red lion DA70D Installation Manual Download Page 1

Install DA70D- B

Drawing No.  LP1094

Revised  03/2020

DA70D Intelligent Edge Controller With 

 

Scalable Inputs/Outputs 

Installation Guide

1

FOR USE IN HAZARDOUS LOCATIONS:

Class I, Division 2, Groups A, B, C, and D

T4

C

US

UL

R

LISTED

IND.CONT. EQ.

E317425

GENERAL DESCRIPTION

The modular 3-sled design of the DA70D allows for up to three 

communications sleds to be added as connectivity requirements 

change or new standards emerge. Rugged, field-installable PID 

control and I/O modules ensure a solution that adapts to meet 

almost any industrial application need.

CONTROLLER PACKAGE CHECKLIST

This product package should contain the items listed below. 

This list does not include any sleds that may have been ordered. 

If any items are missing or damaged, contact Red Lion immediately.

 - DIN Rail Mount DA70D Controller

 - Pre-installed Sled Carriage

 - Dust Cover

 - Installation Guide

SAFETY SUMMARY

All safety related regulations, local codes and instructions that 

appear in this document or on equipment must be observed to 

ensure personal safety and to prevent damage to either the 

device or equipment connected to it. 

Do not use these products to replace proper safety interlocking. 

No software-based device (or any other solid-state device) should 

ever be designed to be responsible for the maintenance of 

personnel safety or consequential equipment not equipped with 

safeguards. Red Lion disclaims any responsibility for damages, 

either direct or consequential, that result from the use of this 

equipment in a manner not specified.

SPECIFICATIONS

1. 

POWER REQUIREMENTS

:

The DA70D Controller must use a Class 2 circuit according to 

National Electrical Code (NEC), NFPA-70 or Canadian 

Electrical Code (CEC), Part I, C22.1 or a Limited Power Supply 

(LPS) according to IEC 60950-1 or Limited-energy circuit 

according to IEC 61010-1.

Power connection via removable three position terminal block.

Supply Voltage: 12 to 24 VDC +/- 15%, Class 2 source

INPUT VOLTAGE

12 V

24 V

Typical Power DA70D Controller only

4 W

4.5 W

Max Power DA70D Controller only

4.5 W

5 W

Available Power for Modules 

(Maximum of 10 modules)

43 W

45 W

Max Power DA70D Controller, with 

Sleds & USB

16 W

17 W

Max Power DA70D Controller with 

full accessories

59 W

62 W

CAUTION: Risk of Danger 

Read complete instructions prior to installation and 

operation of the unit.

ATTENTION : Risque de danger

 

Lire les instructions complètes avant l’installation et 

l’utilisation de l’appareil.

WARNING - EXPLOSION HAZARD - SUBSTITUTION 

OF COMPONENTS MAY IMPAIR SUITABILITY FOR 

CLASS I, DIVISION 2
AVERTISSEMENT - DANGER D’EXPLOSION - LE 

REMPLACEMENT DE COMPOSANTS PEUT NUIRE 

L’APTITUDE À LA CLASSE I, DIVISION 2

This equipment is suitable for use in Class I, Division 2, 

Groups A, B, C, D, or non-hazardous locations only.
Cet équipement est adapté à une utilisation dans des 

endroits de classe I, Division 2, Groupes A, B, C, D, ou 

dans des endroits non dangereux seulement.

WARNING - EXPLOSION HAZARD. NOT HOT 

SWAPPABLE. DO NOT REMOVE OR REPLACE WHILE 

CIRCUIT IS LIVE UNLESS THE AREA IS FREE OF 

IGNITIBLE CONCENTRATIONS.
AVERTISSEMENT - RISQUE D’EXPLOSION. NON 

ÉCHANGEABLE À CHAUD. NE PAS RETIRER OU 

REMPLACER SOUS TENSION SAUF SI LA ZONE EST 

EXEMPTE DE CONCENTRATIONS INFLAMMABLES.

 

z

Protocol conversion feature converts numerous protocols 

simultaneously 

 

z

Modular design supports up to three communications sleds 

and up to 10 PID control or I/O modules

 

z

Advanced web server with Javascript, Bootstrap, CSS and 

HTML5 support delivers operations visibility anywhere

 

z

Real-time data, event and security logging to microSD card or 

via ftp with cryptographic signature support

 

z

Industrial construction for reliable operation

 

z

Wide operating temperature range

II 3 G Ex ec IIC T4 Gc 

DEMKO 20 ATEX 2268X 

IECEx UL 20.0007X

Summary of Contents for DA70D

Page 1: ...ited energy circuit according to IEC 61010 1 Power connection via removable three position terminal block Supply Voltage 12 to 24 VDC 15 Class 2 source INPUT VOLTAGE 12 V 24 V Typical Power DA70D Cont...

Page 2: ...emperature Range 40 to 75 C Storage Temperature Range 40 to 85 C Operating and Storage Humidity 0 to 85 max RH non condensing Vibration to IEC 60068 2 6 Operational 5 500 Hz 2 g Shock to IEC 60068 2 2...

Page 3: ...effective at reducing EMI and increasing relay contact life b If a DC inductive load such as a DC relay coil is controlled by a transistor switch care must be taken not to exceed the breakdown voltage...

Page 4: ...tage rating This type of power supply provides isolation to accessible circuits from hazardous voltage levels generated by a mains power supply due to single faults Safety extra low voltage circuits s...

Page 5: ...EANING YELLOW solid Link established YELLOW flashing Data being transferred GREEN OFF 10 BASE T Communications GREEN ON 100 BASE TX Communications RS232 PORT S The DA70D has one or two RS232 serial po...

Page 6: ...L rating battery must be replaced with one listed in the Specifications RED LION CONTROLS TECHNICAL SUPPORT If for any reason you have trouble operating connecting or simply have questions concerning...

Page 7: ...4G LTE CAT4 Cellular Sled for EMEA SAARC APAC DA S00 CL9C4S EU000 802 11n Wi Fi Sled DA S00 WF10N0 AM000 1 Port USB 2 0 Host Sled DA S00 PN40U4 00000 Dual RS232 Ports Sled Isolated DA S00 PN2221 IS00...

Page 8: ...local state or federal law b The Company shall not be liable for a breach of the warranty set forth in paragraph a if i the defect is a result of Customer s failure to store install commission or mai...

Reviews: