Description of the device
4 — English
— 03.09.2020 - Rev. A
4
Description of the device
4.1
Description
The Reflexomat is a pressurisation station for heating and cooling water systems.
The Reflexomat essentially comprises a controller and at least one expansion
vessel. The additional connection of secondary vessels is optionally possible. The
expansion vessel is fitted with a diaphragm to divide the vessel into an air space
and a water space. preventing the ingress of atmospheric oxygen into the
expansion vessel.
The Reflexomat provides the following safety features:
•
Optimisation of pressurisation and make-up.
•
No direct intake of air thanks to a regulation of the pressurisation and
optional automatic make-up.
•
No circulation issues caused by free bubbles in the circuit water.
•
Reduced corrosion damage due to oxygen removal from make-up
water.
Reflexomat with touch control and one compressor
•
One "RG" primary vessel as expansion vessel.
•
Touch control with one compressor as stand-alone console.
Note!
The connection of "RF" secondary vessels to the "RG" primary vessel is
optionally possible.
Reflexomat with touch control and two compressors
•
One "RG" primary vessel as expansion vessel.
•
Touch control with two compressors as stand-alone console.
Note!
The connection of "RF" secondary vessels to the "RG" primary vessel is
optionally possible.
4.2
Overview
Reflexomat with touch control and one compressor
1 Main switch
5 "RF" secondary vessel
(optional)
2 Control unit
6 "EC" expansion line
3 "RG" primary vessel
7 "LIS" level sensor
4 "SV" safety valve
Reflexomat with touch control and two compressors
1 Main switch
5 "RF" secondary vessel
(optional)
2 Control unit
6 "EC" expansion line
3 "RG" primary vessel
7 "LIS" level sensor
4 "SV" safety valve
4.3
Identification
4.3.1
Nameplate
The nameplate provides information about the manufacturer, the year of
manufacture, the manufacturing number and the technical data.
Information on the type plate
Meaning
Type
Device name
Serial No.
Serial number
min. / max. allowable pressure P
Minimum/maximum permissible
pressure
max. continuous operating
temperature
Maximum temperature for continuous
operation
min. / max. allowable temperature
/ flow temperature TS
Minimum / maximum permissible
temperature / TS flow temperature
Year built
Year of manufacture
min. operating pressure set up on
shop floor
Factory set minimum operating
pressure
at site
Set minimum operating pressure
max. pressure saftey valve
factory - aline
Factory set actuating pressure of the
safety valve
at site
Set actuating pressure of the safety
valve
Cooke Industries - Phone: +64 9 579 2185 Email: [email protected] Web: www.cookeindustries.co.nz