I/O module (optional expansion module)
6 — English
— 03.09.2020 - Rev. A
5
I/O module (optional expansion module)
The I/O module is connected and wired in the factory.
It is used to expand the inputs and outputs Control Touch controller.
Six digital inputs and six digital outputs are used to process messages and
alarms:
Inputs
Three inputs, N.C. with 24 V self potential for standard settings.
•
External temperature monitoring
•
Minimum pressure signal
•
Manual make-up of water
Three inputs, N.O. with 230 V self potential for standard settings.
•
Emergency-Off
•
Manual operation (e.g. for pump or compressor)
•
Manual operation for the overflow
Outputs
Potential-free as changeover contacts. Default settings for messages:
•
Make-up fault
•
Below minimum pressure
•
Above maximum pressure
•
Manual or Stop operation
Note!
•
For the default settings of the I/O modules, see Chapter 5.2.3 "I/O
module default settings" page 7
•
All digital inputs and outputs can be set freely as option. Settings
to be made by Reflex Customer Service, see chapter 13.1 "Reflex
Customer Service" on page 23
5.1
Technical data
Housing
Plastic housing
Width (W):
340 mm
Height (H):
233.6 mm
Depth (D):
77 mm
Weight:
2.0 kg
Permissible operating temperature:
-5 °C – 55 °C
Permissible storage temperature:
-40 °C – 70 °C
Degree of protection IP:
IP 64
Power supply:
230 V AC, 50 – 60 Hz (IEC 38)
Fuse (primary):
0.16 A time-lag
Inputs, outputs
•
6 floating relay outputs (changeover)
•
3 digital inputs 230 V AC
•
3 digital inputs 24 V AC
•
2 Analogue outputs (these are not required, because they are already
contained in the Control Touch controller).
Interfaces to the controller
•
RS-485
•
19.2 kbit/s
•
Floating
•
connection with plug or screw terminals
•
RSI-specific protocol
5.2
Settings
GEFAHR
Danger to life from electric shock!
Risk of serious injury or death due to electric shock. Some parts of the main
board may still carry 230 V voltage even with the device physically isolated
from the 230 V power supply.
•
Before you remove the covers, completely isolate the device controller
from the power supply.
•
Verify that the main circuit board is voltage-free.
5.2.1
Terminator settings in RS-485 networks
Examples for the activation and deactivation of terminators in RS–485 networks.
•
DIP switches 1 and 2 are located on the main board of the controller.
•
Maximum length for an RS–485 connection is 1000 metres
Device controller with I/O module
1
Relay outputs of the I/O
module*
•
6 digital outputs
4
"Control Touch" controller
5
RS-485 connection
2
I/O module
6
Optional RS-485 connection
•
Master - Slave
•
Field bus
3
Connections of the I/ O
conductors
* The 2 analogue outputs are not required because the Control Touch controller
already has two analogue outputs for pressure and level measurement.
Terminator settings
Jumper/switch
Settings
I/O module
Control Touch
Jumper J10
Activated
X
---
and J11
Deactivated
---
---
DIP switch 1
Activated
---
X
and 2
Deactivated
---
---
Device controllers and I/O module in Master-Slave function
1
Control Touch controller in
Master function
4
I/O module for the Slave
function
2
I/O module for the Master
function
5
I/O module for expansion
3
Control Touch controller in
Slave function