Maintenance 

 

 

 

18 

  English  

Vacuum spray degassing 

 18.12.2019 

 Rev. A 

 

 

E R 

Code 

Alarm 

F loating 

contact 

Ca use 

Remedy 

Alarm 

reset 

12 

Filling time 

Set value for the maximum filling duration has 

been exceeded 

 

Check set value in the Customer or Service 

menu. 

 

Check the water loss and correct, if necessary. 

Quit 

13 

Filling volume 

Set value exceeded. 

 

Check set value in the Customer or Service 
menu. 

 

Check the water loss and correct, if necessary. 

Quit 

14 

Discharge period 

 

Set value exceeded. 

 

"DC" degassing line closed. 

 

Dirt trap clogged. 

 

Check set value in the Customer or Service 

menu. 

 

Open the degassing pipe. 

 

Clean the dirt trap. 

Quit 

15 

Make-up valve 

Contact water meter measures without make-

up request. 

Check the 2-way motorized ball valve (WV) for 

leaks. 

Quit 

16 

Power failure 

No power. 

Connect to power supply. 

19 

Stop 

˃

  4 hours 

Device is in stop mode for more than 4 hours. 

Set the controller to Automatic mode. 

20 

Maximum make-up 
quantity 

Set value exceeded. 

Reset the "Make-up quantity" meter in the 
Customer menu. 

Quit 

21 

Maintenance 
recommended 

Set value exceeded. 

Carry out maintenance. 

Quit 

24 

Water treatment 

 

Set value for soft water capacity 
exceeded. 

 

Time interval for replacement of the 

cartridge exceeded. 

Replace the softening cartridges. 

26 

Conductivity measurement 

Measured value outside the measuring range. 

 

Check set value in the Customer or Service 

menu. 

 

Check the sensor and cabling. 

27 

Conductivity exceeded 

 

Set value exceeded. 

 

Cartridge capacity expired. 

 

Check set value in the Customer or Service 
menu. 

 

Replace cartridge. 

30 

I/O module fault 

 

I/O module defective. 

 

Connection between option card and 

controller faulty. 

 

Option card defective. 

 

Replace the I/O module. 

 

Check the connection between option card 

and controller. 

 

Replace the option card. 

31 

EEPROM defective 

Yes 

 

EEPROM defective. 

 

Internal calculation error. 

Inform Reflex Customer Service. 

32 

Undervoltage 

Yes 

Supply voltage not achieved. 

Check power supply. 

33 

Adjustment parameter 

EPROM parameter memory defective. 

Inform Reflex Customer Service. 

Quit 

34 

Main board communication 

faulty 

 

Connecting cable defective. 

 

Main board defective. 

Inform Reflex Customer Service. 

Quit 

35 

Digital input voltage faulty 

Short-circuit of input voltage. 

Check the wiring at the digital inputs (water meter, 
for example). 

36 

Analogue input voltage 
faulty 

Short-circuit of input voltage. 

Check the wiring at the analogue inputs 
(pressure/conductivity). 

37 

Input voltage MKH1 

Short-circuit of input voltage. 

Check the wiring of the 2-way motorized ball valve. 

 

 

9

 

Maintenance 

 

 CAUTION 

 

Risk of burns on hot surfaces 
Hot surfaces in heating systems can cause burns to the skin. 

 

Wait until hot surfaces have cooled down or wear protective safety gloves. 

 

The operating authority is required to place appropriate warning signs in 

the vicinity of the device. 

 

 CAUTION 

 

Risk of injury due to pressurised liquid 
If installation, removal or maintenance work is not carried out correctly, there is a 

risk of burns and other injuries at the connection points, if pressurised hot water 

or hot steam suddenly escapes. 

 

Ensure proper installation, removal or maintenance work. 

 

Ensure that the system is de-pressurised before performing installation, 

removal or maintenance work at the connection points. 

 

 

The ’Servitec’ must be serviced annually or after 16,000 degassing intervals, 

whichever comes first. 

 



Note! 
Shorter maintenance intervals are required if the default setting for 

interval degassing of 8 degassing cycles and 12 h idling time exceeds 

the following times for continuous degassing: 

 

Continuous degassing time of about 14 days 

or 

 

Continuous degassing time of 7 days + 1 year interval degassing 
with default setting. 

