10
|
Regency Horizon® HZ40E-10 Gas Fireplace
|
10
installation
Caution Requirements
The top, back and sides of the ireplace are deined by
standofs. The metal ends of the standof may
NOT
be
recessed into combustible construction.
WARNING
Fire hazard is an extreme risk
if these clearances (air space) to combustible materials are not
adhered to. It is of greatest importance that this ireplace and vent
system be installed only in accordance with these instructions.
CLEARANCES
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related ires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance
that this ireplace and vent system be installed only in accordance with these instructions.
Clearance:
Dimension
Measured From:
A: Mantel Height (min.)
17" (330mm)
Top of Fireplace Opening
B: Sidewall (on one side)
8" (203mm)
Side of Fireplace Opening
C: Ceiling
(room and/or alcove)
22" (559mm)
Top of Fireplace Opening
D: Mantel Depth (max.)
13" (330mm)
22" Above Fireplace Opening
E: Alcove Width
84" (2134mm)
Sidewall to Sidewall (Minimum)
F: Alcove Depth
36" (914mm)
Front to Back Wall (Maximum)
G: From Floor
27" (686mm)
Top of Fireplace Opening
Note:
0"
No hearth required
Installed close
to ceiling.
Flue Clearances to Combustibles
Horizontal - Top
3"
Horiztonal - Side
2"
Horiztonal - Bottom
2"
Vertical
2"
Passing through wall/
floor/ceiling - when
irestop is used.
1-1/2"
Alcove
E
F
F
E
D
A
B
Installed Close
to Floor
G
The
HeatWave
Duct Kit and the Heat
Release Kit have diferent clearance
and framing requirements, check
the
HeatWave
and Heat Release
manual for details.
Heat Release Kit