7 Mounting instructions of the converter
34 of 80
FlexiMova
®
mm - Design and Installation
7.2.1
Wall or machine mounted
A KIT (optional) is available for wall/machine mounting, consisting of metal
plate and brackets that are fixed to the product to enable installation.
Figure 10, Figure 11
and
Figure 12
illustrate the three different KIT
models, differentiated by the size of the product.
Figure 10
: Model of the
wall-mount KIT
Sizes A, B, C
Figure 11
: Model of the
wall-mount KIT
Size D
Figure 12
: Model of the
wall-mount KIT
Size E
The product sizes A, B, C must sit flat against the wall of the fan in order to
convey the airflow from the fan through the heatsink. For sizes D and E this
function is already guaranteed by the special fixing plate mentioned above.
To ensure sufficient cooling, when mounting the device, make sure that the
exhaust air is not directly drawn in or obstructed by other devices.
Comply with the minimum clearance specified in
Table 26
.
Table 26
: Minimum clearance for mounting in the electric cabinet
Minimum clearance from other devices
mm
Top and bottom
100
Side
20