALD24A1 will also automatically exit the menu system
after a few minutes of button inactivity.

Menu listing

(FS = Factory settings)

SETP HEATING Setpoint heating. Range 0...30°C in 0.5K

increments. (FS = 21.0°C)

If presence detection is activated (see below) two heating setpoint
settings will be shown.
SETP HEATING Setpoint heating, occupied. Range 0...30°C in

0.5K increments. (FS = 21.0°C)

SETP HEATING Setpoint heating, unoccupied. Range 0...30°C in

0.5K increments. (FS = 17.0°C)

SETP COOLING Setpoint cooling. Range 0...30°C in 0.5K

increments. (FS = 24.0°C)

If presence detection is activated (see below) two cooling setpoint
settings will be shown.
SETP COOLING Setpoint cooling, occupied. Range 0...30°C in

0.5K increments. (FS = 24.0°C)

SETP COOLING Setpoint cooling, unoccupied. Range 0...30°C in

0.5K increments. (FS = 28.0°C)

P-BAND

Proportional band, heating and cooling. Range
0.5...99.5K in 0.5K increments. (FS = 5.0K)

I-TIME

Reset time. range 0...999 seconds. (FS = 0)

N.B.

 the range is 999 and not 99.9.

N.B.

 0 = P-control, no integration factor.

CAL

Temperature reading calibration. The sensor
value can be corrected ±3K in 0.1K increments.

N.B.

 Use with care. All units are factory calibrated.

Presence detection. ON / OFF. When active, one
of two symbols will be displayed to indicate
which of the two running modes is active.
Man in rectangle = Occupied mode
Man outside rectangle = Unoccupied mode

Setpoint offset

During normal running the configured sepoint value can be
offset ±3K in 0.5K increments.
Klick on either the + button or the - button and the present
displacement will be shown. Change the value using the
+ button or the - button to increase or decrease the value. The
ALD24A1 will automatically revert to normal running display
after 3 seconds of button inactivity.

EMC emission and immunity standard

This product conforms with the requirements of European
EMC standards CENELEC EN50081-1 och EN50082 - 1 and
carries the CE mark.

1
2
3
4
5
6
7
8

Supply  24 V AC
Supply neutral
Output  0...10 V
Signal neutral
Change-over
Signal neutral
External sensor
Presence signal

°C

HEATING

COOLING

SETP.

P-BAND
I-TIME
CAL

Menu
parameter

Running mode

Output

Heating Cooling

Actual temperature

INSTRUCTIONS

INSTRUCTIONS

All neutrals internally connected

Summary of Contents for ALD24A1

Page 1: ...as s att den kortsluter de tv v nstra pinnarna se figur Plint 7 Extern givare NTC Plint 6 Signalnoll Rumsregulator en 0 10 V utg ng Change over funktion ALD24A1 har ing ng f r change over som automati...

Page 2: ...normaldrift Inst llnings omr de 0 30 C i 0 5K steg FI 24 0 C SETP COOLING B rv rde kyla ekonomidrift Inst llnings omr de 0 30 C i 0 5K steg FI 28 0 C P BAND P band v rme och kyla Inst llnings omr de...

Page 3: ...e ALD24A1 change over function input can be used to automatically control the ALD24A1 mode of operation i e heating or cooling function Connect a sensor of type REGIN NTC or a potential free shorting...

Page 4: ...ed Range 0 30 C in 0 5K increments FS 24 0 C SETP COOLING Setpoint cooling unoccupied Range 0 30 C in 0 5K increments FS 28 0 C P BAND Proportional band heating and cooling Range 0 5 99 5K in 0 5K inc...

Page 5: ...e 7 so bewegt wird dass sie die beiden linken Stifte kurzschlie t siehe Abbildung Klemme 7 Externer Geber NTC Klemme 6 Signal neutral Raumregler ein 0 bis 10 V Ausgang Saisonumstellung Der ALD24A1 hat...

Page 6: ...ieb Einstellungsbereich 0 30 C in 0 5 K Schritten FI 24 0 C SETP COOLING Sollwert K hlen Sparmodus Einstellungsbereich 0 30 C in 0 5 K Schritten FI 28 0 C P BAND P Band Heizen und K hlen Einstellungsb...

Page 7: ...al Change over L entr e change over peut automatiquement basculer le ALD24A1 entre chauffage et refroidissement Elle peut tre utilis e avec des sondes REGIN NTC ou un contact sec neutre signal Le r gu...

Page 8: ...consigne refroidissement occup Consigne 0 30 C variable par 0 5K PP 24 0 C SETP COOLING Point de consigne refroidissement libre Con signe 0 30 C variable par 0 5K PP 28 0 C P BAND Bande proportionnell...

Reviews: