24
Regency GF900L-1 Gas Fireplace
installation
The shaded area in the diagram shows all allowable combinations
of straight vertical and offset to vertical terminations, using two
45
o
elbow, with
Rigid Pipe Flueing Systems
.
• Flue must be supported at offsets.
• Minimum distance between elbows is 305mm.
• Maintain clearances to combustibles as listed in the
"Clearances" section in the manual.
• Horizontal flue must be supported every 1M.
• Refer to the "Flue Restrictor Position" section for
details on how to change the flue restrictor from the
factory setting of Set 0 or Set 3 if required.
• Note: For ULPG Flue Restrictor - Set to "0" - 75mm
open.
FLUEING ARRANGEMENT FOR VERTICAL TERMINATIONS
Vertical Venting with One(1) 90
o
Elbows (1 - 90
o =
2 - 45
o
)
6.7m
4m
Res
trictor Set #3
18mm open
Metres
Vertical Height (Metres)
NOTE: FOR ULPG
FLUE RESTRICTOR
SET to “0” - 75MM OPEN