22 LP1109
CONFIGURATION / OPERATING THE FUNCTION KEYS
Documentation for routing diagram.
In general:
When configuring the IAMS devices, you will be guided through all parameters
and you can choose the settings which fit the application. For each menu there
is a scrolling help text which is automatically shown in line 3 on the display.
Configuration is carried out by using the 3 function keys:
1
will increase the numerical value or choose the next parameter
2
will decrease the numerical value or choose the previous parameter
3
will accept the chosen value and proceed to the next menu
When configuration is completed, the display will return to the default state 1.0.
See the reference diagram on page 28.
Pressing and holding
3
will return to the previous menu or return to the default
state (1.0) without saving the changed values or parameters.
If no key is activated for 1 minute, the display will return to the default state
(1.0) without saving the changed values or parameters.
Further explanations:
Fast setpoint adjustment and relay test:
These menus allow you to make a
quick setpoint change and relay test when the FastSet menu is activated. This
function can only be activated when the relays are set for setpoint function
and are controlled by a setpoint.
Pressing
1
and
2
simultaneously will activate a relay test and change the state
of the relay.
Pressing
3
will save the setpoint change.
Holding down
3
for more than 1 second will return the unit to the default state
without saving the setpoint change.
Password protection:
Programming access can be blocked by assigning a
password. The password is saved in the transmitter in order to ensure a high
degree of protection against unauthorised modifications to the configuration.
Default password 2008 allows acces to all configuration menus.