red lion ITMA DC Quick Start Manual Download Page 1

1

!

USER PROGRAMMABLE INPUT
(Thermocouple types J, K, T, & E, or millivolt)

!

MICROPROCESSOR CONTROLLED

!

SIMPLE ADJUSTABLE RANGE SETTING (Using Input Signal)

!

THERMOCOUPLE BREAK DETECTION

!

MOUNTS ON “T” AND “G” STYLE DIN RAILS

!

3-WAY ELECTRICAL ISOLATION (POWER/INPUT/OUTPUT)

!

MULTIPLE ANALOG OUTPUTS (0 to 20 mA, 4 to 20 mA, and 0 to
10 VDC)

!

WIDE OPERATING TEMPERATURE RANGE (-25°C to 75°C)

!

POWER & MEMORY ERROR INDICATION

!

9 to 32 VDC POWERED

DESCRIPTION

The ITMA accepts a thermocouple or millivolt input and converts it into a

voltage or current output. The voltage or current output is linearly proportional
to the temperature or millivolt input. This output is ideal for interfacing to
indicators, chart recorders, controllers, or other instrumentation equipment. 

The ITMA is DC powered. The DC power input is isolated from the signal

input and analog output. The unit scales the analog output proportionally to the
thermocouple or millivolt input signal. The analog output may be configured for
one of the following: 0 to 20 mA, 4 to 20 mA, or 0 to 10 VDC. Making the
signal conversion with the ITMA to a current output signal, makes the signal
less susceptible to noise interference and allows accurate transmission over long
distances. The 3-Way isolation allows the use of grounded thermocouples which
can provide additional noise reduction benefits.

The ITMA uses a ten position DIP switch to accomplish the input sensor

configuration, range selection, and unit calibration. A simple range setting
technique (Field Calibration) is used so the actual input signal adjusts the output
for scaling. This technique eliminates the need for potentiometers which are
vulnerable to changes due to vibration.

The unit is equipped with a universal mounting foot for attachment to

standard DIN style mounting rails, including top hat rail (T) according to EN 50
022 - 35 

×

7.5 and 35 

×

15, and (G) profile according to EN 50 035 - G 32.

SAFETY SUMMARY

All safety related regulations, local codes and instructions that appear in the

manual or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.

SPECIFICATIONS

1.

POWER

: 9 to 32 VDC; 1.75 W The power supply must have 300 mA for

200 msec. surge capacity.

2.

INPUT

: J, K, T, E, mV [selectable via DIP switch]

3. 

OUTPUT

: All output signals scaled linearly using temperature or mV input.

Unit is shipped set for 4 to 20 mA output. 4 to 20 mA or 0 to 20 mA selected
via internal jumper.

Voltage Output Compliance

:

0 to 10 VDC across min 1 K

load (10 mA)

20 mV peak to peak max. ripple (for frequencies up to 120 Hz)

Current Output Compliance

:

0 to 20 mA through max. 600

load (12 VDC)

4 to 20 mA through max. 600

load (12 VDC)

15 mV peak to peak max. ripple across 600

load (for freq. up to 120 Hz)

4.

TC BREAK DETECTION

: Nominal values shown in the following order:

(0 to 20 mA, 4 to 20 mA, and 0 to 10 VDC).

Upscale

: 22.9 mA, 22.5 mA, and 11.5 VDC

Downscale

: -0.5 mA, 3.5 mA, and -0.4 VDC

5.

RESPONSE TIME

: 400 msec (to within 99% of final value w/step input;

typically, response is limited to response time of probe.)

6.

TEMPERATURE EFFECTS

:

Temperature Coefficient

:  

±

0.025% of input range per °C

Ice Point Compensation

:  

±

0.75°C for a 50°C change in temperature

7.

DIELECTRIC WITHSTAND VOLTAGE

: 1500 VAC for 1 minute

Working Voltage

: 50 VAC

Power input to Signal input, Power input to Signal output, & Signal input to
Signal output.

8.

RANGE & ACCURACY

: (12 Bit resolution)

Accuracy

±

( 0.075% Range + 0.25°C [Conformity] + 0.50°C [Ice Point])

at 23°C after 20 min. warm-up, conforming to ITS-90.

Note: TC Conformity and Ice Point do not apply to mV input

MODEL ITMA DC - 

INTELLIGENT THERMOCOUPLE MODULE WITH ANALOG OUTPUT

DIMENSIONS  In inches (mm)

CAUTION: Read complete instructions prior

to installation and operation of the unit.

Bulletin No.  ITMA3-B
Drawing No.  LP0405
Released  6/03

Tel +1 (717) 767-6511
Fax +1 (717) 764-6587
www.redlion-controls.com

Summary of Contents for ITMA DC

Page 1: ...32 SAFETY SUMMARY All safety related regulations local codes and instructions that appear in the manual or on equipment must be observed to ensure personal safety and to prevent damage to either the i...

Page 2: ...ld screen pigtail connection should be made as short as possible The connection point for the shield depends somewhat upon the application Listed below are the recommended methods of connecting the sh...

Page 3: ...nt output nominally within a 2 5 deviation range To select 0 to 20 mA output you must open the case and cut the wire jumper The jumper is located to the left side of the board as shown in the drawing...

Page 4: ...ation To abort this calibration and reset to the previous settings set the FIELD CAL switch 2 OFF prior to the final OFF setting of the OUTPUT CAL switch Step 1 13 and turn off power Wait 5 seconds an...

Page 5: ...FIELD CAL switch 2 ON 1 Connect a precision thermometer accuracy of 0 1 C to the unused terminal beside the TC Input terminals 2 Allow 5 minutes for the temperature to equalize 3 Using the temperatur...

Page 6: ...o install the ITMA on a G style DIN rail angle the module so that the upper groove of the foot catches under the lip of the top rail Push the module toward the rail until it snaps into place To remove...

Page 7: ...7 This page intentionally left blank...

Page 8: ...ity for any affirmation promise or representation with respect to the products The customer agrees to hold Red Lion Controls harmless from defend and indemnify RLC against damages claims and expenses...