background image

1

!

2 LINE X 20 CHARACTER LIQUID CRYSTAL DISPLAY                   

WITH LED BACKLIGHT

!

100 ALARM POINT LOGGER

!

RECIPE HANDLING

!

UNLIMITED PASSWORD PROTECTION

!

REAL TIME CLOCK, BATTERY BACKED

!

EXPRESSION EVALUATION

!

32-BIT MATH (CL050000), 32 BIT / FLOATING POINT MATH

(CL050010)

!

DIRECT PLC COMMUNICATION

!

NEMA 4/IP65 

DESCRIPTION

The Paradigm operator interface Model CL05 was designed to meet the

industrial demands of application power, versatility, reliability, and ease of use.
The CL05 has provision, common to all Paradigm Family products, allowing
for future product upgrades as new options and capabilities are developed.

SAFETY SUMMARY

All safety related regulations, local codes and instructions that appear in the

manual or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.

Do not use this unit to directly command motors, valves, or other actuators

not equipped with safeguards. To do so, can be potentially harmful to persons
or equipment in the event of a fault to the unit.

WARNING - EXPLOSION HAZARD - SUBSTITUTION
OF COMPONENTS MAY IMPAIR SUITABILITY FOR
CLASS I, DIVISION 2 / CLASS II, DIVISION 2 / CLASS III, DIVISION 2

SPECIFICATIONS

1. 

POWER REQUIREMENTS

: 11 to 30 VDC @ 2.5 W

Power Up Current

: 2.5 A for 1 msec max.

Must use a Class 2 or SELV rated power supply.

2. 

DISPLAY

: 2 lines of 20 characters, 0.197" (5 mm) high liquid crystal display

with bright LED backlight 

3. 

KEYPAD

: 3 screen legendable soft keys, numeric pad with raise, lower,

next, previous, enter, delete, exit, alarms and mute keys.

4. 

MEMORY

: 128 K(64 K user) battery backed RAM (Battery life expectancy

7 years 50/50 on/off cycle) Optional factory fit expansion to 512 K(448 K user).

5. 

PHYSICAL DIMENSIONS

: L = 6.69" (170 mm), H = 5.12" (130 mm), 

D = 2.2" (56 mm.)

6. 

CONSTRUCTION

: Steel rear metal enclosure with NEMA 4/IP65

aluminum front plate when correctly fitted with the gasket provided. This unit is
rated for NEMA 4/IP65 indoor use. Installation Category I, Pollution Degree 2.

7. 

MOUNTING REQUIREMENTS

: Max. panel thickness is 0.375"

(9.5 mm). For NEMA 4/IP65 sealing, a steel panel with a minimum thickness
of 0.125" (3.175 mm) is recommended

MODEL CL05 - PARADIGM  2 X 20 LCD OPERATOR INTERFACE TERMINAL

DIMENSIONS  In inches (mm)

PANEL CUT-OUT

MODEL NO. DESCRIPTION

Communication Cables

LCD, 2 X 20, 3 Soft keys, 512 K memory

LCD, 2 X 20, 3 Soft keys, 128 K memory

P895xxxZ

CL050010

BAL3R004

SFEDT

CL050000

CL05

ORDERING INFORMATION

Bulletin No.  CL05-F
Drawing No.  LP0417
Released  3/02

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion-controls.com

CAUTION: Read complete instructions prior to

installation and operation of the unit.

FOR USE IN HAZARDOUS LOCATIONS:

Class I, Division 2, Groups A, B, C, and D
Class II, Division 2, Groups F and G
Class III, Division 2

63YN

LABORATORY EQUIPMENT

Battery Replacement
EDICT-97 Development Kit. Includes Software,
Manual and 9-pin RS232 Programming cables

PART NUMBER

Reviews: