Maintenance
Vacuum spray degassing — 28.08.2019 - Rev. B
English — 27
9.5
Reset
Guidance through the reset can be provided via the Reflex Control Smart app and must then be confirmed by pressing the Auto
button when requested.
You can perform a reset it there is a need to reset the system to factory settings.
1.
Ensure that the system is in stop mode.
2.
Simultaneously press the Auto button and the Stop button for longer than 5 seconds. All LEDs flash briefly.
3.
Release the stop and auto buttons again.
The reset is performed and the device is reset to the factory settings. The device can be restarted via the Reflex Control Smart app.
Alternatively, the system can be operated in Levelcontrol mode without the app.
Note!
After the reset, the continuous degassing and interval degassing operating times are automatically synchronised from
this new point in time, see chapter 8.1.1 "Automatic mode" on page 23 .
10
Maintenance
CAUTION
Risk of burns on hot surfaces
Hot surfaces in heating systems can cause burns to the skin.
•
Wait until hot surfaces have cooled down or wear protective safety gloves.
•
The operating authority is required to place appropriate warning signs in the vicinity of the device.
CAUTION
Risk of injury due to pressurised liquid
If installation, removal or maintenance work is not carried out correctly, there is a risk of burns and other injuries at the
connection points, if pressurised hot water or hot steam suddenly escapes.
•
Ensure proper installation, removal or maintenance work.
•
Ensure that the system is de-pressurised before performing installation, removal or maintenance work at the connection
points.
The ’Servitec’ must be serviced annually or after 16,000 degassing intervals, whichever comes first.
Note!
This corresponds to a continuous degassing time of approximately 14 days or a continuous degassing time of 7 days
+ 1 year interval degassing with a standard setting.
The maintenance intervals depend on the operating conditions and the degassing times.
The following recommended standard value must not be exceeded:
•
Continuous degassing: Continuous degassing time for the largest "Va" system volume, see chapter 5 "Technical data" on
page 11 .
•
Interval degassing: Setting values according to the Service menu.
An indication that the annual service is to be performed after the set device operating time has elapsed is given in the form of a
warning (LED configuration, see chapter 9.4 "Messages" on page 25 ). The warning is acknowledged by pressing the Auto button.
The warning is also displayed in the app.
Note!
Maintenance work must be carried out and confirmed by specialist personnel or the Reflex Customer Service.