8 Electrical connections
FlexiMova
®
mm - Design and Installation
45 of 80
Table 29
: Connection to the AC mains supply network AC and to the motor
Size and
Model
Power
(kW)
Rated input
current
(A)
Section of
input cable
(mm
2
)
Minimum and
maximum cable
diameter
(mm)
Type of
cable gland
used in the
converter
Type of
motor cable
required
A
F0K37
0.37
1.4
3 x1,5 +1,5
7-13
M20
CABLE FRX
4X1,5+(2X1)ST
F0K55
0.55
2
3 x1,5 +1,5
7-13
M20
CABLE FRX
4X1,5+(2X1)ST
F0K75
0.75
2.7
3 x1,5 +1,5
7-13
M20
CABLE FRX
4X1,5+(2X1)ST
F1K10
1.1
3.7
3 x1,5 +1,5
7-13
M20
CABLE FRX
4X1,5+(2X1)ST
F1K50
1.5
5.2
3 x1,5 +1,5
7-13
M20
CABLE FRX
4X1,5+(2X1)ST
B
F2K20
2.2
6.3
3 x1,5 +1,5
10-17
M25
CABLE FRX
4X1,5+(2X1)ST
F3K00
3
8.4
3 x1,5 +1,5
10-17
M25
CABLE FRX
4X1,5+(2X1)ST
F4K00
4
10.4
3 x1,5 +1,5
10-17
M25
CABLE FRX
4X1,5+(2X1)ST
C
F5K50
5.5
14.6
3 x 4 + 4
13-21
M32
CABLE FRX
(4X4+(2X1)ST)ST
F7K50
7.5
18.7
3 x 4 + 4
13-21
M32
CABLE FRX
(4X4+(2X1)ST)ST
F11K0
11
25.9
3 x 6 + 6
13-21
M32
CABLE FRX
4X6+(2X1,5)ST
D
F15K0
15
35.7
3 x 10 + 10
19-28
M40
CABLE OFS
4X10+(2X1,5)ST
F18K5
18.5
45.4
3 x 16 + 16
19-28
M40
CABLE FRX
(4X16+(2X1,5)ST)ST
F22K0
22
52.4
3 x 16 + 16
19-28
M40
CABLE FRX
(4X16+(2X1,5)ST)ST
F30K0
30
69.7
3 x 25 + 25
22-32
M40
CABLE OFS
4X25+(2X1,5) 18216
E
F37K0
37
85.9
3 x 35 + 35
27-39
M63
CABLE FRX-ST
(4X35+(2X1,5)ST)ST
F45K0
45
103.1
3 x 50 + 50
34-45
M63
CABLE FRX-ST
(4X50+(2X1,5)ST)ST
F55K0
55
122.4
3 x 70 + 70
34-45
M63
CABLE FRX-ST
(4X70+(2X1,5)ST)ST