background image

1

12.10 (307.3)

8.20

(208.3)

2.06 (52.4)

8.4

(215)

(MOUNTING CLIPS INSTALLED)

12.3 (314)

2.97 (76)

Module sold

separately

GRAPHITE™ SERIES 

12" Color Touchscreen Operator Interface

Installation Guide

DIMENSIONS  In inches (mm)

See the Red Lion website at www.redlion.net or the enclosed 

USB thumbdrive for full user manual, Crimson software and 

software manual.

SAFETY SUMMARY

All safety related regulations, local codes and instructions that appear in this 

literature or on equipment must be observed to ensure personal safety and to 

prevent damage to either the instrument or equipment connected to it. If 

equipment is used in a manner not specified by the manufacturer, the protection 

provided by the equipment may be impaired. Do not use this unit to directly 

command motors, valves, or other actuators not equipped with safeguards. To 

do so can be potentially harmful to persons or equipment in the event of a fault 

to the unit.        

ORDERING INFORMATION

DESCRIPTION

PART NUMBER

12" color touch screen, indoor use, 24 VDC powered

G12C0000

12" color touch screen, indoor use, 24 VDC powered, 

additional ethernet and serial port

G12C1100

SPECIFICATIONS

POWER

: +24 VDC ±20%

Typical Power HMI only: 

16 W

Maximum Power HMI only:  23 W

    HMI With Module(s): 

56 W

Must use a Class 2 circuit according to National Electrical Code (NEC), 

NFPA-70 or Canadian Electrical Code (CEC), Part I, C22.1 or a Limited 

Power Supply (LPS) according to IEC 60950-1 or Limited-energy circuit 

according to IEC 61010-1.

Power connection via removable three position terminal block.

ENVIRONMENTAL CONDITIONS

:

Operating Temperature Range: -20 to 60 °C

Storage Temperature Range: -20 to 70 °C

Vibration to IEC 68-2-6: Operational 5-500 Hz, 4 g

Shock to IEC 68-2-27: Operational 40 g (10 g, modules w/relays)

Operating and Storage Humidity: 0 to 85% max. RH non-condensing

Altitude: Up to 2000 meters

CERTIFICATIONS AND COMPLIANCES

:

CE Approved

EN 61326-1 Immunity to Industrial Locations

Emission CISPR 11 Class A

IEC/EN 61010-1

RoHS Compliant

UL Listed: File #E302106

UL Hazardous: File #E317425

Type 4X Indoor / IP66 Enclosure rating (Face only) for all models

CONNECTIONS

: High compression cage-clamp terminal block

Wire Strip Length: 0.3" (7.5 mm)

Wire Gauge Capacity: One 14 AWG (2.55 mm) solid,  

two 18 AWG (1.02 mm) or four 20 AWG (0.61 mm)

CONSTRUCTION

: Cast aluminum enclosure with NEMA 4X/IP66 rating for 

indoor use only when correctly fitted with the gasket provided. Installation 

Category II, Pollution Degree 2.

WEIGHT

: 5.06 lb. (2.29 Kg)

WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT 

EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF 

OR AREA IS KNOWN TO BE NON-HAZARDOUS.

WARNING - EXPLOSION HAZARD - SUBSTITUTION OF 

COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, 

DIVISION 2

CAUTION: Risk of Danger.

Read complete instructions prior to 

installation and operation of the unit.

CAUTION: 

Risk of electric shock.

Drawing No.  LP0910C
Released  07/14

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net

C

US LISTED

UL

R

IND. CONT. EQ.

34AD

FOR USE IN HAZARDOUS LOCATIONS: 

Class I, Division 2, Groups A, B, C, and D 

Class II, Division 2, Groups F and G 

Class III, Division 2

C

US

UL

R

LISTED

IND.CONT. EQ.

3PWL

Summary of Contents for GRAPHITE G12C0000

Page 1: ... IEC 61010 1 Power connection via removable three position terminal block ENVIRONMENTAL CONDITIONS Operating Temperature Range 20 to 60 C Storage Temperature Range 20 to 70 C Vibration to IEC 68 2 6 Operational 5 500 Hz 4 g Shock to IEC 68 2 27 Operational 40 g 10 g modules w relays Operating and Storage Humidity 0 to 85 max RH non condensing Altitude Up to 2000 meters CERTIFICATIONS AND COMPLIANC...

Page 2: ...y not more than 6 feet 1 8 m of cable between the supply and the operator interface Ideally the shortest length possible should be used The wire used to connect the operator interface s power supply should be at least 22 gage wire suitably rated for the temperatures of the environment to which it is being installed If a longer cable run is used a heavier gage wire should be used The routing of the...

Page 3: ...t to the DB9 COM port of your computer If you choose to make your own cable use the G12 Port Pin Out Diagram for wiring information The SD can be used to program a G12 by placing a configuration file and firmware on the SD card The card is then inserted into the target G12 and powered Refer to the Crimson literature for more information on the proper names and locations of the files USB DATA TRANS...

Page 4: ...after No warranties expressed or implied are created with respect to The Company s products except those expressly contained herein The Customer acknowledges the disclaimers and limitations contained herein and relies on no other warranties or affirmations BATTERY TIME KEEPING A battery is used to keep time when the unit is without power Typical accuracy at 25 C of the Graphite time keeping is les...

Reviews: