Controller
Vacuum spray degassing — 06.07.2016 - Rev. B
English — 39
9.4
Default settings
The device controller is shipped with the following default settings. Use the Customer menu to adjust these values to local conditions. In
specific cases, it is possible to further adjust the values in the Service menu.
Customer menu
Parameter
Setting
Remarks
Language
EN
Display language
Servitec
Magcontrol
For systems with diaphragm-type pressure expansion
tank
Minimum operating pressure p0
1.0 bar
Only Magcontrol
Safety valve, pressure
3.0 bar
Pressure value for the safety valve of the heat generator
in the system to trip
Next maintenance
12 months
Time left to the next due maintenance
Floating alarm contact
NO
Only the messages marked in the message list
Makeup
Maximum makeup quantity
1000 Litres
Only if controller with "With water meter yes"
Maximum makeup time
20 minutes
Only Magcontrol
Maximum makeup cycles
3 cycles within 2 hours
Only Magcontrol
Degassing
Degassing programme
Interval degassing
Continuous operation with degassing cycles
Continuous degassing time
5 hours
Time of continuous degassing
Softening (Only if "With softening yes")
Lock makeup
No
Available soft ware capacity = 0
Hardness reduction
8°dH
= Target – Actual
Maximum makeup quantity
0 Litres
Attainable makeup quantity
Soft water capacity
0 Litres
Attainable water capacity
Cartridge replacement
18 months
Replace cartridge
Service menu
Parameter
Setting
Remarks
Makeup
Pressure differential, "NSP" makeup
0.2 bar
Only Magcontrol
Pressure differential, filling pressure PF – P0 0.3 bar
Only Magcontrol
Degassing
Idling times between degassing intervals
23 hours
Idling times between the degassing intervals
Number of degassing cycles for each
interval
n = 8
Number of degassing cycles in one interval
Daily start
08:00 h
Start of the daily degassing intervals
Summary of Contents for Servitec 30
Page 2: ......
Page 56: ...Annex 56 English Vacuum spray degassing 06 07 2016 Rev B...
Page 57: ......