Regency Horizon® HZ40E-10 Gas Fireplace
|
26
installation
Maximum
36"(914mm)
Minimum
6"(152mm)
Straight Out Horizontal Venting
Diagram 1
Please note the minimum centerline for
basic install shown above.
HORIZONTAL TERMINATIONS
RIGID PIPE 4" X 6-5/8
"
The diagrams below shows examples of horizontal termination arrangements using one, two, or three 90
o
elbows (two 45
o
elbows equal one 90
o
elbow)
1. A maximum of three 90
o
elbows are permitted (not including the starting 45
o
elbow at the lue collar when using rigid venting).
2. Minimum distance between elbows is 1 ft. (305mm).
• Maintain clearances to combustibles as listed in the "Clearances" section.
• Horizontal vent must be supported every 3 feet.
• Firestops are required at each loor level and whenever passing through a wall.
• Must use optional rigid pipe adaptor (Part# 510-994. when using rigid pipe vent systems.
• A vent guard should be used whenever the termination is lower than the speciied minimum or as per local codes.
•
Flex system can only be used up to 10 feet - otherwise rigid venting must be used.
CL
CL
Min.
height
(Rigid
)
36-1/4"
(743mm)
center
of hole