background image

1

PXU 

Temperature/Process Controller

Installation Guide

See the Red Lion website at www.redlion.net for a complete 

user manual.

SPECIFICATIONS

POWER

:

Line Voltage Models

:

100 to 240 VAC -20/+8 %, 50/60 Hz, 5 VA

Low Voltage Models

:

DC Power: 24 VDC, ±10%, 5 W

INPUT CAPABILITIES

:

Thermocouple Inputs

:

Types: T, E, J, K, R, S, B, N, L, U, and TXK

RTD Inputs

:

Type: 2 or 3 wire, 2 wire can be compensated for lead wire resistance

Excitation: 180 

µ

A  typical

Input Type:

100 

Ω

 Pt alpha = .00385

100 

Ω

 Pt alpha = .00392

120 

Ω

 Nickel alpha = .00672

50 

Ω

 Copper alpha = .00428

Process Input Ranges

:

0-5 VDC

0-20 mA

0-50 mV

0-10 VDC

4-20 mA

USER INPUT (Optional)

Contact/NPN Open Collector Input

  ON Resistance 1 K

Ω 

max.

  OFF Resistance 100 K

Ω 

min.

Response Time

: 1 sec max 

Functions

: Programmable

OUTPUT

:

CONTROL RELAY OUTPUTS (OUT1/OUT2)

:

Type:

 Form A

Contact Rating:

 5 A @ 250 VAC

Contact Isolation to all I/O: 

2300 VAC for 1 min.

CONTROL SSR DRIVE OUTPUT (OUT1)

:

Rating

: 12 VDC ± 10% @ 40 mA max.

CONTROL OUTPUT (OUT1) Analog Models

:

Analog Types

: 4 to 20 mA or 0 to 10 VDC

Isolation To Sensor & Communication Common

: 500 VDC for 1 min.

Compliance

: 10 VDC: 1 K

 load min.,  20 mA: 500 

 load max. 

ALARMS

: 2 relay alarm outputs.

Type:

 Form A or Form C, model and alarm dependent

Contact Rating:

 3 A @ 250 VAC

ENVIRONMENTAL CONDITIONS

:

Operating Temperature Range: 0 to 50 °C

Storage Temperature Range: -20 to 65 °C

Vibration Resistance: Operational 10 to 55 Hz, 1 g

Shock Resistance: Operational 30 g

Operating and Storage Humidity: 80% max relative humidity (non-

condensing) from 0°C to 50°C

Altitude: Up to 2000 meters

CERTIFICATIONS AND COMPLIANCES

:

CE Approved

EN 61326-1 Immunity to Industrial Locations

Emission CISPR 11 Class A

EN 61010-1

RoHS Compliant

UL Listed: File #E179259

IP65 Enclosure rating (Face only)

CONNECTIONS

: Wire-clamping screw terminals

CONSTRUCTION

: Black plastic alloy case and panel latch. Black plastic 

textured bezel with transparent display window. 

Controller meets IP65 

requirements for indoor use when properly installed. 

Installation Category II, 

Pollution Degree 2.

WEIGHT

1/4 DIN: 11.0 oz (312 g) 

1/8 DIN: 7.8 oz (221 g) 

1/16 DIN: 5.3 oz (150 g)

Drawing No.  LP0951C
Released  05/14

C

US LISTED

UL

R

13RW

PROCESS CONTROL EQUIPMENT

(48.0)

1.89

1.89

 (48.0)

(45.0)

1.77

1.77

(45.0)

6

5

4

3

2

1

12

11

10

9

8

7

15

14

13

16
17
18

0.26

(6.70)

3.14 (79.70)

0.31

(7.80)

0.47 (11.88)

0.83 (21.0)

DIMENSIONS  In inches (mm) - 1/16 DIN

PANEL CUT-OUT

CAUTION: Risk of electric shock. 

When the power is on, DO NOT touch the AC terminals, an electric shock may 

occur. Make sure the power is disconnected when you check the input power supply.

1. Prevent dust or metallic debris from falling into the controller and causing malfunctions. DO 

NOT modify the controller.

2. The PXU is an open-type device. Make sure it is installed in an enclosure free of dust and 

humidity in case of an electric shock.

3. Wait for one minute after the power is switched off to allow the unit to discharge. DO NOT touch 

the internal wiring within this period of time.