RedEarth TROPPO - 4841 Installation And Operation Manual Download Page 1

[email protected]

www.redearth.energy

15 Fienta Place  

Darra, QLD 4076

1800 733 637

Troppo-4841 Manual - Version 1. – 17 Apr 2021

Installation and 

Operation Manual

T R O P P O - 4 8 4 1   L I T H I U M   B A T T E R Y   ( L F P )

Summary of Contents for TROPPO - 4841

Page 1: ...dearth energy www redearth energy 15 Fienta Place Darra QLD 4076 1800 733 637 Troppo 4841 Manual Version 1 17 Apr 2021 Installation and Operation Manual T R O P P O 4 8 4 1 L I T H I U M B A T T E R Y...

Page 2: ......

Page 3: ...y and its Use 7 VI Charging and Discharging the Troppo Battery 7 VII Battery Installation Location and Equipment 9 VIII Battery Connection and Operation 11 IX Transportation 13 X Troppo Battery Specif...

Page 4: ...high quality industry standard Amphenol Surlok DC connectors for safe and easy connection of the DC battery cables These have a significant safety advantage over legacy systems using exposed bolted te...

Page 5: ...maximum stacking height is 8 batteries when in RedEarth s transport box Damaged battery A damaged battery must not be used and returned to RedEarth as soon as possible or disposed of via a recycling...

Page 6: ...PO battery has been specifically designed to be self managing This means it does not need to communicate with the inverter charger to operate There is no need for multiple communication wires between...

Page 7: ...y available in a 48Vdc model and is sized to be installed in standard 19 inch racks RedEarth also provides its own range of purpose built 19 racks for this The TROPPO 4841 battery is certified to IEC6...

Page 8: ...ng where the connection and control components are located Battery Weight 42 5kg Battery Dimensions 438mm wide x 725mm deep x 88mm high Package Weight with Battery 44 0kg Package Dimensions 540mm wide...

Page 9: ...3 800mAh and a voltage of 3 2Vdc There are 16 cells in series which provides a battery voltage of 51 2V 48V nominal There are also 21 cells in parallel adding up to 336 cells for the battery and a to...

Page 10: ...ffers a wide range of training options for our partners including regular training courses run at our Brisbane facility on site for our larger customer as well as online training options The battery s...

Page 11: ...ltage disable float otherwise set to 53 5V Float voltage charging is not required Equalisation Voltage disable equalisation otherwise set to 53 5 VDC Avoid equalising the TROPPO battery Inverter Shut...

Page 12: ...nt of a 48Vdc installation RACK19 can be supplied as an IP20 cabinet to house with a maximum of 8 or 20 batteries for indoor applications RACK19 can be configured with a built in Battery Breaker 160 2...

Page 13: ...as specified in this manual the internal BMS will stop the operation of the battery if the cell temperatures move outside their specifications The temperature and humidity remain relatively constant t...

Page 14: ...ltages closed together by charging or discharging one of the batteries before connecting in parallel 2 Switch OFF the OVERCURRENT PROTECTION MCB of all batteries 3 Next ensure the separate Main Batter...

Page 15: ...ual This is a critical step If you are unsure of the settings required contact RedEarth as damage to batteries caused by incorrect settings of the inverter charger will affect your warranty 8 If you h...

Page 16: ...or in pallets of batteries up to eight batteries high The batteries are shipped with The built in battery switch in the off position no voltage on the battery terminals The batteries in a partial sta...

Page 17: ...voltage up to its maximum charge voltage in a laboratory environment 40 0 58 4VDC Nominal DC Voltage 51 2V 3 2V per cell LFP type x 16 cells in series 16S 51 2VDC Maximum Discharge Current 63A Limite...

Page 18: ...a Physical Characteristics Battery mounting options In a standard 19 rack or horizontally vertically or on either side RedEarth can provide its pre wired RACK19 system with built in main battery break...

Page 19: ...provide the surge current needed to start an inverter with up to 14 600uF of capacitors on the DC side High temperature discharge protection 60 5 C Battery will not discharge if the two temperature se...

Page 20: ...ate If you are to add extra capacity the battery must be of the same type part number and specification Before adding the new battery the original battery bank and the new battery must be bought up to...

Page 21: ...gether with the required battery cables Some parameters of the inverter charger may need to be adjusted to get the best performance from the new larger battery bank e g increase the charging current s...

Page 22: ...instead of in parallel 2 Connecting the battery to incompatible equipment e g 12V battery charger 3 Incorrect inverter and or charger settings 4 Disassembling battery 5 Incorrect battery bank sizing...

Page 23: ...RedEarth Energy Storage Ltd 15 Fienta Place Darra Brisbane QLD 4076 Australia RedEarth office Technical support Email 07 3279 6707 1800 733 637 0487 002 451 info redearth energy...

Page 24: ......

Reviews: