: Input data (L1, L2, L3)
Input data (L1, L2, L3)
Supply voltage
Three-phase 380 VAC / 480 VAC
Phase imbalance
+/- 2% supply voltage
Mains frequency
50 – 60 Hz +/-2%
Unity power factor (cos PHI)
> 0.98
Real power factor (
λ
)
better than 0.9
Type of power supply systems
TN networks and IT networks
Switching on feed lines
L1, L2, L3
2 times/min
Harmonic disturbance
In accordance with :
EN 61000-3-2 for converters with rated current up to 16 A
EN 61000-3-12 for converters with rated current greater than 16 A
EMC filter
C1 integrated class B up to 11 Kw
C2 class A-group1 from 15 kW up to 55 kW
Table 8
: Output data (U, V, W)
Output data (U, V, W)
Output voltage
0 – 95% of the supply voltage in the standard version
0 – 100% of the supply voltage with capacitor KIT
Output frequency
(according to the power)
0-500 Hz (resolution 0.1 Hz)
Ramp times
0.1 – 600 s
Overload capability
150% of the rated current
PWM modulation frequency
From 2 kHz to 12 kHz
dV/dt of the output phases
MAX. 5000 V/μs according to the size of the converter
Available motor control methods
V/f Control
Sensorless vector
Sensorless reluctance
Table 9
: Digital inputs
Digital inputs
Programmable digital inputs
4 (+ 2 per STO) optoisolated
ON level
18-30 V
OFF level
0-3 V
Maximum input voltage
30 VDC
Input resistance, IR
Circa 2 kΩ
Scan time
1 ms
Optional STO: Safe Torque Off
SIL 3 (IEC 61508 e EN61800-5-2)