Manual - TC.P Quadro
HMI and RCU
2016-08-05
169/330
V04.52
6
6.3.5.
Troubleshooting using the Human Machine Interface (HMI)
6.3.5.1. Acknowledging warning and error messages
If error states occur, the electrical power supply changes to the Error
operating state.
The electrical power supply is returned to the Ready state by acknowl-
edging the error messages (
<Escape>
button on the main screen) if the
reason for the error has been rectified.
Acknowledging will delete all actual warnings and error messages.
Prior to acknowledging, all messages in the error and warning lists
must be analysed. In particular the error and warning sub-groups pro-
vide further, more detailed information on the error or the warning.
6.3.5.2. Error during initialisation
Errors that occur during the initialisation are indicated in a separate
window. After the error window is acknowledged, the main screen ap-
pears. The electrical power supply is in the Error state and the message
Login Error is displayed in the message bar on the main screen. After
eliminating the reason for the error, a restart (switch off and on at the
circuit breaker) is required:
The following initialisation errors are displayed in an error window.
Error
Reason and correction
“No call for login”
The internal CAN connection cable between device
and HMI is not correctly connected.
HMI: contact manufacturer
RCU: check seating of cable connection between
RCU
and X101 interface, otherwise contact
manufacturer
Table 93
Error description, HMI initialisation (login error)