Electric part-turn actuators SP 0, SPR 0

INSTALLATION, SERVICE AND
MAINTENANCE INSTRUCTIONS

Summary of Contents for SP 0

Page 1: ...74 0802 02 74 0802 02 Electric part turn actuators SP 0 SPR 0 INSTALLATION SERVICE AND MAINTENANCE INSTRUCTIONS...

Page 2: ...perating angle Transmitter Warranty period months Input operating signal Serial number of electric motor Serial number of transmitter Serial number of position controller Tests made in accordance with...

Page 3: ...justment of position switches Fig 4 14 3 2 Adjustment of resistant transmitter Fig 5 15 3 3 Adjustment of the Electronic Position Transmitter EPV the Resistive Transmitter Potentiometer with the Conve...

Page 4: ...components switches have to be consulted with producer 1 2 Safety instructions EA of SP and SPR types are reserved technical devices with higher rate of danger with possibility of installation in area...

Page 5: ...rque Manual control 0096 STN ISO 7000 Protection terminal 5019 IEC 60417 1 4 Warranty conditions The supplier is responsible for completeness of the delivery and guarantees these specifications of the...

Page 6: ...reas of industrial plants without temperature and humidity regulation protected against climate effects e g direct sunshine Installation and operation of EA is possible in any position Vertical positi...

Page 7: ...to 150 Hz with shift amplitude of 0 15 mm for f fp and acceleration amplitude 19 6 m s2 for f fp transition frequency fp is from 57 up to 62 Hz AH 2 medium impacts shocks and vibrations AG 2 with ser...

Page 8: ...an be optionally equipped also with the terminal board for electric motor connection 6 the terminal board for transmitter connection 7 and a resistive transmitter potentiometer 8 Plugs for cables 9 an...

Page 9: ...ue value 7 Nm only Actuators with max load torque 25 Nm are self locking up to torque value 15 Nm only 2 For 24 V DC 50 30 3 Operating time as a funkcion of torque diagram No 1 4 Switching elements fo...

Page 10: ...f output signal of EPV Z 0 2 mA O 0 1 mA b 3 wire version without built in power supply or with built in power supply Current signal 0 20 mA DC Current signal 4 20 mA DC Current signal 0 5 mA DC Power...

Page 11: ...5A 250V AC Digital outputs 4x LED supply error adjustment opening closing with two colour LED Error status control switch 24 V 2W POR Reaction at error situation transmitter error error message LED C...

Page 12: ...e with EN 60 654 IEC 60654 1 and 60654 3 Package is a box Products in boxes is possible to load on the pallets pallet is returnable On the outer side of the package is stated manufacturer label name a...

Page 13: ...us waste 2 Installation and dismantling of actuator Abide by safety measures Notes Repeatedly verify whether placing of EA correspondents to part Operating conditions If actual conditions differ from...

Page 14: ...th a tube with threads on the both ends see dimensional drawing P 0100 While mounting the lever mechanism the angle between the lever and the pull rod is to be more than 15 and less than 165 The coars...

Page 15: ...ection protection switched off directly with the corresponding position or torque switches After electric connection it is recommended Checking of wiring Set the actuator into a mid position Check the...

Page 16: ...on professional competence Disconnect the electrical servo drive from electrical power network Observe safety regulations The adjustment can be performed at a mechanically and electrically connected...

Page 17: ...0 of the EA SPR terminal board Put the actuator to the position closed with the handwheel or with the local electric position control until the corresponding position switch S4 Rotate the transmitter...

Page 18: ...ate measured on the terminals 81 82 to 0 mA or 4mA Set the actuator to the position open Turn the adjusting trimmer GAIN Fig 7 to adjust the output current signal rate measured on the terminals 81 82...

Page 19: ...torque 5 blinks way of regulation 4 blinks wide position Notes 1 The controller at autocalibration automatically sets the feedback type resistant current 2 Parameters set in the production plant if c...

Page 20: ...he controller with D4 diode at initialisation 4 blinks improper connection of the torque switches 5 blinks improper connection of the feedback transmitter 8 blinks bad sense of actuator s turning dire...

Page 21: ...son as required in the Chapter 1 2 After the EA is put into operation it is necessary to check whether during manipulation its surface finishing was not damaged the damages should be eliminated to pre...

Page 22: ...ssion bearings type KX with yellow liner and actuators gearings Changing or filling grease up during first years operation is not required If the electric actuator works only occasionally it is necess...

Page 23: ...3 592 382 3 1 Capacitor 300 047 63 540 305 1 Micro switch CHERRY DB 6G A1LB 64 051 466 4 1 Resistant wire transmitter potentiometer RP19 1x100 64 051 812 8 1 Resistant wire transmitter potentiometer R...

Page 24: ...22 SP 0 SPR 0 6 Accessories 6 1 Wiring diagrams Wiring diagrams for EA SP 0 Wiring diagrams for EA SP 0 24 V DC...

Page 25: ...Z315a connection of EA SPR 24 V DC with resistant feedback and with space heater B1 remote transmitter resistive single B3 electronic position transmitter EPV S3 positional switch open S4 positional...

Page 26: ...24 SP 0 SPR 0 6 2 Dimensional drawings The dimensions are valid for version with convertern and SPR 0 with controller...

Page 27: ...SP 0 SPR 0 25...

Page 28: ...26 SP 0 SPR 0...

Page 29: ...SP 0 SPR 0 27...

Page 30: ...28 SP 0 SPR 0...

Page 31: ...SP 0 SPR 0 29 Shape A Shape C Position indicator VERSION FLANGE The dimensions are valid for version with converter SHAPE...