GENERAL DESCRIPTION

The PAXLA is a versatile meter available as a DC volt, current, or process 

meter with scaling and dual Form C relay outputs. The meter is programmed 
through the front panel buttons and the use of jumpers. The RST Key will also 
function as a front panel display reset.

Once the front panel programming is complete, the buttons can be disabled 

by a user input setting. The meter has been specifically designed for harsh 
industrial environments. With a NEMA 4X/IP65 sealed bezel and extensive 
testing to meet CE requirements, the meter provides a tough yet reliable 
application solution.

SAFETY SUMMARY

All safety regulations, local codes and instructions that appear in this and 

corresponding literature, or on equipment, must be observed to ensure personal 
safety and to prevent damage to either the instrument or equipment connected to 
it. If equipment is used in a manner not specified by the manufacturer, the 
protection provided by the equipment may be impaired.

ORDERING INFORMATION

MODEL NO. DESCRIPTION

PART NUMBER

PAXLA

Volt/Current/Process Meter with Dual Relay Output

PAXLA000

UL Listed Volt/Current/Process Meter with Dual 
Relay Output

PAXLA0U0

PAXLBK

Unit Label Kit Accessory

PAXLBK10

SPECIFICATIONS

1. 

DISPLAY

: 5 digit, 0.56" (14.2 mm) intensity adjustable Red LED (-19999 to 

99999)

2. 

POWER REQUIREMENTS

:

AC POWER: 50 to 250 VAC 50/60 Hz, 12 VA

Isolation: 2300 Vrms for 1 min. to all inputs and outputs

DC POWER: 21.6 to 250 VDC, 6 W
DC Out: +24 VDC @ 100 mA if input voltage is greater than 50 VAC/VDC

 +24 VDC @ 50 mA if input voltage is less than 50 VDC

3. 

INPUT RANGES

: Jumper Selectable

D.C. Voltages

: 200 mV, 2 V, 20 V, 200 V, 10 V

D.C. Currents

: 200 

A, 2 mA, 20 mA, 200 mA

D.C. Process

: 4 to 20 mA, 1 to 5 VDC, 0/1 to 10 VDC

4.

 OVERRANGE/UNDERRANGE INDICATION:

Input Overrange Indication

:  “



”.

Input Underrange Indication

:  “



”.

Display Overrange/Underrange Indication

: “

.....

”/“-

.....

” 

5.

 A/D CONVERTER: 

16 bit resolution

6. 

UPDATE RATES

:

A/D conversion rate: 20 readings/sec.
Display update: 500 msec min.

  5 DIGIT, 0.56" HIGH RED LED DISPLAY

  PROGRAMMABLE SCALING AND DECIMAL POINTS

  PROGRAMMABLE USER INPUT

  DUAL 5 AMP FORM C RELAY

  UNIVERSALLY POWERED

  NEMA 4X/IP65 SEALED FRONT BEZEL

  OPTIONAL CUSTOM UNIT OVERLAY W/ BACKLIGHT

  MINIMUM AND MAXIMUM DISPLAY CAPTURE

MODEL PAXLA - PAX LITE DC VOLT/CURRENT/PROCESS METER

DIMENSIONS  In inches (mm)

Bulletin No.  PAXLA-B
Drawing No.  LP0722
Released  04/09

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net

CAUTION: Risk of Danger.

Read complete instructions prior to 

installation and operation of the unit.

CAUTION: 

Risk of electric shock.

INPUT 

RANGE

INPUT 

IMPEDANCE

MAX 

INPUT 

SIGNAL

RESOLUTION

TEMP. 

COEFFICIENT

200 mV

0.1% of span

1.033 M

75 VDC

10 

V

70 ppm /°C

2 V

0.1% of span

1.033 M

75 VDC

0.1 mV

70 ppm /°C

20 V

0.1% of span

1.033 M

250 VDC

1 mV

70 ppm /°C

10 V

200 V

0.1% of span

0.1% of span

538 K

1.033 M

75 V

250 VDC

1 mV

10 mV

70 ppm /°C

70 ppm /°C

ACCURACY @ 

23 

°

C LESS 

THAN 85% RH

INPUT 

RANGE

INPUT 

IMPEDANCE

MAX 

INPUT 

SIGNAL

RESOLUTION

TEMP. 

COEFFICIENT

200 



0.1% of span

1.111 K

15 mA

10 nA

70 ppm /°C

2 mA

0.1% of span

111 

50 mA

0.1 

A

70 ppm /°C

20 mA

0.1% of span

11 

150 mA

A

70 ppm /°C

200 mA

0.1% of span

500 mA

10 

A

70 ppm /°C

ACCURACY @ 

23 

°

C LESS 

THAN 85% RH

INPUT RANGE

SELECT RANGE

4 - 20 mA

Use the 20 mA range

1 - 5 VDC

Use the 10V range

1 - 10 VDC

Use the 10V range

CC

US LISTED

US LISTED

UL

R

IND. CONT. EQ.

51EB

For Model No. PAXLA0U0 Only

Summary of Contents for PAXLA

Page 1: ...ater than 50 VAC VDC 24 VDC 50 mA if input voltage is less than 50 VDC 3 INPUT RANGES Jumper Selectable D C Voltages 200 mV 2 V 20 V 200 V 10 V D C Currents 200 A 2 mA 20 mA 200 mA D C Process 4 to 20...

Page 2: ...ol and Laboratory use Notes 1 Criterion A Normal operation within specified limits 2 Criterion B Temporary loss of performance from which the unit self recovers 14 WEIGHT 10 4 oz 295 g Class A EN 5501...

Page 3: ...protection Install line filters on the power input cable to the unit to suppress power line interference Install them near the power entry point of the enclosure The following EMI suppression devices...

Page 4: ...2 Terminal 14 NO 2 Terminal 15 Relay 2 Common USER 8 USER COM 9 USER USER COMM 9 8 10 N C 1 COMM 1 12 11 N O 1 13 14 15 N C 2 N O 2 COMM 2 Sinking Logic Sourcing Logic Current Signal self powered Term...

Page 5: ...ntinue by accessing additional modules SELECTION VALUE ENTRY For each parameter the display alternates between the present parameter and the selections value for that parameter The SEL and RST buttons...

Page 6: ...ay Value For Scaling Point 1 User Input Assignment Input Range PAR User Input Function Input Value for Scaling Point 2 Display Value For Scaling Point 2 Scaling Style Display Offset Value User Input A...

Page 7: ...to perform any of the Factory Service Operations shown below FACTORY SERVICE OPERATIONS Enables the Minimum Display Capture capability The PAXLA uses stored calibration values to provide accurate meas...

Page 8: ...hese custom units is activated by this parameter Current Calibration 1 Connect the negative lead of a precision DC current source with an accuracy of 0 01 or better to the COMM terminal Leave the posi...

Page 9: ...cting Unbalanced Hys OUTPUT STATE OFF ON Hys SP SP Hys OFF TRIGGER POINTS High Acting Unbalanced Hys Enter the setpoint output to be programmed The in the following parameters will reflect the chosen...

Page 10: ...nt per the Setpoint Action shown in Setpoint Output Figures Latch means that the output can only be turned off by the front panel RST button or user input manual reset or meter power cycle When the us...

Page 11: ...SEL 4 SPt Act n SPt n HYS n tON n tOF n rSt n rEn n Standby Operation Stb n Front Panel Reset Enable Front Panel Display Select Enable Display Update Time dSP t SEL rSt 3 dSP Display Intensity Level d...

Page 12: ...yer its employees or sub contractors are or may be to any extent liable including without limitation penalties imposed by the Consumer Product Safety Act P L 92 573 and liability imposed upon any pers...