Reer ARGOLUX AU S3M2 Installation, Use And Maintenance Manual Download Page 1

ARGOLUX AU S3M2

CONTROL UNIT

WITH INTEGRATED MUTING FUNCTION

INSTALLATION, USE AND MAINTENANCE

INSTALLATION, USE AND MAINTENANCE

INDEX

INDEX

OVERVIEW ...........................................................................................................4

APPLICATIONS.............................................................................................4
CONTROL UNIT THEORY OF OPERATION AND STATES.................................5
AU S3M2 FUNCTIONING DIAGRAMS.........................................................11
CONTACT STATUS .....................................................................................13
LED STATUS INDICATIONS.........................................................................14

TECHNICAL DATA ..............................................................................................15

DIMENSIONS .....................................................................................................16

INSTALLATION ...................................................................................................16

POSITIONING............................................................................................17
ELECTRICAL CONNECTIONS......................................................................22
CHECKS AND MAINTENANCE....................................................................29
MALFUNCTIONS........................................................................................29

IDENTIFICATION LABEL ......................................................................................31

WARRANTY ........................................................................................................31

Summary of Contents for ARGOLUX AU S3M2

Page 1: ...INDEX INDEX OVERVIEW 4 APPLICATIONS 4 CONTROL UNIT THEORY OF OPERATION AND STATES 5 AU S3M2 FUNCTIONING DIAGRAMS 11 CONTACT STATUS 13 LED STATUS INDICATIONS 14 TECHNICAL DATA 15 DIMENSIONS 16 INSTALLA...

Page 2: ...2...

Page 3: ...y be subject to change due to further development of the Argolux AS System Argolux AS System Since the knowledge of this manual is fundamental for the Since the knowledge of this manual is fundamental...

Page 4: ...he AU S3M2 unit promptly de energizes its output circuit and switches to fail condition Control unit status is output continuously by leds while the self test output permits remote management of infor...

Page 5: ...hase checking the response time and correct functioning of the output circuit Subsequently the AU S3M2 checks the response time of its own output circuit consisting of two guided contact safety relays...

Page 6: ...mplated by safety regulations muting status is indicated externally by an indicator light located close to the dangerous access point The AU S3M2 control unit is complete with an output for connection...

Page 7: ...e the two muting beams at the same The material must obscure the two muting beams at the same time within 4 seconds before intercepting the light barrier time within 4 seconds before intercepting the...

Page 8: ...reeing of the light barrier If one of the sensors 1 or 2 is free but the control unit does not detect correct switching of the output of the light barrier it de energizes relays A and B and indicates...

Page 9: ...sensor 3 has been freed all the elements have switched according to the correct muting sequence The configuration of muting sensors 1 and 2 in the case in which proximity type sensors capacitive indu...

Page 10: ...the material in transit by sensor 1 or 2 and detection by sensor 2 or 1 If TS1S2 is less than 4 seconds the AU S3M2 activates muting Tp 300ms Tp 300ms is the response time of the control unit on switc...

Page 11: ...be of the latching type such as for example push buttons or key selectors with spring return These must also be positioned in such a way that the operator authorized to carry out the operation has com...

Page 12: ...12 Muting function Muting function Override function Override function...

Page 13: ...ed area free area occupied Barrier output 14 19 15 18 AU S3M2 output 16 17 Self diagnosis output K1 1 Relay K1 K1 2 K2 1 Relay K2 K2 2 Muting function Muting function Object present Object not present...

Page 14: ...2 output relays de energized FAIL 3 3 Red 4 4 Red Alternative Flickering Failure of the external relays K1 and K2 AU S3M2 output relays de energized FAIL FAIL K1 K2 5 5 Yellow On Muting function Senso...

Page 15: ...10 Reset time from start of the test ms 150 Muting signals response time ms 300 Electrical connections Terminal blocks Cable lenght m 100 max Working temperature C 0 55 Sealing housing IP 40 Sealing t...

Page 16: ...ype 2 electro sensitive safety devices In a type 2 safety device the test is mandatory i e the relays are energized only after the test command has been sent and only if the test is passed Before inst...

Page 17: ...mperature where the system is installed is compatible with the temperature parameters indicated in the technical data For applications in the food and beverage industry consult the factory to check th...

Page 18: ...e light barrier installation handbook for further details of how to calculate the minimum safety distance and correct positioning of the light barrier in relation to the danger area Muting sensor posi...

Page 19: ...ding of the muting cycle When it is freed sensor 3 causes ending of the muting cycle and the possibility of starting a new muting cycle and the possibility of starting a new muting cycle FSensor 3 mus...

Page 20: ...no longer be in a plane orthogonal to the direction of feed of the pallet This configuration is very useful when a set of pallets separated by a few centimeters is to be made continuous as regards se...

Page 21: ...ig 12 single controlled access fig 12 Figure 12 Entry exit type bi directional system sensor 3 cannot be used To avoid interference between the light barrier and the muting sensors the light barrier m...

Page 22: ...rminals 2 and 3 can improve the The jump connecting terminals 2 and 3 can improve the device life duration and reliability by avoiding inefficient device life duration and reliability by avoiding inef...

Page 23: ...se contacts it is advisable to use specific anti disturbance devices which as indicated in the type B connection diagram on page 25 must be connected to the ends of the coil Warnings regarding the con...

Page 24: ...those specified in the technical data on page 14 In particular they must be of the DARK ON type Refer to table 1 on page 6 for configuration of the output of the muting sensors With relay output Fcon...

Page 25: ...25 Figure 14 Parallel connection of proximity type muting sensors Type A connection diagram Type A connection diagram...

Page 26: ...26 Type B connection diagram Type B connection diagram use of relays or external safety contactors K1 and K2 use of relays or external safety contactors K1 and K2...

Page 27: ...rs with relay output use of sensor 3 Connection to muting sensors with relay output use of sensor 3 Connection to muting sensors with relay output sensor 3 bypassed Connection to muting sensors with r...

Page 28: ...P static output use of sensor 3 Connection to muting sensors with PNP static output use of sensor 3 Connection to muting sensors with PNP static output sensor 3 bypassed Connection to muting sensors w...

Page 29: ...during operation of the plant entrance of a person or of material other than that envisaged in the area controlled by the sensors and light barrier sensor light barrier or indicator device alarms or m...

Page 30: ...instructions given in fig 15 use a 1A 250V 5x20mm delayed fuse check that the emitter and receiver of the light barrier and the muting sensors are correctly aligned and that the lenses are clean If th...

Page 31: ...R undertakes to eliminate any faults in the product repairing or replacing the fault parts free of charge both as regards material and labor However REER S p A reserves the right to replace the entire...

Page 32: ...spatch are the responsibility of the user All products and components replaced become the property of REER REER does not acknowledge any other warranty or rights except for those expressly indicated a...