Technical data 

 

 

 

Fillcontrol Auto Compact — 20.10.2020 - Rev. D 

 

English  — 5 

 

 

4.5

 

Scope of delivery 

The scope of delivery is described in the shipping document and the content is 
shown on the packaging.  
Proceed as follows: 
1. 

Immediately after receipt of the goods, please check the shipment for 
completeness and damage. 

2. 

Please notify us immediately of any transport damage. 

 

Basic make-up equipment: 
• 

The pre-wired device. 

• 

Operating manual. 

 

4.6

 

Optional equipment and accessories 

The following optional equipment and expansion functions are available for this 

device: 

• 

Fillset or Fillset Compact as add-on modules for drinking water systems. 

• 

Softening with Reflex Fillsoft. 

• 

Expansions for Reflex Basic controllers: 
–  

I/O modules 

–  

Bus modules: 
• 

Profibus DP 

• 

Ethernet 

 

 

Note! 
Separate operating instructions are supplied with accessories. 

 

5

 

Technical data 

Permissible ambient temperature 

0 – 45 °C 

Degree of protection 

IP 54 

Noise level 

55 dB 

Electric output 

350 W 

Power supply 

230 V / 50 Hz 

Fusing 

4 A 

Number of RS-485 interfaces 

Weight 

19.1 kg 

Height 

620 mm 

Width 

580 mm 

Depth 

290 mm 

Inlet connection 

G ½" 

Outlet (return) connection 

G ½" 

Overflow connection 

DN 32 

Delivery rate 

195 l/h 

Max. supply pressure 

6 bar 

Max. delivery pressure 

10 bar 

Permissible gauge operating pressure 

10 bar 

Permissible operating temperature 

30 °C 

I/O module 

Optional 

 

 

Performance chart 

M

ake

-u

capac

ity

 in

 li

tre

/h

ou

 

 

Make-up pressure in bar 

 

6

 

Installation 

 DANGER 

 

Risk of serious injury or death due to electric shock. 
If live parts are touched, there is risk of life-threatening injuries. 
• 

Ensure that the system is voltage-free before installing the device. 

• 

Ensure that the system is secured and cannot be reactivated by other 
persons. 

• 

Ensure that installation work for the electric connection of the device is 
carried out by an electrician, and in compliance with electrical 
engineering regulations. 

 

 

 

 CAUTION 

 

Risk of injury due to pressurised liquid 
If installation, removal or maintenance work is not carried out correctly, there 
is a risk of burns and other injuries at the connection points, if pressurised 
hot water or hot steam suddenly escapes. 
• 

Ensure proper installation, removal or maintenance work. 

• 

Ensure that the system is de-pressurised before performing installation, 
removal or maintenance work at the connection points. 

 

 

 

 CAUTION 

 

Risk of burns on hot surfaces 
Hot surfaces in heating systems can cause burns to the skin. 
• 

Wear protective gloves. 

• 

Please place appropriate warning signs in the vicinity of the device. 

 

 CAUTION 

 

Risk of injury due to falls or bumps 
Bruising from falls or bumps on system components during installation. 
• 

Wear personal protective equipment (helmet, protective clothing, 
gloves, safety boots). 

 

 

 

Note! 
Confirm that installation and start-up have been carried out correctly 
using the installation and commissioning certificate. This action is a 
prerequisite for the making of warranty claims. 
–  

Have the Reflex Customer Service carry out commissioning and 
the annual maintenance. 

 

Summary of Contents for Fillcontrol Auto Compact

Page 1: ...Fillcontrol Auto Compact 20 10 2020 Rev D GB Operating manual Original operating manual ...

Page 2: ...on 6 6 4 Switching and make up variants 7 6 5 Electrical connection 7 6 5 1 Terminal diagram 8 6 5 2 RS 485 interface 8 6 6 Installation and commissioning certificate 8 7 Commissioning 8 7 1 Requirements for initial commissioning 9 7 2 Determining the P0 minimum operating pressure for the controller 9 7 3 Filling the device with water 9 7 4 Parametrising the controller in the Customer menu 9 7 5 F...

Page 3: ...safety information can result in death or severe irreversible injuries CAUTION Damage to health The sign in combination with the signal word Caution indicates danger failure to observe the safety information can result in minor reversible injuries ATTENTION Damage to property The sign in combination with the signal word Attention indicates a situation where damage to the product itself or objects ...

Page 4: ...3 Maximum working pressure in bar 1 2 3 4 4 Function 1 FQIRA contact water meter optional accessory 2 Fillsoft optional accessory 3 Fillcontrol Auto Compact PIS Pressure sensor WC Fresh water make up line to the device LS Signal line for insufficient water switch DC Make up line to the system circuit LIS External signal line from a pressurisation unit The device controller uses the pump to regulat...

Page 5: ...pressure in bar 6 Installation DANGER Risk of serious injury or death due to electric shock If live parts are touched there is risk of life threatening injuries Ensure that the system is voltage free before installing the device Ensure that the system is secured and cannot be reactivated by other persons Ensure that installation work for the electric connection of the device is carried out by an e...

Page 6: ...ation 1 Position the device 2 Create the water side connections of the device to the system Use connections with the same dimensions at the device for all lines 3 If required create the interfaces according to the terminal plan 6 3 1 Fitting the add on components WC Connection of the make up line to the mains separator tank OC Connection of the mains separator tank overflow DC Connection of the ma...

Page 7: ...into the system circuit LIS Level sensor To monitor the filling level in the pressurisation unit WC Make up line to the device ST Dirt trap at the shut off valve of the mains separator tank BT Mains separator tank PU Pump PIS Pressure sensor LS Insufficient water switch DN Nominal diameter of the make up line Water make up to system circuits with a pressurisation unit Pressurisation units are equi...

Page 8: ...ontroller for example Set the controller to Levelcontrol User optional 17 Make up 230 V 18 Make up 230 V 22 PE shield Pressure analogue input For output to the display For make up actuation For the Magcontrol make up variant Factory 23 Pressure signal 24 Pressure 18 V 29 A RS 485 interface User optional 30 B 31 GND 32 24 V supply E1 Supply for E1 and E2 Pre wired bridged 33 E1 Contact water meter ...

Page 9: ...or at the impeller using a screwdriver Switch the pump to a zero volts state before turning the pump at the fan wheel with a screwdriver ATTENTION Device damage due to pump start up Pump damage may occur when the pump starts up if you turn the pump motor at the impeller using a screwdriver Switch the pump to a zero volts state before turning the pump at the fan wheel with a screwdriver Fill water ...

Page 10: ...e up functions 8 1 2 Manual mode Use For testing and maintenance tasks Start Press Manual on the controller The auto LED on the controller operating panel and PU in the display flash as visual indicators of manual operation Functions After starting the manual mode you can manually activate and deactivate the pump Proceed as follows Press OK on the controller s operating panel to activate the pump ...

Page 11: ...en the make up variants Levelcontrol and Magcontrol Magcontrol In system circuits with a diaphragm expansion vessel Levelcontrol in system circuits with a pressurisation unit Min op pressure 01 8 bar The system displays the Minimum working pressure message when you have set the Magcontrol make up variant Enter the value for the minimum operating pressure Note Calculation of minimum operating press...

Page 12: ...ormation about the software version 9 2 1 Customer menu The device controller is shipped with the following default settings Use the Customer menu to adjust these values to local conditions In special cases it is possible to further adjust the values in the Service menu Parameter Setting Comment Language DE Display language Parameter Setting Comment Fillcontrol XX Magcontrol For systems with diaph...

Page 13: ...th Magcontrol Set value for the maximum pressure has been exceeded Safety valve defective Pipe to system has insufficient diameter Check the actuating pressure of the safety valve Replace the safety valve Install new pipe to the system with sufficient diameter Quit 11 Make up volume Only if With water meter is activated in the Customer menu Set value of the water meter has been exceeded Leakage in...

Page 14: ...2 1 Customer menu on page 12 Minimum operating pressure P0 Safety valve pressure PSV x Annually 10 2 Exterior leak test Check the following device components for leaks PU pumps and screw fittings Seal any leaks at the connections or replace the connections if required Seal leaking screw connections or replace if required 10 3 Cleaning the dirt trap Clean the ST dirt trap according to the following...

Page 15: ... dismantling block off all water side connections to the device 2 Disconnect the system from the power supply and secure it against unintended reactivation 3 Disconnect the power cable of the device from the power supply 4 Disconnect and remove all cables from the terminals of the device controller 5 Undo all hose and pipe connections between the device and the system and remove them completely 6 ...

Page 16: ... D EN Installation and commissioning certificate This device has been installed and commissioned in accordance with the instructions provided in the operating manual The settings in the controller match the local conditions Typ Type P0 PSV Fabr Nr Serial No ...

Page 17: ...SI1416enD 11 20 Reflex Winkelmann GmbH Gersteinstraße 19 59227 Ahlen Germany 49 0 2382 7069 0 49 0 2382 7069 9546 www reflex winkelmann com ...