 

The maintenance intervals depend on the operating conditions and the 
degassing times. 
The annual maintenance is displayed upon expiry of the set operating time. Use 

"Quit" to acknowledge the "Maintenance recommended" message. 

 



Note! 
Maintenance work must be carried out and confirmed by specialist 

personnel or the Reflex Customer Service. 

 

Summary of Contents for Servitec 35

Page 1: ...Vacuum spray degassing 18 12 2019 Rev A Servitec 35 95 Control Basic controller GB Operating manual Original operating manual...

Page 2: ...d commissioning certificate 11 7 Commissioning 11 7 1 Checking the requirements for commissioning 11 7 2 Setting the minimum operating pressure for Magcontrol 11 7 3 Controller 11 7 3 1 Operator panel...

Page 3: ...perating manual DANGER Danger of death and or serious damage to health The sign in combination with the signal word Danger indicates imminent danger failure to observe the safety information will resu...

Page 4: ...gassing and make up station Its main areas of application are heating and cooling circuits and systems in which malfunctions due to dissolved or free gases are to be prevented The Servitec provides th...

Page 5: ...The pumpreturns degassed water from the vacuum spraytube to the system whereit again begins to dissolve gases There it is able to dissolvegases again Discharge The PU pumpshuts off The system continue...

Page 6: ...softening systems The operational reliability of the device is assured and prevents automatic make up during major water loss or small leaks Fillset Compact for make up Fillset Compact with integrated...

Page 7: ...t 6 2 Preparatory work Condition of the delivered device Check all screw fittings and electrical connections of the Servitec for proper seating Tighten the screws and fittings as necessary Preparing t...

Page 8: ...ystem near the diaphragm type MAG expansion vessel This ensures that the pressure in the diaphragm type expansion vessel is monitored In this case select the Magcontrol operating mode in the controlle...

Page 9: ...ed for facilities with pressurisation stations and enables flexible operation at constant pressure Demand matched water make up takesplace depending on the measured water level in the expansion vessel...

Page 10: ...e device 20 Level signal 21 Level 18V 22 PE shield Pressure analogue input Pre wired 23 Pressure signal 24 Pressure 18 V 25 0 10 V correcting variable Ball control valve Pre wired 26 0 10 V feedback 2...

Page 11: ...leaned of welding residue and dirt before commissioning The entire facility system is filled with water and all gases have been vented in order to ensure a circulation through the entire system The el...

Page 12: ...trol make up variant 5 Enter the actuating pressure of the heat generator safety valve Safety valvepressure Indicated when selecting the Magcontrol make up variant 6 Enter the minimum operating pressu...

Page 13: ...r a successful vacuum test open the ball valve with dirt trap 6 If the controller displays the Insufficient water error message confirm with Quit The vacuum test is completed Note The obtainable vacuu...

Page 14: ...installed standard Only displayed if YES has been set in the With water meter menu option Make up quantity OK Delete meter yes Set the displayed make up quantity to 0 no The displayed water quantity i...

Page 15: ...omatic make up The Servitec controller monitors the functions Faults are displayed and evaluated For automatic mode you can set three different degassing programmesin the Customer menu see chapter 8 2...

Page 16: ...ting CAUTION Risk of injury dueto pumpstart up Hand injuries may occur when the pumpstarts up if you turn the pumpmotor at the impeller using a screwdriver Switch the pumpto a zero volts state before...

Page 17: ...enu on page 16 ER Code Alarm Floating contact Cause Remedy Alarm reset 01 Minimum pressure Yes For Magcontrol setting only Set value not reached Water loss in the system Pumpfault Expansion vessel def...

Page 18: ...ot achieved Check power supply 33 Adjustment parameter EPROM parameter memory defective Inform ReflexCustomer Service Quit 34 Main board communication faulty Connecting cable defective Main board defe...

Page 19: ...the housing of the ST 1 dirt trap 6 Open the ball valve upstream of the ST 1 dirt trap 7 Press Auto on the controller s operator panel The Servitec is switched on and the PU pumpis in operation Note...

Page 20: ...cooled down or wear protective safety gloves The operating authority is required to place appropriate warning signs in the vicinity of the device CAUTION Risk of injury dueto pressurised liquid If ins...

Page 21: ......

Page 22: ...SI2003enA 9127373 01 20 ReflexWinkelmann GmbH Gersteinstra e 19 59227 Ahlen Germany 49 0 2382 7069 0 49 0 2382 7069 9546 www reflex de...

Reviews: