red lion ITMS4037 Manual Download Page 1

GENERAL DESCRIPTION

The ITMS4037 Intelligent Temperature to MODBUS™ Conditioner with

Alarms accepts a wide range of temperature sensors (thermocouple and RTD
elements), and converts the signal into a register format that can be read using
either ASCII or RTU MODBUS protocol.

The ITMS allows a choice of either Fahrenheit or Celsius readout with 0.1 or

1 degree of resolution. An offset value can be programmed to scale the input
signal to meet most process requirements. Additionally, two setpoint values can
be entered for dual relay process monitoring alarms.

The ITMS is programmed with Windows™  based SFIMS software. The

software allows configuration, calibration, and storage of ITMS program files.
Additionally, all setup parameters can be interrogated and modified through
MODBUS register and coil commands.

The RS485 port allows the ITMS to be multidropped, with Baud rates up to

38400. The CBPRO007 programming cable converts the RS232 port of a PC to
RS485, and is terminated with an RJ-11 connector. The bidirectional capability
of the CBPRO007 allows it to be used as a permanent interface cable as well as
a programming cable.

The ITMS’s two relay alarms can be configured independently for absolute

high or low acting with balanced or unbalanced hysteresis. Alarm 2 can also be
configured for deviation and band alarms. In these modes, Setpoint 2 tracks
Setpoint 1. Adjustable alarm trip delays can be used for delaying output
response. The alarms can be programmed for Automatic or Latching. Latched
alarms can be reset with a serial command or a user input. A standby feature
suppresses the alarm during power-up until the temperature stabilizes outside
the alarm region. Standby eliminates power-up tripping for low acting alarms.
A user input can be used to set and reset non-latching alarms. The output relays
can also be manually controlled with register commands.

The module’s high density packaging and DIN rail mounting saves time and

panel space. The module is equipped with a universal mounting foot for
attachment to standard DIN rails, including top hat (T) profile or G profile rail.

SAFETY SUMMARY

All safety related regulations, local codes and instructions that appear in the

manual or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.

1

O

TEMPERATURE TO MODBUS CONVERSION

O

ACCEPTS THERMOCOUPLE, RTD, mV OR RESISTANCE

SIGNALS

O

PROCESSOR BASED SCALING

O

PC CONFIGURATION SOFTWARE

O

DUAL SETPOINT RELAY ALARMS

O

FOUR WAY SIGNAL ISOLATION

MODEL ITMS - INTELLIGENT TEMPERATURE TO MODBUS CONDITIONER W/ ALARMS

MODEL

ITMS

DESCRIPTION

Temperature to MODBUS Conditioner w/Alarms

PART NUMBER

ITMS4037

CBPRO

SFIMS

Programming Interface Cable

PC Configuration Software for Windows

CBPRO007

SFIMS

CBJ

Cable RJ11 to Unterminated 7 foot length

CBJ11A07

RJ Connector to Terminal Adapter

Cable RJ11 to RJ11 6 inch jumper

DRRJ11T6

CBJ11BD5

ORDERING INFORMATION

DIMENSIONS  In inches (mm)

CAUTION: Read complete

instructions prior to installation

and operation of the unit.

CAUTION: Risk of electric shock.

Bulletin No.  ITMS-B
Drawing No.  LP0494
Released  1/07

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net

UL Recognized Component,
File # E179259

Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com

Summary of Contents for ITMS4037

Page 1: ...izes outside the alarm region Standby eliminates power up tripping for low acting alarms A user input can be used to set and reset non latching alarms The output relays can also be manually controlled...

Page 2: ...ME11540 0702001 Issued by Underwriters Laboratories Inc IEC 1010 1 EN 61010 1 Safety requirements for electrical equipment for measurement control and laboratory use Part 1 ELECTROMAGNETIC COMPATIBILI...

Page 3: ...1 MHz c Connect the shield to common of the unit and leave the other end of the shield unconnected and insulated from earth ground 2 Never run Signal or Control cables in the same conduit or raceway w...

Page 4: ...ay be compensated by programming a temperature offset RELAY OUTPUT CONNECTIONS Relay 1 Relay 1 is a Form A output relay Wiring is connected between terminal 9 COMM common and terminal 8 N O the normal...

Page 5: ...n menu Scale Select Fahrenheit or Celsius In linear millivolt or resistance modes this has no effect Resolution For thermocouple RTD or linear resistance modes low resolution selects whole degrees or...

Page 6: ...Setpoint Alarm Figures Trigger Points Trigger Points are the Process Values where the alarm state changes Their values cannot be entered directly but are shown as a reference in the SFIMS software The...

Page 7: ...he SFIMS software will update the category display to these settings Communications Diagnostics The Communications Diagnostics function can be used to troubleshoot systems that are experiencing commun...

Page 8: ...1200 2400 4800 9600 19200 38400 Data Bits 7 or 8 Parity odd even or none Note The CBPRO007 download cable DOES NOT typically require power In most cases it will derive its power from the PC If communi...

Page 9: ...00 ohm resistor CJ calibration should be performed with a TC of known accuracy of types T E J K C or N only When using SFIMS for calibration select the type of calibration to be performed and press th...

Page 10: ...EM CAUSE REMEDIES Green LED will not light Module power Check module power connections and voltage level Process Value not changing Input signal Check input signal connections and signal level Incorre...

Page 11: ...ge Issued when a write to coil or register is attempted with an invalid string length CHECKSUM ERRORS 1 Calibration checksum covers the E2 PROM that contains calibration values for all ranges When a c...

Page 12: ...Write 0 1 degree 1 0 1 degree 40003 Floating Point LO N A N A Read Only IEEE Standard 754 Floating Decimal Point low order of Temperature Value Allows 32 bit accuracy for external monitoring 40013 Use...

Page 13: ...600 0 1 0 1 1 1 0 0 1 39 B9 RTU 8O1 1200 0 1 0 1 1 1 0 1 0 3A BA RTU 8O1 2400 0 1 0 1 1 1 0 1 1 3B BB RTU 8O1 4800 0 1 0 1 1 1 1 0 0 3C BC RTU 8O1 9600 0 1 0 1 1 1 1 0 1 3D BD RTU 8O1 19200 0 1 0 1 1...

Page 14: ...1 1 0 1 1 1 1 0 5E DE ASCII 7O1 38400 0 1 1 0 1 1 1 1 1 5F DF ASCII 8N1 300 0 1 1 1 0 0 0 0 0 60 E0 ASCII 8N1 600 0 1 1 1 0 0 0 0 1 61 E1 ASCII 8N1 1200 0 1 1 1 0 0 0 1 0 62 E2 ASCII 8N1 2400 0 1 1 1...

Page 15: ...15 This page intentionally left blank Courtesy of Steven Engineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www stevenengineering com...

Page 16: ...other matters which Buyer its employees or sub contractors are or may be to any extent liable including without limitation penalties imposed by the Consumer Product Safety Act P L 92 573 and liabilit...

Reviews: