Maintenance
18
—
English
Vacuum spray degassing
—
18.12.2019
–
Rev. A
E R
Code
Alarm
F loating
contact
Ca use
Remedy
Alarm
reset
12
Filling time
-
Set value for the maximum filling duration has
been exceeded
•
Check set value in the Customer or Service
menu.
•
Check the water loss and correct, if necessary.
Quit
13
Filling volume
-
Set value exceeded.
•
Check set value in the Customer or Service
menu.
•
Check the water loss and correct, if necessary.
Quit
14
Discharge period
-
•
Set value exceeded.
•
"DC" degassing line closed.
•
Dirt trap clogged.
•
Check set value in the Customer or Service
menu.
•
Open the degassing pipe.
•
Clean the dirt trap.
Quit
15
Make-up valve
-
Contact water meter measures without make-
up request.
Check the 2-way motorized ball valve (WV) for
leaks.
Quit
16
Power failure
-
No power.
Connect to power supply.
-
19
Stop
˃
4 hours
-
Device is in stop mode for more than 4 hours.
Set the controller to Automatic mode.
-
20
Maximum make-up
quantity
-
Set value exceeded.
Reset the "Make-up quantity" meter in the
Customer menu.
Quit
21
Maintenance
recommended
-
Set value exceeded.
Carry out maintenance.
Quit
24
Water treatment
-
•
Set value for soft water capacity
exceeded.
•
Time interval for replacement of the
cartridge exceeded.
Replace the softening cartridges.
-
26
Conductivity measurement
-
Measured value outside the measuring range.
•
Check set value in the Customer or Service
menu.
•
Check the sensor and cabling.
-
27
Conductivity exceeded
-
•
Set value exceeded.
•
Cartridge capacity expired.
•
Check set value in the Customer or Service
menu.
•
Replace cartridge.
-
30
I/O module fault
-
•
I/O module defective.
•
Connection between option card and
controller faulty.
•
Option card defective.
•
Replace the I/O module.
•
Check the connection between option card
and controller.
•
Replace the option card.
-
31
EEPROM defective
Yes
•
EEPROM defective.
•
Internal calculation error.
Inform Reflex Customer Service.
-
32
Undervoltage
Yes
Supply voltage not achieved.
Check power supply.
-
33
Adjustment parameter
-
EPROM parameter memory defective.
Inform Reflex Customer Service.
Quit
34
Main board communication
faulty
-
•
Connecting cable defective.
•
Main board defective.
Inform Reflex Customer Service.
Quit
35
Digital input voltage faulty
-
Short-circuit of input voltage.
Check the wiring at the digital inputs (water meter,
for example).
-
36
Analogue input voltage
faulty
-
Short-circuit of input voltage.
Check the wiring at the analogue inputs
(pressure/conductivity).
-
37
Input voltage MKH1
-
Short-circuit of input voltage.
Check the wiring of the 2-way motorized ball valve.
-
9
Maintenance
CAUTION
Risk of burns on hot surfaces
Hot surfaces in heating systems can cause burns to the skin.
•
Wait until hot surfaces have cooled down or wear protective safety gloves.
•
The operating authority is required to place appropriate warning signs in
the vicinity of the device.
CAUTION
Risk of injury due to pressurised liquid
If installation, removal or maintenance work is not carried out correctly, there is a
risk of burns and other injuries at the connection points, if pressurised hot water
or hot steam suddenly escapes.
•
Ensure proper installation, removal or maintenance work.
•
Ensure that the system is de-pressurised before performing installation,
removal or maintenance work at the connection points.
The ’Servitec’ must be serviced annually or after 16,000 degassing intervals,
whichever comes first.
Note!
Shorter maintenance intervals are required if the default setting for
interval degassing of 8 degassing cycles and 12 h idling time exceeds
the following times for continuous degassing:
•
Continuous degassing time of about 14 days
or
•
Continuous degassing time of 7 days + 1 year interval degassing
with default setting.
The maintenance intervals depend on the operating conditions and the
degassing times.
The annual maintenance is displayed upon expiry of the set operating time. Use
"Quit" to acknowledge the "Maintenance recommended" message.
Note!
Maintenance work must be carried out and confirmed by specialist
personnel or the Reflex Customer Service.